Home / Quizzes / Electrical science and calculations
Electrical science and calculations quiz
Ohm's law, power, energy costs, three-phase, power factor, transformers, Zs, ring finals and voltage drop. Every answer is worked through so you can see the method.
1A resistance of 46 Ω is connected to a 230 V supply. What current flows?
Answer: 5 A
I = V ÷ R = 230 ÷ 46 = 5 A.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
2A resistance of 23 Ω is connected to a 230 V supply. What current flows?
Answer: 10 A
I = V ÷ R = 230 ÷ 23 = 10 A.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
3A resistance of 4 Ω is connected to a 12 V supply. What current flows?
Answer: 3 A
I = V ÷ R = 12 ÷ 4 = 3 A.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
4A resistance of 8 Ω is connected to a 24 V supply. What current flows?
Answer: 3 A
I = V ÷ R = 24 ÷ 8 = 3 A.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
5A resistance of 115 Ω is connected to a 230 V supply. What current flows?
Answer: 2 A
I = V ÷ R = 230 ÷ 115 = 2 A.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
6A resistance of 22 Ω is connected to a 110 V supply. What current flows?
Answer: 5 A
I = V ÷ R = 110 ÷ 22 = 5 A.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
7A resistance of 3 Ω is connected to a 9 V supply. What current flows?
Answer: 3 A
I = V ÷ R = 9 ÷ 3 = 3 A.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
8A resistance of 16 Ω is connected to a 48 V supply. What current flows?
Answer: 3 A
I = V ÷ R = 48 ÷ 16 = 3 A.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
9A resistance of 10 Ω is connected to a 230 V supply. What current flows?
Answer: 23 A
I = V ÷ R = 230 ÷ 10 = 23 A.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
10A resistance of 80 Ω is connected to a 400 V supply. What current flows?
Answer: 5 A
I = V ÷ R = 400 ÷ 80 = 5 A.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
11A current of 2 A flows through a resistance of 115 Ω. What is the voltage across it?
Answer: 230 V
V = I × R = 2 × 115 = 230 V.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
12A current of 0.5 A flows through a resistance of 24 Ω. What is the voltage across it?
Answer: 12 V
V = I × R = 0.5 × 24 = 12 V.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
13A current of 10 A flows through a resistance of 0.3 Ω. What is the voltage across it?
Answer: 3 V
V = I × R = 10 × 0.3 = 3 V.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
14A current of 5 A flows through a resistance of 0.46 Ω. What is the voltage across it?
Answer: 2.3 V
V = I × R = 5 × 0.46 = 2.3 V.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
15A current of 13 A flows through a resistance of 0.5 Ω. What is the voltage across it?
Answer: 6.5 V
V = I × R = 13 × 0.5 = 6.5 V.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
16A current of 32 A flows through a resistance of 0.25 Ω. What is the voltage across it?
Answer: 8 V
V = I × R = 32 × 0.25 = 8 V.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
17A current of 0.02 A flows through a resistance of 470 Ω. What is the voltage across it?
Answer: 9.4 V
V = I × R = 0.02 × 470 = 9.4 V.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
18A current of 4 A flows through a resistance of 57.5 Ω. What is the voltage across it?
Answer: 230 V
V = I × R = 4 × 57.5 = 230 V.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
19A load draws 13 A from a 230 V supply. Ignoring power factor, what power does it take?
Answer: 2990 W
P = V × I = 230 × 13 = 2990 W.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
20A load draws 10 A from a 230 V supply. Ignoring power factor, what power does it take?
Answer: 2300 W
P = V × I = 230 × 10 = 2300 W.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
21A load draws 4 A from a 230 V supply. Ignoring power factor, what power does it take?
Answer: 920 W
P = V × I = 230 × 4 = 920 W.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
22A load draws 2.5 A from a 12 V supply. Ignoring power factor, what power does it take?
Answer: 30 W
P = V × I = 12 × 2.5 = 30 W.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
23A load draws 0.5 A from a 230 V supply. Ignoring power factor, what power does it take?
