Safe isolation: the step-by-step procedure

Safe isolation: a circuit-breaker locked off with a padlock and a warning tag, a two-pole voltage indicator, and the steps isolate, lock, prove, test, prove again
Beginner

Most electrical accidents during installation work happen on circuits that people thought were dead. Safe isolation is the routine that makes sure they really are. It takes a couple of minutes, and it's the same every time, for a socket swap or a new consumer unit.

The law. The Electricity at Work Regulations 1989 require a suitable means of cutting off and isolating the supply (Regulation 12), adequate precautions to stop equipment that's been made dead becoming live again (Regulation 13), and no live working unless it's unreasonable for the work to be done dead and suitable precautions are taken (Regulation 14).

What you need

  • A two-pole voltage indicator (a proprietary test lamp or voltage detector) that meets HSE GS38 and is made to BS EN 61243-3. Electrical Safety First's guidance advises against using a multimeter to prove dead, as it can be set to the wrong range, and against non-contact detectors, which can miss a live conductor.
  • A proving unit to check the indicator works, or a known live source.
  • Locking devices to fit the breakers, fuse carriers or switches you're using, a padlock with a unique key, and a warning notice.

GS38 also sets out what good test leads look like: probes with no more than 4 mm of exposed metal tip, and preferably 2 mm or less, or spring-loaded retractable shrouds. They should have finger barriers, and leads should be in good condition. Inspect them before every use.

The procedure

  1. Get permission and identify the circuit. Agree the isolation with whoever is in control of the premises, and identify the correct point of isolation. Don't trust circuit labels on their own.
  2. Isolate. Switch off, or remove the fuse, at the point of isolation. Check for other sources: a second supply, a generator, a UPS, solar PV or a battery system.
  3. Secure the isolation. Lock it off with your own padlock and keep the key on you. Fit a warning notice. Insulating tape over a breaker is not a lock.
  4. Prove your voltage indicator works on the proving unit or a known live supply.
  5. Test that the circuit is dead at the point of work, between every combination of conductors (see below).
  6. Prove the indicator again on the proving unit. This proves it didn't fail during the test, which would make a live circuit look dead.
  7. Start work. If you leave the job, the lock stays on. If anyone else works on the circuit, they fit their own lock, using a multi-lock hasp.

Which conductors to test

SupplyTestsNumber
Single-phaseL–N, L–E, N–E3
Three-phase with neutralL1–L2, L2–L3, L3–L1, L1–N, L2–N, L3–N, L1–E, L2–E, L3–E, N–E10

The N–E test catches a neutral that's carrying current from another circuit, which happens with borrowed neutrals and shared neutrals on three-phase boards. Test every conductor at the point of work, including those in switch drops and strappers.

Common mistakes

  • Testing at the board instead of at the point of work, where the circuit may be fed from somewhere else.
  • Skipping the second prove. A voltage indicator can fail at any time, and a dead indicator reads the same as a dead circuit.
  • Assuming switching off the main switch isolates everything. It doesn't isolate the meter tails, and it doesn't isolate solar PV or battery systems, which have their own isolators.
  • Using a socket tester or a non-contact detector to "prove dead".

Once the circuit is isolated you can start dead testing. See the ring final circuit testing guide and the insulation resistance guide. For choosing test equipment, see our multifunction tester buying guide.

Sources

The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.