Home / Quizzes / Inspection and testing (Part 6)

Inspection and testing quiz (BS 7671 Part 6)

Continuity, ring final circuits, insulation resistance, polarity, earth fault loop impedance and RCD tests: the values and methods you need for initial verification.

17 questionsFICA area: BS 7671 Part 6, inspection and testingAnswers checked against the sources shown

0 of 17 answered
  1. 1On a new installation, which test normally comes first, where relevant?

    Answer: Continuity of protective conductors

    The dead tests come first, starting with continuity of protective conductors, then continuity of ring final circuit conductors, then insulation resistance. Live tests such as Zs and RCD tests follow only once the dead tests have passed.

    Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard); IET Guidance Note 3: Inspection and Testing (paid)

    Read more: R1+R2 continuity testing: how to do it and what to expect

  2. 2A low-resistance ohmmeter used for continuity testing to BS EN 61557-4 must deliver a test current of at least:

    Answer: 200 mA

    BS EN 61557-4 instruments use an open-circuit voltage of 4 V to 24 V and a test current of at least 200 mA. Null the leads before you start.

    Source: IET Guidance Note 3: Inspection and Testing (paid)

    Read more: R1+R2 continuity testing: how to do it and what to expect

  3. 3Using the R1+R2 method on a radial circuit, what do you do at the distribution board?

    Answer: Temporarily link the circuit's line conductor to its protective conductor

    With line linked to cpc at the board, measuring line to earth at each point reads R1+R2. The highest reading, normally at the far end, is recorded. Remove the link afterwards.

    Source: IET Guidance Note 3: Inspection and Testing (paid)

    Read more: R1+R2 continuity testing: how to do it and what to expect

  4. 4In the first step of a ring final circuit test, the end-to-end readings of the line (r1) and neutral (rn) should agree to within:

    Answer: 0.05 Ω

    r1 and rn should be within 0.05 Ω of each other. For 2.5/1.5 mm² twin and earth, the cpc reading r2 should be about 1.67 times r1.

    Source: IET Guidance Note 3: Inspection and Testing (paid)

    Read more: Ring final circuit testing: the three-step continuity test

  5. 5After cross-connecting line to cpc at the ends of a ring, what should the reading at each socket be?

    Answer: About (r1 + r2) ÷ 4

    Each socket should read about a quarter of the sum of the end-to-end readings. The highest reading is R1+R2 for the circuit. A socket on a spur reads higher.

    Source: IET Guidance Note 3: Inspection and Testing (paid)

    Read more: Ring final circuit testing: the three-step continuity test

  6. 6What test voltage and minimum insulation resistance apply to a 230 V final circuit?

    Answer: 500 V DC and 1.0 MΩ

    BS 7671 Table 64: circuits up to 500 V are tested at 500 V DC with a minimum of 1.0 MΩ. SELV and PELV use 250 V and 0.5 MΩ, and circuits above 500 V use 1000 V and 1.0 MΩ.

    Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)

    Read more: Insulation resistance testing: test voltages, minimum values and method

  7. 7What test voltage and minimum insulation resistance apply to a SELV circuit?

    Answer: 250 V DC and 0.5 MΩ

    Table 64 gives 250 V DC with a minimum of 0.5 MΩ for SELV and PELV circuits.

    Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)

    Read more: Insulation resistance testing: test voltages, minimum values and method

  8. 8Ten circuits each read 200 MΩ on an insulation resistance test. What would a combined test of all ten at once read?

    Answer: 20 MΩ

    Insulation resistances in parallel combine like resistors: 1 ÷ (10 ÷ 200) = 20 MΩ. That's why a whole-board reading is lower than any single circuit.

    Read more: Insulation resistance testing: test voltages, minimum values and method

  9. 9One of the purposes of a polarity test is to confirm that:

    Answer: Fuses and single-pole switches and protective devices are connected in the line conductor only

    If a switch or fuse were in the neutral, the equipment would stay live with the switch off or the fuse blown. On lighting, the R1+R2 test proves this at the same time, because the reading only appears with the switch on.

    Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard); IET Guidance Note 3: Inspection and Testing (paid)

    Read more: R1+R2 continuity testing: how to do it and what to expect

  10. 10Why are the maximum Zs values in the On-Site Guide lower than those in BS 7671 Table 41.3?

    Answer: They are for readings taken at room temperature, when conductor resistance is lower than in use

    Table 41.3 values apply at the conductor's maximum operating temperature. Testing is done cold, so the On-Site Guide gives maximum measured values at about 80% of Table 41.3. For a B32 that's 1.10 Ω instead of 1.37 Ω.

    Source: IET On-Site Guide, Table B6, maximum measured Zs (paid)

    Read more: Earth fault loop impedance testing: Ze, Zs and what the readings mean

  11. 11When measuring Ze at the origin, why is the main earthing conductor disconnected from the main earthing terminal?

    Answer: So parallel earth paths through the bonding don't lower the reading

    With the installation safely isolated, disconnecting the main earthing conductor removes parallel paths through gas and water bonding. It must be reconnected straight away, and never disconnected with the installation energised.

    Source: IET Guidance Note 3: Inspection and Testing (paid)

    Read more: Earth fault loop impedance testing: Ze, Zs and what the readings mean

  12. 12A circuit has Ze = 0.21 Ω and R1+R2 = 0.38 Ω. What is Zs?

    Answer: 0.59 Ω

    Zs = Ze + (R1 + R2) = 0.21 + 0.38 = 0.59 Ω. For a B32, that's below the 1.10 Ω maximum measured value, so it passes.

    Source: IET Guidance Note 3: Inspection and Testing (paid)

    Read more: Earth fault loop impedance testing: Ze, Zs and what the readings mean

  13. 13When measuring prospective fault current at the origin, which value do you record?

    Answer: The higher of the prospective short-circuit current and the prospective earth fault current

    Measure both PSCC (line to neutral) and PEFC (line to earth) and record the higher. It must not exceed the breaking capacity of the protective devices fitted.

    Source: IET Guidance Note 3: Inspection and Testing (paid)

    Read more: Earth fault loop impedance testing: Ze, Zs and what the readings mean

  14. 14A general non-delayed 30 mA RCD is tested at its rated residual current, IΔn. It must trip within:

    Answer: 300 ms

    General RCDs must trip within 300 ms at IΔn. A time-delayed S type must trip between 130 ms and 500 ms.

    Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)

    Read more: BS 7671 test values: Zs, insulation resistance, RCDs and continuity

  15. 15Since Amendment 2, which RCD test is required by BS 7671 for initial verification?

    Answer: A test at the rated residual operating current, IΔn

    Amendment 2 removed the requirement for the ½ × and 5 × IΔn tests. They can still help with fault finding.

    Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)

    Read more: BS 7671 test values: Zs, insulation resistance, RCDs and continuity

  16. 16What resistance does IET guidance suggest for a main protective bonding conductor, measured end to end?

    Answer: In the order of 0.05 Ω or less

    Use the wander lead method from the main earthing terminal to the pipe clamp. A higher reading usually means a poor clamp or a corroded pipe surface.

    Source: IET Guidance Note 3: Inspection and Testing (paid)

    Read more: R1+R2 continuity testing: how to do it and what to expect

  17. 17A lighting circuit is 20 m of 1.5/1.0 mm² cable, about 30.2 mΩ per metre for line and cpc together. Roughly what R1+R2 should you expect?

    Answer: 0.60 Ω

    20 m × 30.2 mΩ/m = 604 mΩ, about 0.60 Ω at 20 °C. A much higher reading suggests a poor connection, and an open circuit means a broken cpc.

    Read more: R1+R2 continuity testing: how to do it and what to expect

Written by us to help you revise. Not affiliated with SJIB, SECTT, the IET or City & Guilds. Questions follow BS 7671:2018+A4:2026 and the other documents named in each answer. If you think an answer is wrong, tell us and we'll check it against the source.