Answer: 115 W
P = V × I = 230 × 0.5 = 115 W.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
24A load draws 20 A from a 400 V supply. Ignoring power factor, what power does it take?
Answer: 8000 W
P = V × I = 400 × 20 = 8000 W.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
25A load draws 0.5 A from a 5 V supply. Ignoring power factor, what power does it take?
Answer: 2.5 W
P = V × I = 5 × 0.5 = 2.5 W.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
26A load draws 32 A from a 230 V supply. Ignoring power factor, what power does it take?
Answer: 7360 W
P = V × I = 230 × 32 = 7360 W.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
27What is the design current of a 3 kW single-phase load at 230 V (power factor 1)?
Answer: 13.04 A
Ib = P ÷ V = 3000 ÷ 230 = 13.04 A.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
28What is the design current of a 9.2 kW single-phase load at 230 V (power factor 1)?
Answer: 40 A
Ib = P ÷ V = 9200 ÷ 230 = 40 A.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
29What is the design current of a 7.36 kW single-phase load at 230 V (power factor 1)?
Answer: 32 A
Ib = P ÷ V = 7360 ÷ 230 = 32 A.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
30What is the design current of a 2.3 kW single-phase load at 230 V (power factor 1)?
Answer: 10 A
Ib = P ÷ V = 2300 ÷ 230 = 10 A.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
31What is the design current of a 1.15 kW single-phase load at 230 V (power factor 1)?
Answer: 5 A
Ib = P ÷ V = 1150 ÷ 230 = 5 A.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
32What is the design current of a 10.8 kW single-phase load at 230 V (power factor 1)?
Answer: 46.96 A
Ib = P ÷ V = 10800 ÷ 230 = 46.96 A.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
33What is the design current of a 0.69 kW single-phase load at 230 V (power factor 1)?
Answer: 3 A
Ib = P ÷ V = 690 ÷ 230 = 3 A.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
34A current of 10 A flows through a conductor with a resistance of 0.5 Ω. How much power is lost as heat?
Answer: 50 W
P = I² × R = 10² × 0.5 = 50 W.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
35A current of 20 A flows through a conductor with a resistance of 0.1 Ω. How much power is lost as heat?
Answer: 40 W
P = I² × R = 20² × 0.1 = 40 W.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
36A current of 32 A flows through a conductor with a resistance of 0.05 Ω. How much power is lost as heat?
Answer: 51.2 W
P = I² × R = 32² × 0.05 = 51.2 W.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
37A current of 2 A flows through a conductor with a resistance of 10 Ω. How much power is lost as heat?
Answer: 40 W
P = I² × R = 2² × 10 = 40 W.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
38A current of 5 A flows through a conductor with a resistance of 2 Ω. How much power is lost as heat?
Answer: 50 W
P = I² × R = 5² × 2 = 50 W.
Source: Worked out from the formula in the explanation
Read more: Ohm's law calculator
39What is the total resistance of a 10 Ω and a 10 Ω resistor in parallel?
Answer: 5 Ω
R = (R1 × R2) ÷ (R1 + R2) = (10 × 10) ÷ (10 + 10) = 5 Ω. Parallel resistance is always less than the smallest one.
Source: Worked out from the formula in the explanation
Read more: Series and parallel resistors
40What is the total resistance of a 20 Ω and a 30 Ω resistor in parallel?
Answer: 12 Ω
R = (R1 × R2) ÷ (R1 + R2) = (20 × 30) ÷ (20 + 30) = 12 Ω. Parallel resistance is always less than the smallest one.
Source: Worked out from the formula in the explanation
Read more: Series and parallel resistors
41What is the total resistance of a 6 Ω and a 3 Ω resistor in parallel?
Answer: 2 Ω
R = (R1 × R2) ÷ (R1 + R2) = (6 × 3) ÷ (6 + 3) = 2 Ω. Parallel resistance is always less than the smallest one.
Source: Worked out from the formula in the explanation
Read more: Series and parallel resistors
42What is the total resistance of a 100 Ω and a 100 Ω resistor in parallel?
