Home / Learn / Electrical installations

Insulation resistance testing: test voltages, minimum values and method

An insulation resistance tester at 500 V DC reading more than 999 megohms between the line and neutral conductors joined together and earth, across a twin and earth cable
Beginner

An insulation resistance test checks that the insulation between conductors, and between conductors and earth, is sound. It applies a DC test voltage, higher than the normal working voltage, and measures the tiny leakage current to work out a resistance in megohms. It finds damaged cables, screws through cables, moisture, and wiring mistakes such as a neutral touching earth.

Test voltages and minimum values

These come from BS 7671 Table 64.

Circuit nominal voltageTest voltage (DC)Minimum insulation resistance
SELV and PELV250 V0.5 MΩ
Up to and including 500 V (including 230 V and 400 V)500 V1 MΩ
Above 500 V1000 V1 MΩ

The minimum is a pass mark, not a target. A new installation will normally read hundreds of megohms, often more than the tester's top range. A reading that passes but is far lower than similar circuits is worth investigating.

Before you test

  • Isolate the circuit or installation safely. The test voltage can damage equipment and give someone a nasty shock.
  • Disconnect anything that could be damaged or affect the reading: surge protective devices, electronic equipment such as dimmers, timers, smart switches, LED drivers and appliances, and anything the manufacturer says to disconnect. Remove lamps.
  • Close switches so the whole circuit is tested. With two-way switching, test with the switches in both positions, so each strapper is tested.

If equipment can't reasonably be disconnected, BS 7671 Regulation 643.3.3 allows testing before it's connected, then a 250 V DC test between live conductors and the protective conductor once it is. That test must read at least 1 MΩ.

The tests

  1. Between live conductors: line to neutral. On three-phase, each line to every other line, and each line to neutral.
  2. Between live conductors and earth: line and neutral joined together, tested to the protective conductor. Joining them is quicker and tests both at once. If the reading is low, separate them to find which is at fault.

You can test a whole distribution board at once, from the main switch with all the breakers on. Remember the circuits are then in parallel, so the combined reading is lower than any one circuit. If it's low, test circuit by circuit to find the culprit.

Parallel readings. Ten circuits that each read 200 MΩ give a combined reading of 20 MΩ, because insulation resistances in parallel combine like resistors: 1 ÷ (10 ÷ 200) = 20 MΩ. Use the series and parallel calculator for mixed values.

What low readings usually mean

  • Line or neutral to earth low: damaged insulation, a nail or screw through a cable, water in a back box or outside light, or a piece of equipment left connected.
  • Neutral to earth low only: often a neutral touching earth in an accessory, or a borrowed neutral from another circuit.
  • Line to neutral very low: a lamp, transformer or appliance still connected, or a short circuit.

Safety

  • Long cables and capacitive loads store charge from the test. Most testers discharge the circuit automatically when the test button is released. Keep the leads connected until the voltage has fallen, before you touch the conductors.
  • Use leads that meet HSE GS38, and keep your fingers behind the barriers.
  • Always check against the current edition of BS 7671 and the equipment manufacturer's instructions.

For all the test limits in one place, see the BS 7671 test values cheat sheet. To choose a tester, see our insulation tester buying guide.

Sources

The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.