Buying guide: insulation resistance and continuity testers

An insulation resistance tester applying 500 volts and reading over 999 megohms between conductors and earth
Beginner
How we wrote this: we haven't tested these instruments hands-on for this guide. Every figure comes from the manufacturer's own specifications, linked at the end. Models get discontinued and replaced, so check the current version before you buy. We don't earn anything if you buy one.

An insulation resistance tester applies a high DC voltage, typically 250 V, 500 V or 1000 V, between conductors that should be isolated from each other and measures the tiny current that leaks through. The result, in megohms, tells you whether cable insulation is sound. Most also include a low-resistance continuity test for protective conductors. In the UK they're essential for verifying installations to BS 7671.

Safety: insulation testing puts a high voltage on the circuit under test, and should only be carried out by a competent person on a safely isolated circuit. Disconnect or protect sensitive equipment, such as surge protective devices and electronic controls, first. The tester will discharge the circuit when the test ends, so keep the leads connected until it has.

Test voltages and minimum values

BS 7671:2018 (the IET Wiring Regulations, 18th Edition) sets the test voltage and minimum insulation resistance by the circuit's nominal voltage, in Table 64:

Circuit nominal voltageTest voltage (DC)Minimum insulation resistance
SELV and PELV250 V0.5 MΩ
Up to and including 500 V, including FELV500 V1.0 MΩ
Above 500 V1000 V1.0 MΩ

Where surge protection or other equipment can't be disconnected, the regulations allow a reduced 250 V test between the live conductors, connected together, and protective earth, but the minimum stays at 1 MΩ. Check the current edition and its amendments, and the IET's Guidance Note 3, for the full procedure. In practice a healthy new circuit usually reads far above the minimum, often hundreds of megohms, and a low or falling reading is worth investigating even if it passes.

What to look for

  • The test voltages you need. 250 V, 500 V and 1000 V cover BS 7671 work. 50 V and 100 V are useful for telecoms and sensitive equipment.
  • Continuity at 200 mA or more. BS EN 61557-4, the standard for continuity testers, requires a test current of at least 200 mA, so protective conductor readings are made with a meaningful current.
  • Range. 1000 MΩ is plenty for pass or fail testing. Higher ranges, into the tens or hundreds of gigohms, help with trending motor and cable insulation over time.
  • PI and DAR. The polarisation index (the ten-minute reading divided by the one-minute reading) and dielectric absorption ratio show whether insulation is clean and dry. They matter most for motors, generators and transformers.
  • Live circuit warning. A good tester refuses to start, or warns loudly, if it finds voltage on the circuit.
  • A remote or switched probe saves a lot of reaching when testing many circuits at a board.
  • Safety rating of at least CAT III 600 V for installation work.

Three testers compared

TesterInsulation test voltagesInsulation rangeContinuitySafety rating
Megger MIT420/250, 100, 250, 500, 1000 V, plus variable 10 to 1000 VUp to 200 GΩ200 mA (0.01 to 4 Ω)CAT IV 600 V, CAT III 1000 V
Megger MIT410/250, 100, 250, 500, 1000 VUp to 200 GΩ200 mACAT IV 600 V, CAT III 1000 V
Fluke 150750, 100, 250, 500, 1000 V0.01 MΩ to 10 GΩOver 200 mACAT IV 600 V

Megger MIT400/2 series

Megger's handheld range. The MIT420/2 adds a variable test voltage, capacitance measurement and memory for over 1,000 results to the MIT410/2, and the MIT430/2 adds Bluetooth download. All measure insulation up to 200 GΩ and support PI, DAR and pass or fail limit alarms. They're a common choice for UK electricians.

Fluke 1507

Five test voltages from 50 V to 1000 V, insulation readings from 0.01 MΩ to 10 GΩ, earth bond continuity at over 200 mA, and automatic PI and DAR. It refuses to start a test if it sees more than 30 V on the circuit, comes with a remote test probe, and is rated CAT IV 600 V. It also measures AC and DC voltage up to 600 V.

Do you need a multifunction tester instead?

If you certify installations, you'll also need loop impedance, prospective fault current and RCD tests. A multifunction tester does all of these plus insulation and continuity in one instrument. See our guide to multifunction testers. Whichever you buy, have it calibrated regularly, typically every year, and keep the certificates.

Sources

The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.