Answer: 50 Ω
R = (R1 × R2) ÷ (R1 + R2) = (100 × 100) ÷ (100 + 100) = 50 Ω. Parallel resistance is always less than the smallest one.
Source: Worked out from the formula in the explanation
Read more: Series and parallel resistors
43What is the total resistance of a 12 Ω and a 4 Ω resistor in parallel?
Answer: 3 Ω
R = (R1 × R2) ÷ (R1 + R2) = (12 × 4) ÷ (12 + 4) = 3 Ω. Parallel resistance is always less than the smallest one.
Source: Worked out from the formula in the explanation
Read more: Series and parallel resistors
44What is the total resistance of a 60 Ω and a 40 Ω resistor in parallel?
Answer: 24 Ω
R = (R1 × R2) ÷ (R1 + R2) = (60 × 40) ÷ (60 + 40) = 24 Ω. Parallel resistance is always less than the smallest one.
Source: Worked out from the formula in the explanation
Read more: Series and parallel resistors
45What is the total resistance of 10 Ω, 22 Ω and 47 Ω in series?
Answer: 79 Ω
In series you add them: 10 + 22 + 47 = 79 Ω.
Source: Worked out from the formula in the explanation
Read more: Series and parallel resistors
46What is the total resistance of 100 Ω, 220 Ω and 330 Ω in series?
Answer: 650 Ω
In series you add them: 100 + 220 + 330 = 650 Ω.
Source: Worked out from the formula in the explanation
Read more: Series and parallel resistors
47What is the total resistance of 1.5 Ω, 2.5 Ω and 4 Ω in series?
Answer: 8 Ω
In series you add them: 1.5 + 2.5 + 4 = 8 Ω.
Source: Worked out from the formula in the explanation
Read more: Series and parallel resistors
48What is the total resistance of 0.2 Ω, 0.35 Ω and 0.45 Ω in series?
Answer: 1 Ω
In series you add them: 0.2 + 0.35 + 0.45 = 1 Ω.
Source: Worked out from the formula in the explanation
Read more: Series and parallel resistors
49A 3 kW appliance runs for 2 hours. At 25p per kWh, what does that cost?
Answer: £1.50
Energy = 3 kW × 2 h = 6 kWh. Cost = 6 × 25p = 150 p, which is £1.50.
Source: Worked out from the formula in the explanation
Read more: Electricity cost calculator
50A 2 kW appliance runs for 5 hours. At 30p per kWh, what does that cost?
Answer: £3.00
Energy = 2 kW × 5 h = 10 kWh. Cost = 10 × 30p = 300 p, which is £3.00.
Source: Worked out from the formula in the explanation
Read more: Electricity cost calculator
51A 0.1 kW appliance runs for 10 hours. At 25p per kWh, what does that cost?
Answer: £0.25
Energy = 0.1 kW × 10 h = 1 kWh. Cost = 1 × 25p = 25 p, which is £0.25.
Source: Worked out from the formula in the explanation
Read more: Electricity cost calculator
52A 9.5 kW appliance runs for 0.5 hours. At 28p per kWh, what does that cost?
Answer: £1.33
Energy = 9.5 kW × 0.5 h = 4.75 kWh. Cost = 4.75 × 28p = 133 p, which is £1.33.
Source: Worked out from the formula in the explanation
Read more: Electricity cost calculator
53A 1.5 kW appliance runs for 4 hours. At 24p per kWh, what does that cost?
Answer: £1.44
Energy = 1.5 kW × 4 h = 6 kWh. Cost = 6 × 24p = 144 p, which is £1.44.
Source: Worked out from the formula in the explanation
Read more: Electricity cost calculator
54A 7 kW appliance runs for 3 hours. At 20p per kWh, what does that cost?
Answer: £4.20
Energy = 7 kW × 3 h = 21 kWh. Cost = 21 × 20p = 420 p, which is £4.20.
Source: Worked out from the formula in the explanation
Read more: Electricity cost calculator
55In a balanced star-connected three-phase system, the line voltage is 400 V. What is the phase (line to neutral) voltage, to the nearest volt?
