Home / Tools / Cable voltage drop calculator

Cable voltage drop calculator

Work out how many volts you lose along a copper cable, as a percentage of the supply, and the longest run that keeps the drop within a limit.

  • Electrical tool
  • Runs in your browser
  • Tested 19 November 2026
  • Sources
Line to line for three-phase, for example 400.
BS 7671's voltage drop tables assume the cable is at its maximum operating temperature.

How it's worked out

Current flows out along one conductor and back along the other, so a single-phase or DC circuit loses voltage across twice the cable length:

Vdrop = 2 × I × L × R, where R is the resistance of one conductor per metre.

For a balanced three-phase load there's no current in the neutral, and the drop between lines is √3 × I × L × R.

The resistances are the maximum values allowed by IEC 60228 for copper conductors at 20 °C. For example, 2.5 mm² is 7.41 Ω per km. They're then corrected for temperature, because copper's resistance rises by about 0.393 % per °C. AWG sizes use the resistivity of annealed copper instead.

Worked example. A 20 A load at the end of 25 m of 2.5 mm² twin and earth, with the cable at 70 °C: each conductor is 8.87 Ω per km, so the drop is 2 × 20 × 25 × 0.00887 = 8.9 V, or 3.9 % of 230 V. That's within 5 % for a socket circuit but over the 3 % limit for lighting.

How much drop is allowed

In the UK, BS 7671 Appendix 4 gives limits from the origin of an installation supplied from the public low-voltage network: 3 % for lighting (6.9 V at 230 V) and 5 % for other uses (11.5 V). Other countries set similar limits. For 12 V and 24 V systems, a few percent is a fraction of a volt, so long runs to LED strips and pumps need thicker cable than the current alone suggests.

How accurate it is

  • For copper up to 16 mm², the mV/A/m figure here matches the BS 7671 tables for 70 °C cables within rounding. For example, 18 mV/A/m for 2.5 mm² single-phase and 15 for three-phase.
  • It counts resistance only. At 25 mm² and above, the cable's reactance adds noticeably on AC, so use the tables in BS 7671 or the manufacturer's data for large cables.
  • At 70 °C it's slightly pessimistic for a lightly loaded cable. BS 7671 allows a correction for the real operating temperature.
Only one check. Voltage drop is one part of sizing a cable. The cable must also carry the current in its installed conditions, and the earth fault loop impedance must let the protective device disconnect in time. Mains installation work must comply with BS 7671 or your local wiring rules, and be done or checked by a competent person.

Sources

Where the formulas and figures on this page come from. We test every tool against worked examples from these before publishing.