Testing an RCD to BS 7671
Since Amendment 2 (2022), BS 7671 requires one test: an AC test at the RCD's rated residual operating current, IΔn. A general (non-delayed) RCD must trip within 300 ms. A time-delayed S type must trip between 130 ms and 500 ms. The tests at 5 × IΔn and at half IΔn are no longer required, though the half-IΔn test (which should not trip it) can still help track down nuisance tripping. The test button should be checked too, and the result recorded.
The product standards (BS EN 61008 and BS EN 61009) also set a time at 5 × IΔn: within 40 ms for a general RCD, and 50 to 150 ms for an S type. The tool shows these for reference.
TT systems: maximum earth electrode resistance
On a TT system the earth fault current is too small for a circuit-breaker to clear, so an RCD provides fault protection. BS 7671 Regulation 411.5.3 requires RA × IΔn ≤ 50 V, where RA is the resistance of the earth electrode and protective conductors. So the maximum is RA = 50 V ÷ IΔn: 1,667 Ω for 30 mA, 500 Ω for 100 mA, 167 Ω for 300 mA and 100 Ω for 500 mA. These match BS 7671 Table 41.5.
Things to know
- The IET's guidance notes that an electrode resistance above about 200 Ω may not be stable, because soil dries out and freezes. Aim well below the limit.
- Additional protection for sockets and cables in walls needs a 30 mA RCD (BS 7671 Regulation 411.3.3 and 522.6.202).
- Check the RCD type suits the load (AC, A, F or B). Electric vehicle chargers and some inverters need type A with 6 mA DC detection, or type B.
- Always check against the current edition of BS 7671. Testing must be done by a competent person with a suitable tester.