Answer: 231 V
Phase voltage = line voltage ÷ √3 = 400 ÷ 1.732 = 230.9 V, so about 231 V.
Source: Worked out from the formula in the explanation
Read more: AC power calculator (single and three-phase)
56In a balanced star-connected three-phase system, the line voltage is 415 V. What is the phase (line to neutral) voltage, to the nearest volt?
Answer: 240 V
Phase voltage = line voltage ÷ √3 = 415 ÷ 1.732 = 239.6 V, so about 240 V.
Source: Worked out from the formula in the explanation
Read more: AC power calculator (single and three-phase)
57In a balanced star-connected three-phase system, the line voltage is 690 V. What is the phase (line to neutral) voltage, to the nearest volt?
Answer: 398 V
Phase voltage = line voltage ÷ √3 = 690 ÷ 1.732 = 398.4 V, so about 398 V.
Source: Worked out from the formula in the explanation
Read more: AC power calculator (single and three-phase)
58A balanced three-phase load takes 11 kW at 400 V with a power factor of 1. What is the line current, to 1 decimal place?
Answer: 15.9 A
I = P ÷ (√3 × VL) = 11000 ÷ (1.732 × 400) = 15.9 A.
Source: Worked out from the formula in the explanation
Read more: AC power calculator (single and three-phase)
59A balanced three-phase load takes 22 kW at 400 V with a power factor of 1. What is the line current, to 1 decimal place?
Answer: 31.8 A
I = P ÷ (√3 × VL) = 22000 ÷ (1.732 × 400) = 31.8 A.
Source: Worked out from the formula in the explanation
Read more: AC power calculator (single and three-phase)
60A balanced three-phase load takes 7.5 kW at 400 V with a power factor of 1. What is the line current, to 1 decimal place?
Answer: 10.8 A
I = P ÷ (√3 × VL) = 7500 ÷ (1.732 × 400) = 10.8 A.
Source: Worked out from the formula in the explanation
Read more: AC power calculator (single and three-phase)
61A balanced three-phase load takes 15 kW at 400 V with a power factor of 1. What is the line current, to 1 decimal place?
Answer: 21.7 A
I = P ÷ (√3 × VL) = 15000 ÷ (1.732 × 400) = 21.7 A.
Source: Worked out from the formula in the explanation
Read more: AC power calculator (single and three-phase)
62A load has an apparent power of 10 kVA and a power factor of 0.8. What is its true power?
Answer: 8 kW
True power = apparent power × power factor = 10 × 0.8 = 8 kW.
Source: Worked out from the formula in the explanation
Read more: Power factor correction calculator
63A load has an apparent power of 50 kVA and a power factor of 0.9. What is its true power?
Answer: 45 kW
True power = apparent power × power factor = 50 × 0.9 = 45 kW.
Source: Worked out from the formula in the explanation
Read more: Power factor correction calculator
64A load has an apparent power of 20 kVA and a power factor of 0.85. What is its true power?
Answer: 17 kW
True power = apparent power × power factor = 20 × 0.85 = 17 kW.
Source: Worked out from the formula in the explanation
Read more: Power factor correction calculator
65A load has an apparent power of 100 kVA and a power factor of 0.7. What is its true power?
Answer: 70 kW
True power = apparent power × power factor = 100 × 0.7 = 70 kW.
Source: Worked out from the formula in the explanation
Read more: Power factor correction calculator
66An ideal transformer steps 230 V down to 12 V. The primary has 1150 turns. How many turns does the secondary have, to the nearest turn?
Answer: 60
Vp ÷ Vs = Np ÷ Ns, so Ns = Np × Vs ÷ Vp = 1150 × 12 ÷ 230 = 60, about 60 turns.
Source: Worked out from the formula in the explanation
67An ideal transformer steps 400 V down to 230 V. The primary has 800 turns. How many turns does the secondary have, to the nearest turn?
Answer: 460
Vp ÷ Vs = Np ÷ Ns, so Ns = Np × Vs ÷ Vp = 800 × 230 ÷ 400 = 460, about 460 turns.
