A multifunction tester (MFT) combines every test needed to verify a low-voltage installation in the UK in one instrument: continuity, insulation resistance, polarity, earth fault loop impedance, prospective fault current, RCD operation and often earth electrode resistance and phase rotation. It's the main tool for initial verification and periodic inspection to BS 7671.
What to look for
No-trip loop testing
Measuring earth fault loop impedance (Zs) pushes a test current from line to earth. On a circuit protected by a 30 mA RCD, a high-current test would trip it. A no-trip, or low-current, loop test uses a small current over a longer time so the RCD stays put. Every current MFT offers this, but they differ in how stable the readings are. Look for a high-current two-wire mode as well, for fast, high-resolution readings at the origin where there's no RCD.
The RCD types you'll meet
RCDs come in types that respond to different fault currents. Type AC detects only sinusoidal AC. Type A also detects pulsating DC. Type F adds mixed-frequency currents from variable-speed drives. Type B also detects smooth DC. BS 7671:2018 limits Type AC RCDs to fixed equipment known to produce no DC component, so Type A is now the norm in homes. Make sure the tester can test every type you install, including Type B if you work on solar, heat pumps or EV chargers.
EV charge points
EV charge points need protection against DC fault currents, usually a Type B RCD or a residual direct current detecting device (RDC-DD) that trips at 6 mA DC. Testing the 6 mA DC function needs either a tester that can generate it or an adapter. Check this if you install charge points.
Insulation and continuity
Look for 250 V, 500 V and 1000 V insulation tests and 200 mA continuity, the same as a standalone insulation tester. Some testers warn you if equipment is still connected before applying the test voltage, which can save damaged appliances.
Results and certificates
Saving results and sending them to certificate software, by Bluetooth or app, saves a lot of typing on large jobs. Check that the tester works with the software you or your scheme use.
Practical points
Battery life, a display you can read in a dark cupboard, sturdy GS38-compliant leads and a strap to hang it up all matter on a full day of testing. Calibration is typically done every year, and competent person schemes expect to see the certificates.
Three testers compared
| Tester | Insulation tests | Loop testing | RCD types | Safety rating |
|---|---|---|---|---|
| Megger MFT-X1 | 50 to 1000 V, plus variable 50 to 999 V | No-trip two-wire and three-wire; high-current; high-resolution 0.001 Ω mode; PFC to 50 kA | AC, A, B, and their S versions; 6 mA DC with the EV adapter | CAT IV 300 V |
| Fluke 1664 FC | 50, 100, 250, 500, 1000 V | Loop impedance including a high-current mΩ mode | A, AC, B and S | CAT III 500 V, CAT IV 300 V |
| Kewtech KT65DL | 250, 500, 1000 V | No-trip loop, 0.01 to 2000 Ω | 10 to 500 mA test currents; RCD types not stated by the seller | CAT III 500 V, CAT IV 300 V |
Figures are from Megger's, Fluke's and the seller's published specifications. None of these specifications lists a Type F RCD setting. A Type F RCD must also meet the Type A requirements, so testers without a Type F setting are generally used on their Type A setting. Check the instrument's manual to confirm.
Megger MFT-X1
Megger's current flagship, which replaced the popular MFT1741+. It has a colour display, a rechargeable lithium-ion battery, Megger's True Loop no-trip testing, and RCD tests for types AC, A and B including selective versions. Continuity runs at over 200 mA, and results transfer to Megger's CertSuite app. It suits contractors doing a lot of certification work.
Fluke 1664 FC
Fluke's top MFT. Its Insulation PreTest checks whether appliances are still connected and stops the test if so. An auto test runs up to seven tests in one sequence, and results can go to a phone through Fluke Connect. It tests RCD types A, AC, B and S, and handles EV charge point RDC-DD checks in its variable mode.
Kewtech KT65DL
A long-running, more affordable option from a UK brand. It covers insulation at 250, 500 and 1000 V, continuity, no-trip loop testing, RCD tests from 10 to 500 mA including ramp tests, and earth electrode testing. The seller's listing doesn't state which RCD types it supports, so check that with Kewtech before buying if you install Type B devices.
Related guides
For maintenance work, a standalone insulation tester may be all you need. For three-phase work, see our guide to phase rotation testers.
Sources
The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.
- BS 7671:2018 Requirements for Electrical Installations, Table 64 and Regulation 643.3 (IET, paid standard)
- Megger MFT-X1 specifications (Test Instrument Solutions)
- Fluke 1664 FC specifications
- Kewtech KT65DL listing (CEF)
- HSE GS38: Electrical test equipment for use on low voltage electrical systems