A surge protective device (SPD) limits short voltage spikes, called transient overvoltages, to a level the installation and connected equipment can withstand. Since the 18th Edition, SPDs have become a normal part of new consumer units, and many people ask whether they need one. This guide explains what they do and what BS 7671 says.
What causes surges
Transient overvoltages are very short, from microseconds up to about a millisecond, but they can reach thousands of volts. They come from two main sources:
- Lightning, usually not a direct strike on the building but a strike on or near overhead power or telephone lines, whose surge travels along the lines into nearby properties.
- Switching of large inductive or capacitive loads such as motors, transformers and capacitor banks, on site or nearby. The IET notes that heat pumps, EV chargers and speed-controlled appliances make switching transients more common in homes than they used to be.
A big surge can destroy equipment at once. Smaller, repeated ones can damage electronics gradually, so failures show up later.
When BS 7671 requires SPDs
Regulation 443.4.1 of BS 7671:2018+A2:2022, unchanged in principle by Amendment 4, says protection against transient overvoltages shall be provided where the consequence caused by overvoltage could result in:
- serious injury to, or loss of, human life;
- failure of a safety service, as defined in Part 2;
- significant financial or data loss.
For all other cases, protection shall be provided unless the owner of the installation declares that it isn't required, because any loss or damage would be tolerable and they accept the risk of damage to equipment and any consequential loss.
So for a typical home, SPDs are the default, and leaving them out is the owner's informed decision. SPDs are also needed where the building has a lightning protection system. Regulation 443.4.2 adds that protection should be considered where equipment on site is likely to produce switching overvoltages exceeding the rated impulse voltage of other equipment.
Existing installations
As the IET points out, installations built to earlier editions may not comply with the current one in every respect, and that doesn't necessarily make them unsafe or mean they must be upgraded. A home without SPDs isn't dangerous because of it. When work is done, though, the electrician should give you the information to decide whether to add them.
Type 1, 2 and 3 SPDs
| Type | Where it goes | Handles |
|---|---|---|
| Type 1 | At the origin, such as the main distribution board | Partial lightning currents; needed where there's a lightning protection system or a risk of direct strikes to the supply |
| Type 2 | Consumer units and sub-distribution boards | Indirect lightning and switching surges: the usual domestic choice |
| Type 3 | Close to the protected equipment | A final layer; must only be installed as a supplement to a Type 2 |
Combined Type 1 and 2 SPDs are available and are often fitted in consumer units. Where more than one SPD is used, they must be coordinated (Regulation 534.4.4.5), and SPDs from different makers must be confirmed as suitable together.
How they're installed
- Usually inside the consumer unit, or in a small enclosure next to it if there's no room.
- Short connecting leads matter. The voltage the equipment sees is the SPD's protection level plus the voltage across its connecting leads during the surge, so leads are kept as short and straight as possible.
- The SPD needs the overcurrent protection its maker specifies, often a dedicated circuit-breaker.
- Most have a status window or indicator. When it shows the end of life, the SPD or its plug-in module must be replaced.
- Surges also arrive on telephone, broadband and aerial cables, so protecting those may be worth considering too.
A plug-in "surge-protected" extension lead is a Type 3-style device. It helps the equipment plugged into it but doesn't protect the rest of the installation.
Going deeper
Rated impulse voltage categories
Table 443.2 groups equipment by the impulse voltage it must withstand. For a 230/400 V installation, equipment at the origin (category IV) is rated at 6 kV, distribution equipment (category III) at 4 kV, appliances (category II) at 2.5 kV, and sensitive equipment (category I) at 1.5 kV. The SPD's voltage protection level Up, plus the drop on its leads, must stay below the withstand of the equipment it protects. That's why a Type 2 SPD with a Up around 1.5 kV is the usual choice in a consumer unit.
Why lead length matters, in numbers
A surge current rises in microseconds, and a conductor's inductance is roughly 1 µH per metre. With a surge of 5 kA rising in about 8 µs, the voltage across 1 m of lead is roughly L × di/dt = 1 µH × 5,000 A ÷ 8 µs, about 625 V, which adds directly to the SPD's protection level. Halving the lead length halves that addition. BS 7671's Section 534 sets out lead length requirements and connection arrangements.
The risk assessment route
The 2018 edition offered a calculated risk level (CRL) method for deciding whether SPDs were needed. The Amendment 2 (2022) wording quoted by the IET is simpler: SPDs are mandatory in the listed cases and the default everywhere else unless the owner declares them unnecessary. Section 443 also allows a full risk assessment to BS EN 62305-2 for lightning, which is the route for larger buildings.
Where on the earthing system they connect
SPD connection arrangements depend on the earthing system and whether the SPD is upstream or downstream of an RCD. Section 534 shows the permitted arrangements: on a TT system upstream of an RCD, for example, a "3+1" arrangement is used, with a spark-gap type device between neutral and earth.
Sources
The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.