Home / Quizzes / Scottish Building Standards

Scottish Building Standards quiz for electricians

Socket numbers, switch heights, smoke and heat alarms, extract fans and building warrants, from the Scottish Government's domestic technical handbook (April 2026). FICA Section F has five questions on this.

18 questionsFICA area: Scottish Building StandardsAnswers checked against the sources shown

0 of 18 answered
  1. 1How many 13 A socket-outlets should a dwelling's kitchen have, at minimum?

    Answer: 6, with at least 3 above worktop level, plus any for floor-standing white goods or built-in appliances

    Clause 4.6.4. Single or double outlets can be used to reach the number.

    Source: Scottish Government: Building standards technical handbook, domestic (April 2026)

  2. 2How many 13 A socket-outlets should each apartment (habitable room) of a dwelling have, at minimum?

    Answer: 4

    Clause 4.6.4: 4 in each apartment, 6 in the kitchen, and an additional 4 anywhere in the dwelling, including at least 1 in each circulation area on each level.

    Source: Scottish Government: Building standards technical handbook, domestic (April 2026)

  3. 3Besides the outlets in apartments and the kitchen, what else does clause 4.6.4 recommend?

    Answer: An additional 4 anywhere in the dwelling, including at least 1 in each circulation area on each storey

    The aim is to reduce the use of adapters, which can overheat, and extension leads, which create trip hazards.

    Source: Scottish Government: Building standards technical handbook, domestic (April 2026)

  4. 4At what height should light switches be fitted in a dwelling?

    Answer: Between 900 mm and 1.1 m above floor level

    Clause 4.8.5. All outlets and controls of electrical fixtures should be no more than 1.2 m above floor level, unless a higher location is shown to be needed.

    Source: Scottish Government: Building standards technical handbook, domestic (April 2026)

  5. 5What is the minimum height above floor level for standard socket-outlets, and TV and telephone outlets?

    Answer: 400 mm

    Clause 4.8.5. Above an obstruction such as a worktop, fixtures should be at least 150 mm above the projecting surface.

    Source: Scottish Government: Building standards technical handbook, domestic (April 2026)

  6. 6How far should outlets and controls of electrical fixtures be from an internal corner or projecting wall?

    Answer: At least 350 mm

    Clause 4.8.5 applies this to sockets, switches, fire alarm call points and timer controls.

    Source: Scottish Government: Building standards technical handbook, domestic (April 2026)

  7. 7What fire detector should be fitted in every kitchen of a dwelling?

    Answer: A heat alarm

    Clause 2.11.1: at least one heat alarm in every kitchen, which is less likely to give false alarms from cooking.

    Source: Scottish Government: Building standards technical handbook, domestic (April 2026)

  8. 8Which type of smoke alarm is recommended for the principal habitable room, including one that's open plan with the kitchen?

    Answer: Optical

    Clause 2.11.3: optical alarms are more sensitive to slow, smouldering fires in furnishings, and less prone to false alarms from cooking fumes in an open plan kitchen.

    Source: Scottish Government: Building standards technical handbook, domestic (April 2026)

  9. 9What is the minimum grade of fire detection and fire alarm system for a dwelling?

    Answer: Grade D: mains powered smoke and heat alarms with an integral standby supply

    Clause 2.11.8: at least a Grade D system to BS 5839-6, with every alarm interconnected so that one sounding sets them all off.

    Source: Scottish Government: Building standards technical handbook, domestic (April 2026)

  10. 10Which circuit can mains powered smoke and heat alarms be wired from?

    Answer: An independent circuit at the main distribution board, or a separately protected, regularly used local lighting circuit

    Clause 2.11.9. On an independent circuit, nothing else should be connected except a dedicated device that monitors the mains supply to the alarms.

    Source: Scottish Government: Building standards technical handbook, domestic (April 2026)

  11. 11How far from every bedroom door should a smoke alarm in a circulation space be?

    Answer: No more than 3 m

    Clause 2.11.7: within 3 m of every bedroom door, and within 7 m of the door to a living room or kitchen.

    Source: Scottish Government: Building standards technical handbook, domestic (April 2026)

  12. 12How far below the ceiling should the sensing element of a ceiling-mounted heat alarm be?

    Answer: Between 25 mm and 150 mm

    Clause 2.11.7: smoke alarms between 25 mm and 600 mm below the ceiling and at least 300 mm from walls and light fittings; heat alarms between 25 mm and 150 mm below the ceiling.

    Source: Scottish Government: Building standards technical handbook, domestic (April 2026)

  13. 13What is the minimum intermittent extract rate for a kitchen extract fan fitted above the hob?

    Answer: 30 litres per second

    Table 3.12: 30 l/s above the hob or cooker, 60 l/s if the extract is elsewhere in the kitchen, 15 l/s for a bathroom or shower room.

    Source: Scottish Government: Building standards technical handbook, domestic (April 2026)

  14. 14What is the minimum intermittent extract rate for a bathroom or shower room?

    Answer: 15 litres per second

    Table 3.12 gives 15 l/s for a bathroom or shower room and 6 l/s for sanitary accommodation (a toilet).

    Source: Scottish Government: Building standards technical handbook, domestic (April 2026)

  15. 15Which spaces in a dwelling should have at least one lighting point?

    Answer: Every circulation space, kitchen, bathroom, toilet, and any other space of 2 m² or more

    Clause 4.6.1. A lighting point serving a stair should have switches at or near the landing on each storey.

    Source: Scottish Government: Building standards technical handbook, domestic (April 2026)

  16. 16What lighting level should common stairs in a building of flats have at floor level?

    Answer: At least 100 lux on stair flights and landings

    Clause 4.6.2: 100 lux on stair flights and landings, 50 lux elsewhere in circulation areas, with automatic control so it works in the hours of darkness.

    Source: Scottish Government: Building standards technical handbook, domestic (April 2026)

  17. 17Does electrical work in an existing house normally need a building warrant in Scotland?

    Answer: No, it's normally exempt, but it must still meet the building standards

    Schedule 3, type 1 exempts most work to or in a house, including electrical work, from needing a warrant, but regulation 5 says the work must still meet the standards. There are exceptions, such as work that adversely affects a separating wall, for example recessed sockets.

    Source: Scottish Government: Building standards technical handbook, domestic (April 2026)

  18. 18A new house has a driveway. What EV charging provision should it have?

    Answer: At least one charge point socket rated at least 7 kW next to the parking space

    Standard 7.2, clause 7.2.1, subject to the installation cost cap explained there.

    Source: Scottish Government: Building standards technical handbook, domestic (April 2026)