Home / Quizzes / Safe isolation

Safe isolation quiz

Proving dead, locking off and the law behind it. FICA Section D needs 100%, so this is worth knowing cold.

10 questionsFICA area: Health and safetyAnswers checked against the sources shown

0 of 10 answered
  1. 1Which kind of instrument should you use to prove a circuit dead?

    Answer: A two-pole voltage indicator to GS38, made to BS EN 61243-3

    Electrical Safety First's guidance advises against non-contact detectors, which can miss a live conductor, and multimeters, which can be set to the wrong range.

    Source: Electrical Safety First Best Practice Guide 2: Safe isolation; HSE GS38: Electrical test equipment for use on low voltage electrical systems

    Read more: Safe isolation: the step-by-step procedure

  2. 2Under GS38, test probe tips should have no more than how much exposed metal?

    Answer: 4 mm, and preferably 2 mm or less

    GS38 recommends no more than 4 mm of exposed tip, preferably 2 mm or less, or spring-loaded retractable shrouds, plus finger barriers.

    Source: HSE GS38: Electrical test equipment for use on low voltage electrical systems

    Read more: Safe isolation: the step-by-step procedure

  3. 3Why do you prove the voltage indicator on a proving unit again after testing the circuit dead?

    Answer: To show it didn't fail during the test, which would make a live circuit look dead

    A failed indicator reads the same as a dead circuit. Proving it before and after the test shows the 'dead' reading was real.

    Source: Electrical Safety First Best Practice Guide 2: Safe isolation

    Read more: Safe isolation: the step-by-step procedure

  4. 4How many tests are needed to prove a single-phase circuit dead at the point of work?

    Answer: 3: L–N, L–E and N–E

    Test between every combination of conductors. The N–E test catches a neutral carrying current from another circuit, such as a borrowed neutral.

    Source: Electrical Safety First Best Practice Guide 2: Safe isolation

    Read more: Safe isolation: the step-by-step procedure

  5. 5How many tests are needed to prove a three-phase supply with neutral dead?

    Answer: 10

    L1–L2, L2–L3, L3–L1, each line to neutral (3), each line to earth (3) and N–E: 10 in total.

    Source: Electrical Safety First Best Practice Guide 2: Safe isolation

    Read more: Safe isolation: the step-by-step procedure

  6. 6What is the right way to secure an isolation?

    Answer: Lock it off with your own padlock, keep the key, and fit a warning notice

    Tape isn't a lock. If others work on the same circuit, each fits their own lock using a multi-lock hasp.

    Source: Electrical Safety First Best Practice Guide 2: Safe isolation

    Read more: Safe isolation: the step-by-step procedure

  7. 7Where should you test that a circuit is dead?

    Answer: At the point of work

    The circuit may be fed from somewhere you don't expect, so test every conductor where you'll actually be working, including switch drops and strappers.

    Source: Electrical Safety First Best Practice Guide 2: Safe isolation

    Read more: Safe isolation: the step-by-step procedure

  8. 8You switch off the main switch in a house with solar PV and a battery. What is still live?

    Answer: The meter tails, and the PV and battery systems, which have their own isolators

    The main switch doesn't isolate the supply side, and generating or storage systems are separate sources. Check for every source before you start.

    Source: Electrical Safety First Best Practice Guide 2: Safe isolation

    Read more: Safe isolation: the step-by-step procedure

  9. 9Which regulation of the Electricity at Work Regulations 1989 requires suitable means for cutting off the supply and for isolation?

    Answer: Regulation 12

    Regulation 12 covers means for cutting off the supply and for isolation, and defines isolation as disconnection and separation from every source in a way that is secure.

    Source: The Electricity at Work Regulations 1989

    Read more: Safe isolation: the step-by-step procedure

  10. 10Which regulation of the Electricity at Work Regulations 1989 requires precautions to stop equipment that has been made dead from becoming charged during the work?

    Answer: Regulation 13

    Regulation 13: adequate precautions shall be taken to prevent equipment made dead from becoming electrically charged during the work, if danger may arise. Locking off is how you meet it.

    Source: The Electricity at Work Regulations 1989

    Read more: Safe isolation: the step-by-step procedure