Source: Worked out from the formula in the explanation
68An ideal transformer steps 230 V down to 24 V. The primary has 2300 turns. How many turns does the secondary have, to the nearest turn?
Answer: 240
Vp ÷ Vs = Np ÷ Ns, so Ns = Np × Vs ÷ Vp = 2300 × 24 ÷ 230 = 240, about 240 turns.
Source: Worked out from the formula in the explanation
69An ideal transformer steps 11000 V down to 433 V. The primary has 2540 turns. How many turns does the secondary have, to the nearest turn?
Answer: 100
Vp ÷ Vs = Np ÷ Ns, so Ns = Np × Vs ÷ Vp = 2540 × 433 ÷ 11000 = 100, about 100 turns.
Source: Worked out from the formula in the explanation
70Ze is 0.35 Ω and the circuit's measured R1 + R2 is 0.42 Ω. What is the calculated Zs?
Answer: 0.77 Ω
Zs = Ze + (R1 + R2) = 0.35 + 0.42 = 0.77 Ω.
Source: Worked out from the formula in the explanation
Read more: Earth fault loop impedance testing: Ze, Zs and what the readings mean
71Ze is 0.8 Ω and the circuit's measured R1 + R2 is 0.61 Ω. What is the calculated Zs?
Answer: 1.41 Ω
Zs = Ze + (R1 + R2) = 0.8 + 0.61 = 1.41 Ω.
Source: Worked out from the formula in the explanation
Read more: Earth fault loop impedance testing: Ze, Zs and what the readings mean
72Ze is 0.2 Ω and the circuit's measured R1 + R2 is 0.95 Ω. What is the calculated Zs?
Answer: 1.15 Ω
Zs = Ze + (R1 + R2) = 0.2 + 0.95 = 1.15 Ω.
Source: Worked out from the formula in the explanation
Read more: Earth fault loop impedance testing: Ze, Zs and what the readings mean
73Ze is 0.35 Ω and the circuit's measured R1 + R2 is 1.12 Ω. What is the calculated Zs?
Answer: 1.47 Ω
Zs = Ze + (R1 + R2) = 0.35 + 1.12 = 1.47 Ω.
Source: Worked out from the formula in the explanation
Read more: Earth fault loop impedance testing: Ze, Zs and what the readings mean
74Ze is 0.8 Ω and the circuit's measured R1 + R2 is 0.27 Ω. What is the calculated Zs?
Answer: 1.07 Ω
Zs = Ze + (R1 + R2) = 0.8 + 0.27 = 1.07 Ω.
Source: Worked out from the formula in the explanation
Read more: Earth fault loop impedance testing: Ze, Zs and what the readings mean
75Ze is 0.21 Ω and the circuit's measured R1 + R2 is 0.58 Ω. What is the calculated Zs?
Answer: 0.79 Ω
Zs = Ze + (R1 + R2) = 0.21 + 0.58 = 0.79 Ω.
Source: Worked out from the formula in the explanation
Read more: Earth fault loop impedance testing: Ze, Zs and what the readings mean
76An earth fault loop impedance of 0.35 Ω is measured at 230 V. What is the prospective earth fault current, to the nearest amp?
Answer: 657 A
I = U0 ÷ Zs = 230 ÷ 0.35 = 657 A (0.66 kA).
Source: Worked out from the formula in the explanation
Read more: Fault current calculator
77An earth fault loop impedance of 0.8 Ω is measured at 230 V. What is the prospective earth fault current, to the nearest amp?
Answer: 288 A
I = U0 ÷ Zs = 230 ÷ 0.8 = 288 A (0.29 kA).
Source: Worked out from the formula in the explanation
Read more: Fault current calculator
78An earth fault loop impedance of 0.23 Ω is measured at 230 V. What is the prospective earth fault current, to the nearest amp?
Answer: 1,000 A
I = U0 ÷ Zs = 230 ÷ 0.23 = 1,000 A (1 kA).
Source: Worked out from the formula in the explanation
Read more: Fault current calculator
79An earth fault loop impedance of 1.15 Ω is measured at 230 V. What is the prospective earth fault current, to the nearest amp?
