Buying guide: multifunction installation testers (MFTs)

A multifunction installation tester showing loop impedance and RCD trip time results on its screen
Beginner
How we wrote this: we haven't tested these instruments hands-on for this guide. Every figure comes from the manufacturer's own specifications, linked at the end. Models get discontinued and replaced, so check the current version before you buy. We don't earn anything if you buy one.

A multifunction tester (MFT) combines every test needed to verify a low-voltage installation in the UK in one instrument: continuity, insulation resistance, polarity, earth fault loop impedance, prospective fault current, RCD operation and often earth electrode resistance and phase rotation. It's the main tool for initial verification and periodic inspection to BS 7671.

Competence matters more than the tester. Testing an installation means working near live parts and applying high test voltages. It should only be carried out by someone trained and competent in inspection and testing, following BS 7671 and the IET's Guidance Note 3.

What to look for

No-trip loop testing

Measuring earth fault loop impedance (Zs) pushes a test current from line to earth. On a circuit protected by a 30 mA RCD, a high-current test would trip it. A no-trip, or low-current, loop test uses a small current over a longer time so the RCD stays put. Every current MFT offers this, but they differ in how stable the readings are. Look for a high-current two-wire mode as well, for fast, high-resolution readings at the origin where there's no RCD.

The RCD types you'll meet

RCDs come in types that respond to different fault currents. Type AC detects only sinusoidal AC. Type A also detects pulsating DC. Type F adds mixed-frequency currents from variable-speed drives. Type B also detects smooth DC. BS 7671:2018 limits Type AC RCDs to fixed equipment known to produce no DC component, so Type A is now the norm in homes. Make sure the tester can test every type you install, including Type B if you work on solar, heat pumps or EV chargers.

EV charge points

EV charge points need protection against DC fault currents, usually a Type B RCD or a residual direct current detecting device (RDC-DD) that trips at 6 mA DC. Testing the 6 mA DC function needs either a tester that can generate it or an adapter. Check this if you install charge points.

Insulation and continuity

Look for 250 V, 500 V and 1000 V insulation tests and 200 mA continuity, the same as a standalone insulation tester. Some testers warn you if equipment is still connected before applying the test voltage, which can save damaged appliances.

Results and certificates

Saving results and sending them to certificate software, by Bluetooth or app, saves a lot of typing on large jobs. Check that the tester works with the software you or your scheme use.

Practical points

Battery life, a display you can read in a dark cupboard, sturdy GS38-compliant leads and a strap to hang it up all matter on a full day of testing. Calibration is typically done every year, and competent person schemes expect to see the certificates.

Three testers compared

TesterInsulation testsLoop testingRCD typesSafety rating
Megger MFT-X150 to 1000 V, plus variable 50 to 999 VNo-trip two-wire and three-wire; high-current; high-resolution 0.001 Ω mode; PFC to 50 kAAC, A, B, and their S versions; 6 mA DC with the EV adapterCAT IV 300 V
Fluke 1664 FC50, 100, 250, 500, 1000 VLoop impedance including a high-current mΩ modeA, AC, B and SCAT III 500 V, CAT IV 300 V
Kewtech KT65DL250, 500, 1000 VNo-trip loop, 0.01 to 2000 Ω10 to 500 mA test currents; RCD types not stated by the sellerCAT III 500 V, CAT IV 300 V

Figures are from Megger's, Fluke's and the seller's published specifications. None of these specifications lists a Type F RCD setting. A Type F RCD must also meet the Type A requirements, so testers without a Type F setting are generally used on their Type A setting. Check the instrument's manual to confirm.

Megger MFT-X1

Megger's current flagship, which replaced the popular MFT1741+. It has a colour display, a rechargeable lithium-ion battery, Megger's True Loop no-trip testing, and RCD tests for types AC, A and B including selective versions. Continuity runs at over 200 mA, and results transfer to Megger's CertSuite app. It suits contractors doing a lot of certification work.

Fluke 1664 FC

Fluke's top MFT. Its Insulation PreTest checks whether appliances are still connected and stops the test if so. An auto test runs up to seven tests in one sequence, and results can go to a phone through Fluke Connect. It tests RCD types A, AC, B and S, and handles EV charge point RDC-DD checks in its variable mode.

Kewtech KT65DL

A long-running, more affordable option from a UK brand. It covers insulation at 250, 500 and 1000 V, continuity, no-trip loop testing, RCD tests from 10 to 500 mA including ramp tests, and earth electrode testing. The seller's listing doesn't state which RCD types it supports, so check that with Kewtech before buying if you install Type B devices.

For maintenance work, a standalone insulation tester may be all you need. For three-phase work, see our guide to phase rotation testers.

Sources

The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.