How it works
Fault current is the supply voltage divided by the impedance of the loop the current flows round.
- Earth fault, for example a kettle element breaking down to its metal case: the current goes out along the line conductor and back along the protective conductor (cpc) and the supply's earth path.
I = U₀ / (Ze + R1 + R2). - Short circuit, line to neutral, for example a damaged flex where the cores touch:
I = U₀ / (ZL-N + R1 + Rn), where ZL-N = U₀ ÷ PSCC at the origin. - For a fault in an appliance, the resistance of both cores of its flex is added, using the IEC 60228 values for flexible (class 5) copper, such as 26 mΩ/m for 0.75 mm².
The tool gives two figures for each. The maximum uses conductors at 20 °C and U₀ = 230 V. The minimum uses conductors at 70 °C and 0.95 × U₀, the same assumptions as BS 7671 Table 41.3. The minimum is the one that decides whether the breaker disconnects in time.
Will the breaker trip instantly?
BS EN 60898 circuit-breakers have an instantaneous (magnetic) trip that operates within 0.1 s once the current reaches the top of their band: 5 × In for type B, 10 × In for type C and 20 × In for type D. Below that, only the slower thermal trip works, which can take seconds or minutes, too slow to meet the 0.4 s limit for final circuits. So the key check is whether the minimum fault current reaches that figure.
Plug fuses
For an appliance on a plug, the BS 1362 fuse in the plug and the circuit-breaker both see the fault current. At a few hundred amps both act very quickly, and which one goes first isn't guaranteed. The plug fuse is there mainly to protect the flex.
Breaking capacity
Every protective device must be able to break the largest fault current at the point where it's installed. Compare the PSCC at the origin with the rating marked on the breaker (Icn, often 6 kA or 10 kA). Domestic consumer units to BS EN 61439-3 are commonly given a conditional rating of 16 kA when supplied through a BS 88-3 cut-out fuse of up to 100 A, which is why a higher PSCC is often acceptable there. Check the manufacturer's data and the current edition of BS 7671.
Things to know
- Three-phase PSCC is roughly twice the single-phase line-to-neutral value. That's the rule of thumb in IET Guidance Note 3.
- The supply voltage in the UK can be up to 253 V (230 V +10 %), so real fault currents can be up to 10 % higher than the maximum shown.
- Measured values always beat calculated ones. Use a loop tester to confirm Zs and PFC on site.