Answer: 200 A
I = U0 ÷ Zs = 230 ÷ 1.15 = 200 A (0.2 kA).
Source: Worked out from the formula in the explanation
Read more: Fault current calculator
80An earth fault loop impedance of 0.5 Ω is measured at 230 V. What is the prospective earth fault current, to the nearest amp?
Answer: 460 A
I = U0 ÷ Zs = 230 ÷ 0.5 = 460 A (0.46 kA).
Source: Worked out from the formula in the explanation
Read more: Fault current calculator
81An earth fault loop impedance of 0.46 Ω is measured at 230 V. What is the prospective earth fault current, to the nearest amp?
Answer: 500 A
I = U0 ÷ Zs = 230 ÷ 0.46 = 500 A (0.5 kA).
Source: Worked out from the formula in the explanation
Read more: Fault current calculator
82On a ring final circuit with 2.5/1.5 mm² cable, the end-to-end readings are r1 = 0.52 Ω and r2 = 0.86 Ω. With line and cpc cross-connected, what is the highest R1 + R2 you expect on the ring, at the sockets near the mid-point?
Answer: 0.345 Ω
With line and cpc cross-connected, the highest reading, at the mid-point, is (r1 + r2) ÷ 4 = (0.52 + 0.86) ÷ 4 = 0.345 Ω. With a smaller cpc, sockets near the ends read a little less.
Source: Worked out from the formula in the explanation
Read more: Ring final circuit continuity calculator
83On a ring final circuit with 2.5/1.5 mm² cable, the end-to-end readings are r1 = 0.4 Ω and r2 = 0.66 Ω. With line and cpc cross-connected, what is the highest R1 + R2 you expect on the ring, at the sockets near the mid-point?
Answer: 0.265 Ω
With line and cpc cross-connected, the highest reading, at the mid-point, is (r1 + r2) ÷ 4 = (0.4 + 0.66) ÷ 4 = 0.265 Ω. With a smaller cpc, sockets near the ends read a little less.
Source: Worked out from the formula in the explanation
Read more: Ring final circuit continuity calculator
84On a ring final circuit with 2.5/1.5 mm² cable, the end-to-end readings are r1 = 0.3 Ω and r2 = 0.5 Ω. With line and cpc cross-connected, what is the highest R1 + R2 you expect on the ring, at the sockets near the mid-point?
Answer: 0.2 Ω
With line and cpc cross-connected, the highest reading, at the mid-point, is (r1 + r2) ÷ 4 = (0.3 + 0.5) ÷ 4 = 0.2 Ω. With a smaller cpc, sockets near the ends read a little less.
Source: Worked out from the formula in the explanation
Read more: Ring final circuit continuity calculator
85On a ring final circuit with 2.5/1.5 mm² cable, the end-to-end readings are r1 = 0.64 Ω and r2 = 1.06 Ω. With line and cpc cross-connected, what is the highest R1 + R2 you expect on the ring, at the sockets near the mid-point?
Answer: 0.425 Ω
With line and cpc cross-connected, the highest reading, at the mid-point, is (r1 + r2) ÷ 4 = (0.64 + 1.06) ÷ 4 = 0.425 Ω. With a smaller cpc, sockets near the ends read a little less.
Source: Worked out from the formula in the explanation
Read more: Ring final circuit continuity calculator
86On a ring final circuit with 2.5/1.5 mm² cable, the end-to-end readings are r1 = 0.48 Ω and r2 = 0.8 Ω. With line and cpc cross-connected, what is the highest R1 + R2 you expect on the ring, at the sockets near the mid-point?
Answer: 0.32 Ω
With line and cpc cross-connected, the highest reading, at the mid-point, is (r1 + r2) ÷ 4 = (0.48 + 0.8) ÷ 4 = 0.32 Ω. With a smaller cpc, sockets near the ends read a little less.
Source: Worked out from the formula in the explanation
Read more: Ring final circuit continuity calculator
87A 2.5 mm² cable has a voltage drop of 18 mV/A/m. It carries 20 A over 25 m. What is the voltage drop?
