Home / Quizzes / Special locations (Part 7)

Special locations quiz: bathrooms, EV charging and more

Bathroom zones, socket distances, RCDs and bonding in Section 701, plus EV charging and other Part 7 locations, including what Amendment 4 changed.

14 questionsFICA area: BS 7671 Parts 1, 3, 4, 5 and 7Answers checked against the sources shown

0 of 14 answered
  1. 1In a room with a bath, how far does zone 2 extend horizontally beyond zone 1?

    Answer: 0.6 m

    Zone 2 is the area outside zone 1 for 0.6 m horizontally, up to 2.25 m from the floor or the highest fixed shower head, whichever is higher.

    Source: SELECT pocket guide: Section 701, locations containing a bath or shower

    Read more: Part P: what electrical work is notifiable in England?

  2. 2How high do zones 1 and 2 extend in a bathroom?

    Answer: 2.25 m above the floor, or to the highest fixed shower head if that is higher

    Both zones are bounded by 2.25 m above the floor or the highest fixed shower head or water outlet, whichever is higher.

    Source: SELECT pocket guide: Section 701, locations containing a bath or shower

    Read more: Part P: what electrical work is notifiable in England?

  3. 3A 13 A socket-outlet, not on a SELV circuit, is planned for a bathroom. How far horizontally from the boundary of zone 1 must it be?

    Answer: At least 2.5 m

    Section 701 prohibits socket-outlets, other than SELV ones and shaver supply units, within 2.5 m horizontally of the zone 1 boundary. Older editions used 3 m. Sockets outside that distance also need 30 mA RCD protection.

    Source: SELECT pocket guide: Section 701, locations containing a bath or shower; Electrical Safety First Best Practice Guide 4: EICR classification codes

    Read more: EICR codes explained: C1, C2, C3 and FI (Amendment 4)

  4. 4What is the minimum degree of protection for electrical equipment installed in zone 2 of a bathroom?

    Answer: IPX4

    Equipment in zones 1 and 2 needs at least IPX4, protection against splashing from any direction, and must also be suitable according to the manufacturer's instructions.

    Source: SELECT pocket guide: Section 701, locations containing a bath or shower

  5. 5Which low voltage circuits in a location containing a bath or shower need additional protection by a 30 mA RCD?

    Answer: All circuits serving the location, and any passing through zones 1 or 2

    Section 701 requires one or more 30 mA RCDs for every low voltage circuit serving the room, including lighting, and for circuits that pass through zones 1 or 2 even if they don't serve the room.

    Source: SELECT pocket guide: Section 701, locations containing a bath or shower

  6. 6When can local supplementary bonding be left out in a bathroom, in a building with suitable main protective bonding?

    Answer: When all three listed conditions are met: automatic disconnection, 30 mA RCDs on all final circuits, and all extraneous-conductive-parts bonded

    All final circuits of the location must meet the requirements for automatic disconnection, all must have 30 mA RCD protection, and all extraneous-conductive-parts must be effectively connected to the protective equipotential bonding. If any one isn't met, supplementary bonding is needed.

    Source: SELECT pocket guide: Section 701, locations containing a bath or shower

  7. 7The space under a bath can only be reached by removing a panel with a tool. Which zone is it in?

    Answer: Outside the zones

    Space under a bath or shower tray is zone 1 if it can be reached without a tool, and outside the zones if a tool is needed.

    Source: SELECT pocket guide: Section 701, locations containing a bath or shower

  8. 8For a shower without a basin, such as a wet room, how far does zone 1 extend horizontally?

    Answer: 1.2 m from the centre point of the fixed water outlet

    With no basin there's no zone 2. Instead zone 1 extends 1.2 m from the centre of the fixed water outlet on the wall or ceiling.

    Source: SELECT pocket guide: Section 701, locations containing a bath or shower

    Read more: Part P: what electrical work is notifiable in England?

  9. 9What additional protection does each EV charging point need under Section 722?

    Answer: A 30 mA RCD of at least Type A, plus protection against DC fault current, such as a Type B RCD or a Type A with a 6 mA DC detecting device

    A car's charger can leak smooth DC current that blinds an ordinary RCD, so Section 722 requires a Type B RCD, or a Type A RCD with a residual direct current detecting device (RDC-DD) that trips at 6 mA DC. Many chargers have the DC detection built in.

    Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)

    Read more: EV charger installation at home: what UK rules require

  10. 10On a TN-C-S (PME) supply, when can the PME earth be used for a charge point that charges a car outdoors?

    Answer: Only when one of the protective measures listed in Section 722 is in place, such as open-PEN protection

    A broken PEN conductor could raise the car body towards line voltage, so Regulation 722.411.4.1 requires a listed measure: for example a charger with built-in open-PEN protection, a separate earth electrode, or a separate open-PEN device.

    Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)

    Read more: EV charger installation at home: what UK rules require

  11. 11Under Section 708, what earthing arrangement must not be used for the socket-outlets on caravan park pitches?

    Answer: A PME earthing terminal

    Section 708 doesn't allow a PME earth for the socket-outlets on caravan park pitches, because of the danger to people outdoors from a broken PEN conductor.

    Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)

    Read more: Earthing systems explained: TN-S, TN-C-S (PME) and TT

  12. 12What did Amendment 4 (2026) say about AFDDs on circuits supplying EV charging equipment with BS EN IEC 62196-2 sockets or connectors?

    Answer: They are not required

    Amendment 4 added Regulation 722.421.1.7.201, which makes clear that AFDDs aren't required on these circuits.

    Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)

    Read more: EV charger installation at home: what UK rules require

  13. 13Which new section did Amendment 4 add for distributing extra-low voltage DC power over telecommunications cabling?

    Answer: Section 716, Power over Ethernet

    Section 716 is new in Amendment 4. Chapter 57, also new, covers stationary secondary batteries, and Section 722 is EV charging.

    Source: Electrical Safety First: BS 7671:2018+A4:2026 and domestic installations, pocket guide (April 2026)

  14. 14Under Amendment 4, how are stationary batteries used for energy storage treated?

    Answer: As generating sets, not as loads

    Amendment 4 clarifies in Section 551 that stationary batteries are treated as generating sets, and adds Chapter 57 for stationary secondary batteries.

    Source: Electrical Safety First: BS 7671:2018+A4:2026 and domestic installations, pocket guide (April 2026)

Written by us to help you revise. Not affiliated with SJIB, SECTT, the IET or City & Guilds. Questions follow BS 7671:2018+A4:2026 and the other documents named in each answer. If you think an answer is wrong, tell us and we'll check it against the source.