EICR codes quiz: C1, C2, C3 and FI
Code the observation. Based on Electrical Safety First's Best Practice Guide 4 and Amendment 4's changes to periodic reports.
1What does code C1 mean on an EICR?
Answer: Danger present: immediate remedial action required
A C1 means there's a risk of injury now. The inspector should make it safe there and then, with the client's agreement.
Source: Electrical Safety First Best Practice Guide 4: EICR classification codes
Read more: EICR codes explained: C1, C2, C3 and FI (Amendment 4)
2What does code C2 mean?
Answer: Potentially dangerous: urgent remedial action required
Not dangerous right now, but it would become dangerous if a fault or another foreseeable event happened.
Source: Electrical Safety First Best Practice Guide 4: EICR classification codes
Read more: EICR codes explained: C1, C2, C3 and FI (Amendment 4)
3Since Amendment 4, what effect does an FI code have on the overall outcome of a report?
Answer: It doesn't make the report unsatisfactory on its own
FI and C3 observations now go in a separate part of the report and don't decide the outcome. Only C1 and C2 make it unsatisfactory. FI now means 'further investigation is advised'.
Source: Electrical Safety First Best Practice Guide 4: EICR classification codes; Electrical Safety First: BS 7671:2018+A4:2026 and domestic installations, pocket guide (April 2026)
Read more: EICR codes explained: C1, C2, C3 and FI (Amendment 4)
4A consumer unit has a missing blank, so live parts can be touched with a finger. How is it coded?
Answer: C1
Accessible live parts are a danger present.
Source: Electrical Safety First Best Practice Guide 4: EICR classification codes
Read more: EICR codes explained: C1, C2, C3 and FI (Amendment 4)
5There's no main protective bonding to the incoming gas pipe. How is it coded?
Answer: C2
Best Practice Guide 4 codes absent main bonding, or bonding smaller than 6 mm², as C2.
Source: Electrical Safety First Best Practice Guide 4: EICR classification codes
Read more: EICR codes explained: C1, C2, C3 and FI (Amendment 4)
6A circuit's insulation resistance reads 0.6 MΩ. How should it be coded?
Answer: C2
Insulation resistance below 1 MΩ is C2. The IET's view is that it should get a proper code rather than FI.
Source: Electrical Safety First Best Practice Guide 4: EICR classification codes
Read more: EICR codes explained: C1, C2, C3 and FI (Amendment 4)
7A Type AC RCD is fitted where a Type A is required. How is it coded?
Answer: C3
Best Practice Guide 4 codes this as improvement recommended.
Source: Electrical Safety First Best Practice Guide 4: EICR classification codes
Read more: EICR codes explained: C1, C2, C3 and FI (Amendment 4)
8An older installation is wired in red and black, with no other defects. How is it coded?
Answer: It isn't coded
Old cable colours are a non-compliance with today's standard, not a danger. A notice should be fitted where old and new colours meet.
Source: Electrical Safety First Best Practice Guide 4: EICR classification codes
Read more: EICR codes explained: C1, C2, C3 and FI (Amendment 4)
9A ring final circuit has a broken conductor. How is it coded?
Answer: C2
Best Practice Guide 4 lists a ring with a broken conductor as C2, potentially dangerous. So is a borrowed neutral shared between circuits.
Source: Electrical Safety First Best Practice Guide 4: EICR classification codes
Read more: EICR codes explained: C1, C2, C3 and FI (Amendment 4)
10A single-family house has no AFDDs. How is it recorded?
Answer: As an observation only, with no code
No AFDD is C3 only in high-rise residential buildings, HMOs, purpose-built student accommodation and care homes.
Source: Electrical Safety First Best Practice Guide 4: EICR classification codes
Read more: AFDDs explained: arc fault detection devices and where BS 7671 requires them
11A socket-outlet, not SELV or a shaver socket, is 1.5 m horizontally from the edge of zone 1 in a bathroom. How is it coded?
Answer: C2
Section 701 requires 2.5 m, and Best Practice Guide 4 codes a socket inside that distance as C2.
Source: Electrical Safety First Best Practice Guide 4: EICR classification codes; SELECT pocket guide: Section 701, locations containing a bath or shower
Read more: EICR codes explained: C1, C2, C3 and FI (Amendment 4)