Home / Reference

BS 7671 test values cheat sheet: Zs, insulation resistance, RCDs and continuity

A clipboard of test results next to a multifunction tester: Zs, insulation resistance, RCD trip time and continuity, each with a tick
Beginner

The numbers you compare test results with, on one page. They're for single-phase 230 V installations to BS 7671:2018 with Amendment 2. Always check against the current edition and your own copy of the On-Site Guide or Guidance Note 3, and remember that inspection and testing must be carried out by a competent person.

Amendment 4 (2026). BS 7671:2018+A4:2026 was published in April 2026 and must be used from 15 October 2026. Check whether any values below have changed in your copy.

Maximum measured earth fault loop impedance (Zs)

These are the maximum values for a reading taken at normal room temperature. They're lower than the BS 7671 Table 41.3 values because conductors get hotter, and their resistance rises, in use. They match the IET On-Site Guide's Table B6. For any rating or older BS 3871 breakers, use the maximum Zs calculator.

Maximum measured Zs (Ω) at ambient temperature, circuit-breakers to BS EN 60898 and RCBOs to BS EN 61009, U₀ 230 V
Type6 A10 A16 A20 A25 A32 A40 A50 A63 A
B5.833.502.191.751.401.100.880.700.56
C2.921.751.100.880.700.550.440.350.28
D (0.4 s)1.460.880.550.440.350.28–––
D (5 s)2.921.751.100.880.700.550.440.350.28

The D type 0.4 s row stops at 32 A, as it does in the On-Site Guide.

Insulation resistance (BS 7671 Table 64)

Circuit voltageTest voltage (DC)Minimum insulation resistance
SELV and PELV250 V0.5 MΩ
Up to and including 500 V, including FELV (most 230 V and 400 V circuits)500 V1.0 MΩ
Above 500 V1000 V1.0 MΩ

A reading that meets the minimum but is much lower than similar circuits, or below about 2 MΩ, is worth investigating. Disconnect or isolate surge protective devices and sensitive electronic equipment before testing, or test at 250 V where BS 7671 allows it.

RCDs

  • Test at the rated residual operating current, IΔn, with an AC test current.
  • General (non-delayed) RCDs: must trip within 300 ms.
  • S type (time-delayed): must trip between 130 ms and 500 ms.
  • Since Amendment 2 (2022) the 5 × IΔn and ½ × IΔn tests aren't required, though they can still help with fault finding.
  • TT systems: RA × IΔn must not exceed 50 V, so 1,667 Ω for a 30 mA RCD. An electrode resistance above 200 Ω may not be stable.

The RCD test calculator checks a reading for you.

Ring final circuit continuity

Measure each loop end to end: line (r1), neutral (rn) and cpc (r2).

  • r1 and rn should be the same, within 0.05 Ω.
  • For 2.5/1.5 mm² twin and earth, r2 should be about 1.67 × r1, the ratio of the cross-sections.
  • After cross-connecting line to cpc, the reading at each socket should be about (r1 + r2) ÷ 4. The highest of these readings is R1 + R2 for the circuit. Sockets wired as spurs read higher.

As a guide, 2.5 mm² copper is about 7.41 mΩ per metre and 1.5 mm² about 12.1 mΩ per metre at 20 °C, so a ring of 50 m of 2.5/1.5 mm² cable has r1 ≈ 0.37 Ω and r2 ≈ 0.61 Ω.

Typical maximum Ze quoted by network operators

  • TN-C-S (PME): 0.35 Ω
  • TN-S (cable sheath earth): 0.8 Ω
  • TT: 21 Ω is quoted for the supply side only. The installation's own earth electrode is usually much higher, which is why TT systems rely on RCDs.

These are the figures used for design when the actual value isn't known. Always measure.

Sources

The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.

  • BS 7671:2018+A2 Tables 41.1 and 41.3, and Appendix 3 (IET, paid standard). Check the current amendment.
  • IET On-Site Guide, Appendix B Table B6: maximum measured earth fault loop impedance at ambient temperature (paid)
  • IET Wiring Matters (July 2022): Changes to RCD testing in BS 7671:2018+A2:2022
  • BS 7671 Regulation 411.5.3 and Table 41.5 (RA × IΔn ≤ 50 V; IET, paid standard)
  • IEC 60228: Conductors of insulated cables (maximum resistance values, paid standard)