How AWG is defined
AWG sizes come from ASTM B258. Gauge 36 is defined as 0.005 inch (0.127 mm) diameter and 0000 (4/0) as 0.46 inch, with 38 equal ratio steps in between. That gives:
d = 0.127 mm × 92(36 − n)/39
For the sizes above 0, use n = −1 for 00 (2/0), −2 for 000 (3/0) and −3 for 0000 (4/0). Every 6 gauges halves the diameter, and every 3 gauges roughly halves the area.
Resistance
The tool uses the resistivity of standard annealed copper from IEC 60028, 1/58 Ω·mm²/m at 20 °C, so resistance per km = 17.24 ÷ area in mm². That's for a solid conductor of exactly that size. Stranded conductors and real cables are a little higher, and metric cable standards (IEC 60228) set a maximum resistance per size rather than an exact area.
Things to know
- Stranded AWG wire is specified by its total copper area, so a stranded 12 AWG has about the same area as a solid one but a larger overall diameter.
- Don't swap AWG and metric sizes when following wiring regulations. Use the current rating from the relevant standard, such as BS 7671 Appendix 4 in the UK, for the cable you actually use.