How it's worked out
Current flows out along one conductor and back along the other, so a single-phase or DC circuit loses voltage across twice the cable length:
Vdrop = 2 × I × L × R, where R is the resistance of one conductor per metre.
For a balanced three-phase load there's no current in the neutral, and the drop between lines is √3 × I × L × R.
The resistances are the maximum values allowed by IEC 60228 for copper conductors at 20 °C. For example, 2.5 mm² is 7.41 Ω per km. They're then corrected for temperature, because copper's resistance rises by about 0.393 % per °C. AWG sizes use the resistivity of annealed copper instead.
How much drop is allowed
In the UK, BS 7671 Appendix 4 gives limits from the origin of an installation supplied from the public low-voltage network: 3 % for lighting (6.9 V at 230 V) and 5 % for other uses (11.5 V). Other countries set similar limits. For 12 V and 24 V systems, a few percent is a fraction of a volt, so long runs to LED strips and pumps need thicker cable than the current alone suggests.
How accurate it is
- For copper up to 16 mm², the mV/A/m figure here matches the BS 7671 tables for 70 °C cables within rounding. For example, 18 mV/A/m for 2.5 mm² single-phase and 15 for three-phase.
- It counts resistance only. At 25 mm² and above, the cable's reactance adds noticeably on AC, so use the tables in BS 7671 or the manufacturer's data for large cables.
- At 70 °C it's slightly pessimistic for a lightly loaded cable. BS 7671 allows a correction for the real operating temperature.