Check that a protective conductor is big enough to carry an earth fault current until the device disconnects, without overheating. Enter the fault current and disconnection time to get the minimum size, or check a size you've already chosen.

  • Electrical tool
  • Runs in your browser
  • Tested 19 November 2026
  • Sources
For an earth fault, U₀ ÷ Zs.
From the device's time–current curve at this current. Up to 5 s.
Copper. k values from BS 7671 Tables 54.2 and 54.3.

The adiabatic equation

For a fault lasting up to 5 seconds, BS 7671 Regulation 543.1.3 gives the minimum cross-sectional area of a protective conductor as:

S = √(I² t) / k

S is in mm², I is the fault current in amps, t is the disconnection time in seconds, and k depends on the conductor material, its insulation and the temperatures involved. The equation assumes all the heat stays in the conductor during the fault (that's what adiabatic means), which is a safe assumption for short faults.

Where k comes from

k is set by how hot the conductor starts and how hot the insulation can safely get. For copper, IEC 60364-5-54 gives k = 226 √(ln(1 + (θf − θi) / (234.5 + θi))). A cpc inside a 70 °C PVC cable starts at 70 °C and may reach 160 °C, so k = 115. A separate PVC-covered conductor starts at 30 °C, so k = 143. The tool shows the k it uses, worked out from the temperatures, so you can check it against the tables.

Worked example. A fault current of 800 A, cleared in 0.1 s, in a 70 °C PVC twin and earth cable (k = 115): S = √(800² × 0.1) ÷ 115 = 2.2 mm². A 1.5 mm² cpc is too small at that current and time, but 2.5 mm² is enough. In practice a type B breaker clears 800 A almost instantly, much faster than 0.1 s, so read the real time from the device's curve.

Using it in practice

  • Get the fault current from U₀ ÷ Zs (the maximum Zs calculator estimates Zs), and read the disconnection time for that current from the device manufacturer's time–current curve or the curves in BS 7671 Appendix 3.
  • For circuit-breakers that clear a fault in under 0.1 s, the manufacturer's let-through energy (I²t) is more accurate than I² × t. Enter it by setting t to 1 s and I to √(I²t).
  • Alternatively, BS 7671 Table 54.7 lets you size the cpc from the line conductor without calculating, but the result is usually larger.
  • Always check against the current edition of BS 7671.