BS 7671 design and protection quiz
Disconnection times, earth fault loop impedance, circuit-breakers, RCDs, voltage drop and how BS 7671 is laid out. This covers the kind of Parts 1 to 5 questions you'll meet in FICA Section F and other 18th Edition exams.
1In a TN system at 230 V, what is the maximum disconnection time for a final circuit rated up to 63 A that supplies socket-outlets?
Answer: 0.4 s
BS 7671 Table 41.1 gives 0.4 s for TN final circuits up to 63 A with socket-outlets, and up to 32 A supplying only fixed equipment, at a U₀ of 230 V. A circuit-breaker's instantaneous trip easily achieves this when Zs is low enough.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: Earth fault loop impedance testing: Ze, Zs and what the readings mean
2In a TT system at 230 V, what is the maximum disconnection time for a final circuit rated up to 32 A that supplies socket-outlets?
Answer: 0.2 s
Table 41.1 of BS 7671 sets 0.2 s for TT final circuits in this range at a U₀ of 230 V, half the TN time. In practice the loop impedance of a TT system is far too high for a breaker to manage this, so a 30 mA RCD provides the fault protection.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: Earthing systems explained: TN-S, TN-C-S (PME) and TT
3In a TN system, what is the maximum disconnection time for a distribution circuit, or a final circuit rated above 63 A?
Answer: 5 s
BS 7671 allows up to 5 s in a TN system for distribution circuits and for final circuits not covered by Table 41.1. The equivalent figure for a TT system is 1 s.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: Earth fault loop impedance testing: Ze, Zs and what the readings mean
4When BS 7671 works out the maximum earth fault loop impedance for a circuit-breaker, what value of Cmin does it use?
Answer: 0.95
Cmin, 0.95, allows for the supply voltage being at the low end of its permitted range. The maximum is Zs = U₀ × Cmin ÷ Ia. Don't confuse it with the 0.8 factor sometimes used to convert Table 41.3 values to readings at room temperature.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: Earth fault loop impedance testing: Ze, Zs and what the readings mean
5A Type B circuit-breaker to BS EN 60898 must trip instantly between what multiples of its rated current, In?
Answer: Over 3 × In, up to 5 × In
Type B: 3 to 5 × In. Type C: 5 to 10 × In. Type D: 10 to 20 × In. BS 7671 uses the top of the range, 5 × In for a Type B, to work out maximum Zs, because that current guarantees an instant trip.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: Type B vs Type C vs Type D circuit-breakers (MCBs and RCBOs)
6Using Zs = U₀ × Cmin ÷ Ia with U₀ = 230 V, what is the maximum Zs for a 32 A Type B circuit-breaker?
Answer: 1.37 Ω
Ia for a B32 is 5 × 32 = 160 A, so Zs = 230 × 0.95 ÷ 160 = 1.37 Ω, the figure in BS 7671 Table 41.3. 1.10 Ω is the lower maximum measured value used when testing at room temperature, and 0.68 Ω is the Table 41.3 value for a C32.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: Earth fault loop impedance testing: Ze, Zs and what the readings mean
7What is the Table 41.3 maximum Zs for a 16 A Type C circuit-breaker at a U₀ of 230 V?
Answer: 1.37 Ω
Ia for a Type C is 10 × In, so 160 A for a C16. Zs = 230 × 0.95 ÷ 160 = 1.37 Ω, the same as a B32, because both need 160 A to trip instantly. 2.73 Ω is the value for a B16.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: Type B vs Type C vs Type D circuit-breakers (MCBs and RCBOs)
8A circuit-breaker to BS EN 60898 must trip within one hour at its conventional tripping current. What is that current?
Answer: 1.45 × In
At 1.13 × In it must not trip within one hour, and at 1.45 × In it must trip within one hour. BS 7671 requires the tripping current, I₂, to be no more than 1.45 times the cable's current-carrying capacity, which a 60898 breaker meets if In isn't more than the cable rating.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: Type B vs Type C vs Type D circuit-breakers (MCBs and RCBOs)
9A circuit-breaker has 6000 printed in a small box on its front. What does it mean?
