An arc fault detection device (AFDD), made to BS EN 62606, switches a circuit off when it detects the electrical signature of a dangerous arc. Arcs from damaged cables and loose connections are a known cause of electrical fires, and neither a circuit-breaker nor an RCD can reliably see them.
Arcs that other devices miss
- Series arc: a break or loose connection in one conductor, such as a crushed flex, a nail through a cable or a loose terminal. The current still flows through the arc, so it's never more than the normal load current. A circuit-breaker won't trip, and because no current leaks to earth, an RCD won't either. A series arc of a few amps can still be hot enough to start a fire.
- Parallel arc between line and neutral: the current can be high but is chopped up and intermittent, so it may not reach a breaker's instant trip level. There's no leakage to earth, so an RCD won't see it.
- Parallel arc to earth: an RCD will usually catch this one.
An AFDD watches the current waveform for the high-frequency noise and patterns that arcing produces, and uses its built-in logic to tell those apart from normal switching, motors and dimmers. Many AFDDs on sale are combined with an RCBO in one unit.
Where BS 7671 requires AFDDs
Regulation 421.1.7 says AFDDs shall be provided for single-phase AC final circuits supplying socket-outlets rated up to 32 A in:
- high-rise residential buildings (HRRBs);
- houses in multiple occupation (HMOs);
- purpose-built student accommodation;
- care homes.
For all other premises, AFDDs to BS EN 62606 are recommended for those circuits, not required.
What Amendment 4 changed
Amendment 2 (2022) used the term "higher risk residential buildings". Amendment 4 (2026) changed it to "high-rise residential buildings", to avoid confusion with "higher-risk buildings" in the Building Safety Act 2022, which mean something different. NICEIC's guidance gives the BS 7671 meaning as a residential building over 18 metres high or with more than six storeys, counting the ground floor. SELECT and BEAMA both confirm the list of places where AFDDs shall be fitted is otherwise unchanged.
Amendment 4 also says AFDDs aren't required on circuits supplying EV charge points with BS EN IEC 62196-2 sockets or connectors. And BS 7671 doesn't require them on circuits supplying battery storage.
How AFDDs are coded on an EICR
Electrical Safety First's Best Practice Guide 4 (issue 7.4) codes:
- no AFDD in an HRRB, HMO, purpose-built student accommodation or care home as C3, improvement recommended;
- no AFDD anywhere else as an observation only, with no code.
So a home without AFDDs isn't unsafe or unsatisfactory because of it. Like most of BS 7671, the requirement applies to new work, not retrospectively.
Things to know before fitting them
- They take more room than a standard breaker; check the consumer unit has space and that the AFDD is approved by the consumer unit's manufacturer.
- Most need a neutral connection and draw a little standby power.
- Use the test button as the manufacturer instructs. Many AFDDs also self-test, and some show why they last tripped with indicator lights, which helps fault finding.
- Unwanted tripping can happen with some older or faulty equipment, such as worn brushed motors. If an AFDD keeps tripping, treat it as a fault to investigate, not a reason to remove it.
- An AFDD doesn't replace good workmanship. Most arcing faults start at poor terminations, so tight, correctly made connections matter most.
Sources
The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.
- BS EN 62606: General requirements for arc fault detection devices (paid)
- NICEIC: Understanding BS 7671:2018+Amendment 4:2026 (changes and FAQs, including FI and AFDD terminology)
- SELECT: So what's new? Overview of BS 7671:2018+Amendment 4:2026
- BEAMA (via EDA): BS 7671:2018+A4:2026 overview, including AFDD and Section 722 changes
- Electrical Safety First Best Practice Guide 4: Electrical installation condition reporting, classification codes (Issue 7.4, August 2026)