Maximum Zs and R1+R2 calculator

Check that a circuit-breaker will disconnect an earth fault fast enough. Get the maximum measured earth fault loop impedance (Zs) for type B, C and D breakers, the figure to compare your test readings with, plus the BS 7671 Table 41.3 design value and an estimate of Zs from Ze and the cable.

  • Electrical tool
  • Runs in your browser
  • Tested 19 November 2026
  • Sources

Optional: estimate Zs for a copper circuit

0.35 Ω is the usual maximum quoted for TN-C-S (PME), 0.8 Ω for TN-S.
A test reading at normal room temperature.

How the maximum is worked out

In a TN system, an earth fault must make the protective device disconnect within the time in BS 7671 Table 41.1: 0.4 s for most final circuits up to 63 A at 230 V, or 5 s for distribution circuits and larger final circuits. For that to happen, the fault current must be at least the current Ia that operates the device in that time, so the loop impedance must be no more than:

Zs = U₀ × Cmin / Ia

U₀ is the nominal voltage to earth (230 V in the UK) and Cmin = 0.95 allows for the supply voltage being at the low end of its permitted range. For circuit-breakers to BS EN 60898 and RCBOs to BS EN 61009, Ia is the top of the instantaneous tripping band: 5 × In for type B, 10 × In for type C, and 20 × In for type D (10 × In for type D at 5 s). Older BS 3871 breakers use 4 × In (type 1), 7 × In (type 2) and 10 × In (type 3). Worked out this way, every value matches BS 7671:2018 Table 41.3. For example, a 32 A type B: 230 × 0.95 ÷ 160 A = 1.37 Ω.

Which figure to compare your test reading with

The Table 41.3 values are for conductors at their normal operating temperature, 70 °C for thermoplastic (PVC) cables. Readings taken on a cold circuit will be lower than they would be in service, because copper's resistance rises by about 0.4 % per °C. So for test readings, the IET's On-Site Guide (Table B6) gives maximum measured values of 0.8 × U₀ × Cmin ÷ Ia, rounded up to two decimal places. That's the headline figure this calculator shows, and it matches every entry in Table B6. For the 32 A type B above: 0.8 × 1.3656 = 1.0925, which the guide gives as 1.10 Ω.

A reading over the measured maximum but under the Table 41.3 value isn't automatically a pass. It only complies if a proper temperature correction, using the method in Guidance Note 3, shows the circuit will still be within Table 41.3 when warm.

Estimating Zs before you install

Zs = Ze + (R1 + R2), where Ze is the external loop impedance and R1 + R2 is the resistance of the line conductor and the circuit protective conductor (cpc) together. The tool uses the maximum resistance of plain copper conductors at 20 °C from IEC 60228 (for example 7.41 mΩ/m for 2.5 mm² and 12.1 mΩ/m for 1.5 mm²), then corrects them to 70 °C, which multiplies them by about 1.2.

Worked example. 20 m of 2.5/1.5 mm² twin and earth: R1 + R2 = (7.41 + 12.1) × 20 ÷ 1000 = 0.39 Ω at 20 °C, or 0.47 Ω at 70 °C. With Ze = 0.35 Ω, Zs ≈ 0.82 Ω, well under the 1.37 Ω Table 41.3 limit for a 32 A type B (the estimate is already corrected to 70 °C, so it is compared with the Table 41.3 value, not the measured value). The prospective earth fault current is then about 230 ÷ 0.82 = 280 A.

Things to know

  • This covers circuit-breakers only. Fuses don't have a single trip current, so their limits come from the time–current curves in BS 7671 Tables 41.2 and 41.4.
  • Manufacturers sometimes publish higher limits for their own devices, based on their actual trip curves. Those apply only to that device.
  • Where an RCD provides fault protection, as on most TT systems, the requirement is different and much easier to meet. See BS 7671 Regulation 411.5.
  • Always check against the current edition of BS 7671 and its amendments. Inspection, testing and certification must be done by a competent person.