Answer: It can safely break a fault current of up to 6 kA
The boxed number is the rated short-circuit capacity, Icn, in amps. The prospective fault current where it's installed must not be more than this, unless the consumer unit has a higher conditional rating with the supplier's fuse upstream.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: Type B vs Type C vs Type D circuit-breakers (MCBs and RCBOs)
10Since Amendment 2, when can a Type AC RCD be used?
Answer: Only where the load is known not to produce DC components
Regulation 531.3.3 restricts Type AC RCDs to loads known not to contain DC components. In practice Type A is the normal minimum for new domestic work.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: RCD types explained: AC, A, F and B, and which one you need
11Which RCD type detects AC and pulsating DC residual currents, including when up to 6 mA of smooth DC is present?
Answer: Type A
Type A covers AC and pulsating DC with up to 6 mA of smooth DC. Type F goes further, to 10 mA of smooth DC and composite currents. Type B also detects smooth DC. S marks a time-delayed RCD, not a waveform type.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: RCD types explained: AC, A, F and B, and which one you need
12For an installation supplied directly from a public low voltage network, what voltage drop does BS 7671 Appendix 4 suggest as the limit for a lighting circuit?
Answer: 3%
Appendix 4 gives 3% for lighting (6.9 V at 230 V) and 5% for other uses (11.5 V), measured from the origin of the installation.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: Cable voltage drop calculator
13A socket circuit in 2.5 mm² twin and earth (18 mV/A/m) carries 20 A over a 25 m run. What is the voltage drop, and does it meet the 5% limit for other uses?
Answer: 9.0 V, which is within the 11.5 V limit
Voltage drop = mV/A/m × I × L ÷ 1000 = 18 × 20 × 25 ÷ 1000 = 9.0 V. 5% of 230 V is 11.5 V, so it passes. It would fail the 3% (6.9 V) limit if this were a lighting circuit.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: Cable voltage drop calculator
14What is the maximum normal operating temperature at the conductor for a cable with thermoplastic (PVC) insulation?
Answer: 70 °C
General purpose thermoplastic cables are rated for 70 °C at the conductor in normal use. 90 °C applies to thermosetting (XLPE) cables, and 160 °C is the final temperature allowed for a PVC-insulated conductor during a fault.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: Adiabatic equation calculator
15Which part of BS 7671 covers inspection and testing?
Answer: Part 6
Part 1 is scope and fundamental principles, Part 2 definitions, Part 3 assessment of general characteristics, Part 4 protection for safety, Part 5 selection and erection, Part 6 inspection and testing, and Part 7 special installations or locations.
Source: Electrical Safety First: BS 7671:2018+A4:2026 and domestic installations, pocket guide (April 2026)
16How does Part 7 of BS 7671 relate to Parts 1 to 6?
Answer: It supplements or modifies them for special installations or locations
Part 7's requirements for places such as bathrooms, caravan parks and EV charging add to or change the general requirements of Parts 1 to 6. Where Part 7 says nothing, the general requirements still apply.
Source: Electrical Safety First: BS 7671:2018+A4:2026 and domestic installations, pocket guide (April 2026)
17BS 7671 Regulation 421.1.7 requires AFDDs on socket-outlet circuits up to 32 A in which of these?
Answer: A house in multiple occupation (HMO)
AFDDs are required on single-phase AC socket-outlet final circuits up to 32 A in high-rise residential buildings, HMOs, purpose-built student accommodation and care homes. Elsewhere they're recommended, not required.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: AFDDs explained: arc fault detection devices and where BS 7671 requires them
18Why can't a circuit-breaker or an RCD reliably detect a series arc in a damaged flex?
Answer: The current is no higher than the load current and none leaks to earth
A series arc is in one conductor, so the load current still flows through it and never reaches the breaker's trip level, and with no leakage to earth the RCD sees nothing. That's the gap an AFDD fills.
Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)
Read more: AFDDs explained: arc fault detection devices and where BS 7671 requires them