Answer: 9 V
Voltage drop = mV/A/m × Ib × L ÷ 1000 = 18 × 20 × 25 ÷ 1000 = 9 V.
Source: Worked out from the formula in the explanation
Read more: Cable voltage drop calculator
88A 2.5 mm² cable has a voltage drop of 18 mV/A/m. It carries 16 A over 30 m. What is the voltage drop?
Answer: 8.64 V
Voltage drop = mV/A/m × Ib × L ÷ 1000 = 18 × 16 × 30 ÷ 1000 = 8.64 V.
Source: Worked out from the formula in the explanation
Read more: Cable voltage drop calculator
89A 4 mm² cable has a voltage drop of 11 mV/A/m. It carries 32 A over 20 m. What is the voltage drop?
Answer: 7.04 V
Voltage drop = mV/A/m × Ib × L ÷ 1000 = 11 × 32 × 20 ÷ 1000 = 7.04 V.
Source: Worked out from the formula in the explanation
Read more: Cable voltage drop calculator
90A 6 mm² cable has a voltage drop of 7.3 mV/A/m. It carries 40 A over 18 m. What is the voltage drop?
Answer: 5.26 V
Voltage drop = mV/A/m × Ib × L ÷ 1000 = 7.3 × 40 × 18 ÷ 1000 = 5.26 V.
Source: Worked out from the formula in the explanation
Read more: Cable voltage drop calculator
91A 2.5 mm² cable has a voltage drop of 18 mV/A/m. It carries 13 A over 40 m. What is the voltage drop?
Answer: 9.36 V
Voltage drop = mV/A/m × Ib × L ÷ 1000 = 18 × 13 × 40 ÷ 1000 = 9.36 V.
Source: Worked out from the formula in the explanation
Read more: Cable voltage drop calculator
92A 4 mm² cable has a voltage drop of 11 mV/A/m. It carries 25 A over 30 m. What is the voltage drop?
Answer: 8.25 V
Voltage drop = mV/A/m × Ib × L ÷ 1000 = 11 × 25 × 30 ÷ 1000 = 8.25 V.
Source: Worked out from the formula in the explanation
Read more: Cable voltage drop calculator
93Using the On-Site Guide Table B6 method, what is the maximum measured Zs for a 6 A Type B circuit-breaker at 230 V?
Answer: 5.83 Ω
Max measured Zs = 0.8 × U0 × Cmin ÷ Ia = 0.8 × 230 × 0.95 ÷ (5 × 6) = 5.8267, rounded up to 5.83 Ω. For a Type B breaker, Ia is taken as 5 × In, the top of its instant-trip range (3 to 5 × In).
Source: IET On-Site Guide Table B6 (paid), method shown in our Max Zs cheat sheet
94Using the On-Site Guide Table B6 method, what is the maximum measured Zs for a 10 A Type B circuit-breaker at 230 V?
Answer: 3.50 Ω
Max measured Zs = 0.8 × U0 × Cmin ÷ Ia = 0.8 × 230 × 0.95 ÷ (5 × 10) = 3.4960, rounded up to 3.50 Ω. For a Type B breaker, Ia is taken as 5 × In, the top of its instant-trip range (3 to 5 × In).
Source: IET On-Site Guide Table B6 (paid), method shown in our Max Zs cheat sheet
95Using the On-Site Guide Table B6 method, what is the maximum measured Zs for a 16 A Type B circuit-breaker at 230 V?
Answer: 2.19 Ω
Max measured Zs = 0.8 × U0 × Cmin ÷ Ia = 0.8 × 230 × 0.95 ÷ (5 × 16) = 2.1850, rounded up to 2.19 Ω. For a Type B breaker, Ia is taken as 5 × In, the top of its instant-trip range (3 to 5 × In).
Source: IET On-Site Guide Table B6 (paid), method shown in our Max Zs cheat sheet
96Using the On-Site Guide Table B6 method, what is the maximum measured Zs for a 20 A Type B circuit-breaker at 230 V?
