In a three-phase supply, the three phases reach their peaks in a fixed order. Swap any two and a three-phase motor runs backwards. A phase rotation tester shows the sequence, so you can check it before connecting a motor, pump or conveyor, or after work on a supply. It's much safer than finding out by bumping the motor.
Contact or non-contact
- Contact testers connect to the three phases with probes or clips. They're simple and cheap, and many need no battery because they're powered by the supply under test. You still have to touch live terminals, so use them only where you can do so safely.
- Non-contact testers clip around the insulated cables and sense the phase through the insulation. No metal touches a live part, which is safer and quicker, especially on cables you can't easily get a probe onto.
What to look for
- Voltage range that covers your systems. In the UK, a three-phase supply is 400 V between lines and 230 V to earth.
- Open-phase indication, so a missing phase isn't mistaken for a reversed one.
- Motor rotation. Some testers can also show which way an unpowered motor will turn when you spin its shaft, or a running motor's direction without contact.
- Safety rating appropriate to where you'll use it, from CAT III at distribution boards to CAT IV at the origin.
Three testers compared
| Tester | Type | Voltage range | Safety rating | Power |
|---|---|---|---|---|
| Fluke 9040 | Contact, with probes and clips | 40 to 700 V, 15 to 400 Hz | CAT III 600 V, CAT IV 300 V | No battery: powered from the circuit |
| Fluke 9062 | Contact, plus contactless motor rotation | Phase display 120 to 400 V AC, 2 to 400 Hz | CAT III 300 V | Battery |
| Hioki PD3259-50 | Non-contact sensors on the insulation | 90 to 520 V AC, 45 to 66 Hz | CAT IV, 600 V to earth | Four AA batteries, about 5 hours |
Fluke 9040
A straightforward contact tester. Its display shows all three phases and the direction of rotation, it works from 40 to 700 V, and it needs no battery. Its probes have an adjustable clamping range to suit industrial sockets.
Fluke 9062
Adds motor work to phase testing. As well as showing the supply's phase sequence, it can find the rotation direction of a running three-phase motor without contact, which helps when the shaft is hidden. Its CAT III 300 V rating means it's meant for use at equipment level, not at the origin of an installation.
Hioki PD3259-50
A non-contact tester whose three sensors clip around insulated cables from 6 to 30 mm across, with no exposed metal. It shows phase sequence and the three line-to-line and line-to-ground voltages together, and warns of reverse sequence with a red light and buzzer. Its CAT IV rating makes it suitable at the supply origin.
Related guides
Most electricians carry a phase rotation tester alongside a multifunction tester and a clamp meter. Some MFTs include phase rotation testing, so check yours before buying a separate one.