Home / Quizzes / Earthing and bonding
Earthing and bonding quiz
TN-S, TN-C-S and TT systems, Ze values, PME risks and earthing and bonding conductor sizes.
1In the earthing system TN-C-S, what does the C mean?
Answer: Neutral and protective functions are combined in one conductor in part of the system
The letters come from IEC 60364. S means separate neutral and protective conductors and C means combined (a PEN conductor). TN-C-S has a PEN in the supply and separate conductors in the installation.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: Earthing systems explained: TN-S, TN-C-S (PME) and TT
2In earthing system names, what does a first letter T mean?
Answer: The supply is connected directly to earth, usually at the transformer star point
The first letter describes the supply: T means directly earthed, I means isolated from earth or earthed through a high impedance. The second letter describes the installation.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: Earthing systems explained: TN-S, TN-C-S (PME) and TT
3What maximum Ze do network operators typically quote for a TN-C-S (PME) supply?
Answer: 0.35 Ω
0.35 Ω for TN-C-S, 0.8 Ω for TN-S, and 21 Ω for the supply side only of a TT system. Always measure the actual value.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: Earthing systems explained: TN-S, TN-C-S (PME) and TT
4What maximum Ze do network operators typically quote for a TN-S supply?
Answer: 0.8 Ω
TN-S typically uses the lead sheath or armour of the supply cable as the earth return, with a quoted maximum of 0.8 Ω.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: Earthing systems explained: TN-S, TN-C-S (PME) and TT
5On a TT system, what condition must an RCD providing fault protection meet?
Answer: RA × IΔn ≤ 50 V
Regulation 411.5.3. For a 30 mA RCD that allows RA up to 1,667 Ω, though an electrode resistance above about 200 Ω may not be stable.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: Earthing systems explained: TN-S, TN-C-S (PME) and TT
6Using RA × IΔn ≤ 50 V, what is the highest RA allowed with a 30 mA RCD?
Answer: 1,667 Ω
50 ÷ 0.03 = 1,667 Ω. With a 100 mA RCD it would be 500 Ω, and with 500 mA, 100 Ω.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: Earthing systems explained: TN-S, TN-C-S (PME) and TT
7On a PME supply with a supply neutral up to 35 mm², what is the minimum copper main protective bonding conductor size?
Answer: 10 mm²
Table 54.8 sizes PME main bonding from the supply neutral: 10 mm² up to 35 mm², 16 mm² up to 50 mm², 25 mm² up to 95 mm², 35 mm² up to 150 mm² and 50 mm² above.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: Earthing systems explained: TN-S, TN-C-S (PME) and TT
8On a TN-S or TT installation, what is the smallest copper main protective bonding conductor allowed under Regulation 544.1.1?
Answer: 6 mm²
At least half the cross-section required for the earthing conductor, and not less than 6 mm². It need not be more than 25 mm² copper.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: Earthing systems explained: TN-S, TN-C-S (PME) and TT
9For a typical home with 25 mm² meter tails, what size main earthing conductor does Table 54.7 give?
Answer: 16 mm² copper
Table 54.7 gives 16 mm² for line conductors over 16 mm² and up to 35 mm². The supplier may ask for more.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: Earthing systems explained: TN-S, TN-C-S (PME) and TT
10Why does a broken PEN conductor on a PME supply create a danger?
Answer: Earthed metalwork in properties beyond the break can rise towards line voltage
Neutral current has no path back except through the installation's earthing and bonding, which is why PME has larger bonding conductors and is restricted for things like EV charging outdoors and caravan pitches.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: Earthing systems explained: TN-S, TN-C-S (PME) and TT
11Which of these is NOT a suitable earth electrode for a TT installation?
Answer: A metal pipe of a water utility supply
BS 7671 doesn't allow a metallic pipe for gases, flammable liquids or a water utility supply to be used as an earth electrode. Using a gas or water pipe as the means of earthing is coded C2 on an EICR.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard); Electrical Safety First Best Practice Guide 4: EICR classification codes
Read more: EICR codes explained: C1, C2, C3 and FI (Amendment 4)