Home / Quizzes / Part P, plugs and extension leads
Part P, plugs and extension leads quiz
Which jobs are notifiable in England, plug fuses, wiring a plug and how not to overload an extension lead.
1In England, is installing a new circuit for an electric shower notifiable building work?
Answer: Yes, any new circuit is notifiable
Regulation 12(6A) makes installing a new circuit notifiable, whatever it supplies.
Source: The Building Regulations 2010, regulation 12 (notifiable work)
Read more: Part P: what electrical work is notifiable in England?
2In England, is adding a socket to an existing circuit in a bedroom notifiable?
Answer: No, but it must still be safe and meet BS 7671
Additions to existing circuits are only notifiable in a special location. The work must still meet Part P and BS 7671.
Source: The Building Regulations 2010, regulation 12 (notifiable work)
Read more: Part P: what electrical work is notifiable in England?
3In England, is replacing a consumer unit notifiable?
Answer: Yes
Replacing a consumer unit is listed as notifiable in regulation 12(6A).
Source: The Building Regulations 2010, regulation 12 (notifiable work)
Read more: Part P: what electrical work is notifiable in England?
4For Part P in England, how far out from the edge of a bath does the special location run?
Answer: 0.6 m
It runs 0.6 m out from the bath or shower tray, and from the floor up to 2.25 m (or the shower head if that's higher).
Source: The Building Regulations 2010, regulation 12 (notifiable work)
Read more: Part P: what electrical work is notifiable in England?
5For Part P in England, where there's no shower tray, as in a wet room, how far does the special location run?
Answer: 1.2 m from the centre of the shower head
Without a tray, the horizontal limit is 1.2 m from the centre point of the fixed shower head.
Source: The Building Regulations 2010, regulation 12 (notifiable work)
Read more: Part P: what electrical work is notifiable in England?
6Is a kitchen a special location for Part P notification in England?
Answer: No
The current rules only single out the space around baths and showers and rooms with a swimming pool or sauna heater.
Source: The Building Regulations 2010, regulation 12 (notifiable work)
Read more: Part P: what electrical work is notifiable in England?
7Within how many days must a competent person scheme electrician give the customer a compliance certificate for notifiable work?
Answer: 30 days
The registered person must give the certificate, and notify building control, within 30 days of finishing.
Source: The Building Regulations 2010, regulation 20 (self-certification)
Read more: Part P: what electrical work is notifiable in England?
8You want to do notifiable electrical work in your own home in England without a registered electrician. What must you do?
Answer: Give building control a building notice or full plans application before starting, and pay their fee
The law allows it, but building control must be told before you start, and they'll inspect the work.
Source: The Building Regulations 2010, regulation 12 (notifiable work)
Read more: Part P: what electrical work is notifiable in England?
9Which of these does Part P cover?
Answer: Electrical installations in an outbuilding, such as a shed, supplied from a dwelling
Requirement P1 covers dwellings, common parts serving dwellings (but not lifts) and outbuildings or gardens supplied from a dwelling.
Source: Approved Document P: Electrical safety, dwellings (England)
Read more: Part P: what electrical work is notifiable in England?
10Which British Standard covers UK 13 A plugs and sockets?
Answer: BS 1363
Plugs and sockets are BS 1363. The cartridge fuse inside the plug is BS 1362.
Source: Electrical Safety First: plugs and fuses
Read more: Plug fuses and extension leads: 3 A or 13 A, and how not to overload
11Which plug fuse does a 2 kW kettle need?
Answer: 13 A
Electrical Safety First's guide is 13 A for appliances from about 700 W up to 3,000 W. 2000 ÷ 230 is about 8.7 A.
Source: Electrical Safety First: plugs and fuses
Read more: Plug fuses and extension leads: 3 A or 13 A, and how not to overload
12Which plug fuse does a table lamp normally take?
Answer: 3 A
Appliances up to about 700 W, such as lamps and televisions, take a 3 A fuse.
Source: Electrical Safety First: plugs and fuses
Read more: Plug fuses and extension leads: 3 A or 13 A, and how not to overload
13What does the fuse in a plug mainly protect?
Answer: The flexible cable to the appliance
The wall circuit is protected at the consumer unit, often at 32 A. The plug fuse protects the much thinner flex.
Source: Electrical Safety First: plugs and fuses
Read more: Plug fuses and extension leads: 3 A or 13 A, and how not to overload
14Looking into the back of a UK plug, where does the brown (live) conductor go?
Answer: Bottom right, the terminal with the fuse
Brown to live (bottom right, with the fuse), blue to neutral (bottom left), green and yellow to earth (top centre).
Source: Electrical Safety First: plugs and fuses
Read more: Plug fuses and extension leads: 3 A or 13 A, and how not to overload
15On old flex, what colour was the neutral conductor?
Answer: Black
Old flex used red for live, black for neutral and green for earth. Today's colours are brown, blue and green and yellow.
Source: Electrical Safety First: plugs and fuses
Read more: Plug fuses and extension leads: 3 A or 13 A, and how not to overload
16What is the most a 13 A extension lead should supply, however many sockets it has?
Answer: About 3,000 W in total
The rating is for the whole lead. Four sockets doesn't mean four times the power.
Source: Electrical Safety First: extension leads, cable reels and block adaptors
Read more: Plug fuses and extension leads: 3 A or 13 A, and how not to overload
17A 3 kW kettle and a 2 kW fan heater are plugged into one 13 A extension lead. Roughly what current do they draw at 230 V?
Answer: About 21.7 A, well over the lead's rating
5000 W ÷ 230 V ≈ 21.7 A, far more than 13 A. Plug high-power appliances straight into a wall socket.
Source: Electrical Safety First: extension leads, cable reels and block adaptors
Read more: Plug fuses and extension leads: 3 A or 13 A, and how not to overload
18Why should a cable reel be fully unwound before use?
Answer: Its rating assumes it's unwound, and running it wound up can overheat it
Coiled cable can't lose heat, so a wound-up reel under heavy load can overheat and catch fire.
Source: Electrical Safety First: extension leads, cable reels and block adaptors
Read more: Plug fuses and extension leads: 3 A or 13 A, and how not to overload
19Is it OK to plug one extension lead into another?
Answer: No, never daisy-chain extension leads
Electrical Safety First advises one extension lead per wall socket and never plugging one into another.
Source: Electrical Safety First: extension leads, cable reels and block adaptors
Read more: Plug fuses and extension leads: 3 A or 13 A, and how not to overload
20Why does Electrical Safety First list fridges under 13 A fuses even though they only use a few hundred watts?
Answer: Motors and compressors draw a much bigger current for a moment when they start
Starting current can be several times the running current, so follow the appliance's instructions, not just the running wattage.
Source: Electrical Safety First: plugs and fuses
Read more: Plug fuses and extension leads: 3 A or 13 A, and how not to overload
21Where does the 700 W dividing line between 3 A and 13 A plug fuses come from?
Answer: 700 W ÷ 230 V is about 3 A
Amps = watts ÷ volts, so 700 ÷ 230 = 3.0 A. Likewise 3,000 W is about 13 A.
Source: Electrical Safety First: plugs and fuses
Read more: Plug fuses and extension leads: 3 A or 13 A, and how not to overload
Your score
Written by us to help you revise. Not affiliated with SJIB, SECTT, the IET or City & Guilds. Questions follow BS 7671:2018+A4:2026 and the other documents named in each answer. If you think an answer is wrong, tell us and we'll check it against the source.