The adiabatic equation
For a fault lasting up to 5 seconds, BS 7671 Regulation 543.1.3 gives the minimum cross-sectional area of a protective conductor as:
S = √(I² t) / k
S is in mm², I is the fault current in amps, t is the disconnection time in seconds, and k depends on the conductor material, its insulation and the temperatures involved. The equation assumes all the heat stays in the conductor during the fault (that's what adiabatic means), which is a safe assumption for short faults.
Where k comes from
k is set by how hot the conductor starts and how hot the insulation can safely get. For copper, IEC 60364-5-54 gives k = 226 √(ln(1 + (θf − θi) / (234.5 + θi))). A cpc inside a 70 °C PVC cable starts at 70 °C and may reach 160 °C, so k = 115. A separate PVC-covered conductor starts at 30 °C, so k = 143. The tool shows the k it uses, worked out from the temperatures, so you can check it against the tables.
Using it in practice
- Get the fault current from U₀ ÷ Zs (the maximum Zs calculator estimates Zs), and read the disconnection time for that current from the device manufacturer's time–current curve or the curves in BS 7671 Appendix 3.
- For circuit-breakers that clear a fault in under 0.1 s, the manufacturer's let-through energy (I²t) is more accurate than I² × t. Enter it by setting t to 1 s and I to √(I²t).
- Alternatively, BS 7671 Table 54.7 lets you size the cpc from the line conductor without calculating, but the result is usually larger.
- Always check against the current edition of BS 7671.