Answer: 1.75 Ω
Max measured Zs = 0.8 × U0 × Cmin ÷ Ia = 0.8 × 230 × 0.95 ÷ (5 × 20) = 1.7480, rounded up to 1.75 Ω. For a Type B breaker, Ia is taken as 5 × In, the top of its instant-trip range (3 to 5 × In).
Source: IET On-Site Guide Table B6 (paid), method shown in our Max Zs cheat sheet
97Using the On-Site Guide Table B6 method, what is the maximum measured Zs for a 25 A Type B circuit-breaker at 230 V?
Answer: 1.40 Ω
Max measured Zs = 0.8 × U0 × Cmin ÷ Ia = 0.8 × 230 × 0.95 ÷ (5 × 25) = 1.3984, rounded up to 1.40 Ω. For a Type B breaker, Ia is taken as 5 × In, the top of its instant-trip range (3 to 5 × In).
Source: IET On-Site Guide Table B6 (paid), method shown in our Max Zs cheat sheet
98Using the On-Site Guide Table B6 method, what is the maximum measured Zs for a 6 A Type C circuit-breaker at 230 V?
Answer: 2.92 Ω
Max measured Zs = 0.8 × U0 × Cmin ÷ Ia = 0.8 × 230 × 0.95 ÷ (10 × 6) = 2.9133, rounded up to 2.92 Ω. For a Type C breaker, Ia is taken as 10 × In, the top of its instant-trip range (5 to 10 × In).
Source: IET On-Site Guide Table B6 (paid), method shown in our Max Zs cheat sheet
99Using the On-Site Guide Table B6 method, what is the maximum measured Zs for a 10 A Type C circuit-breaker at 230 V?
Answer: 1.75 Ω
Max measured Zs = 0.8 × U0 × Cmin ÷ Ia = 0.8 × 230 × 0.95 ÷ (10 × 10) = 1.7480, rounded up to 1.75 Ω. For a Type C breaker, Ia is taken as 10 × In, the top of its instant-trip range (5 to 10 × In).
Source: IET On-Site Guide Table B6 (paid), method shown in our Max Zs cheat sheet
100Using the On-Site Guide Table B6 method, what is the maximum measured Zs for a 16 A Type C circuit-breaker at 230 V?
Answer: 1.10 Ω
Max measured Zs = 0.8 × U0 × Cmin ÷ Ia = 0.8 × 230 × 0.95 ÷ (10 × 16) = 1.0925, rounded up to 1.10 Ω. For a Type C breaker, Ia is taken as 10 × In, the top of its instant-trip range (5 to 10 × In).
Source: IET On-Site Guide Table B6 (paid), method shown in our Max Zs cheat sheet
101Using the On-Site Guide Table B6 method, what is the maximum measured Zs for a 20 A Type C circuit-breaker at 230 V?
Answer: 0.88 Ω
Max measured Zs = 0.8 × U0 × Cmin ÷ Ia = 0.8 × 230 × 0.95 ÷ (10 × 20) = 0.8740, rounded up to 0.88 Ω. For a Type C breaker, Ia is taken as 10 × In, the top of its instant-trip range (5 to 10 × In).
Source: IET On-Site Guide Table B6 (paid), method shown in our Max Zs cheat sheet
102Using the On-Site Guide Table B6 method, what is the maximum measured Zs for a 25 A Type C circuit-breaker at 230 V?
Answer: 0.70 Ω
Max measured Zs = 0.8 × U0 × Cmin ÷ Ia = 0.8 × 230 × 0.95 ÷ (10 × 25) = 0.6992, rounded up to 0.70 Ω. For a Type C breaker, Ia is taken as 10 × In, the top of its instant-trip range (5 to 10 × In).
Source: IET On-Site Guide Table B6 (paid), method shown in our Max Zs cheat sheet
Your score
Written by us to help you revise. Not affiliated with SJIB, SECTT, the IET or City & Guilds. Questions follow BS 7671:2018+A4:2026 and the other documents named in each answer. If you think an answer is wrong, tell us and we'll check it against the source.