New to this? Read from the top. Already know the basics? Jump to Going deeper for intermediate and advanced detail.

A metal consumer unit with a 100 amp main switch, a surge protective device with a green status window, and a row of RCBOs, each with its own test button
Beginner

The consumer unit, still often called the fuse box, is where the supply from your meter is split into separate circuits, each with its own protection. Knowing what's in it helps you reset a trip safely, understand an electrician's quote, and spot an old board that's due for an upgrade.

Never take the cover off a consumer unit. Parts behind it, including the main switch's incoming terminals and the meter tails, stay live even with the main switch off. Only a competent person should work inside one.

What's inside

DeviceWhat it protects againstHow to spot it
Main switchIsolates the whole installation (it doesn't trip on faults)Largest switch, labelled "main switch", usually 100 A
MCB (circuit-breaker)Overload and short circuit on one circuitRated in amps with a type letter, such as B32
RCDEarth leakage: electric shock and some fire risks. Usually covers a group of circuitsHas a "T" test button and a mA rating, normally 30 mA
RCBOAn MCB and an RCD in one device, for one circuitSingle-circuit device with a test button and both ratings
SPDTransient overvoltages (surges)Status window, often green when healthy
AFDDArc faults from damaged cables and loose connectionsWider device, often combined with an RCBO; see AFDDs explained

More on breaker letters in Type B, C and D breakers, and on RCD types in RCD types explained.

Board layouts: split-load or all RCBO?

  • Old boards with no RCD: common before the 2000s. Not automatically unsafe, but they lack the additional protection modern rules require.
  • Split-load: a single RCD protects some circuits and the rest have none. Common in the 2000s.
  • Dual RCD: circuits split between two RCDs. One earth fault trips the RCD and takes every circuit on that side off, so a fault on a freezer circuit could also turn off the lights on that side.
  • All RCBO: every circuit has its own RCBO. A fault only trips the circuit that has it, which makes fault finding easy and avoids unwanted tripping from the leakage of many circuits adding up. It costs more, but it's the best arrangement for most homes. See why does my RCD keep tripping?

What BS 7671 requires

A non-combustible enclosure

Regulation 421.1.201 requires consumer units and similar switchgear assemblies in domestic premises to have their enclosure made of non-combustible material, or be enclosed in a cabinet of non-combustible material. In practice this means a metal consumer unit. The rule came in with Amendment 3 to the 17th Edition, in force from January 2016, after fires starting in plastic consumer units. Existing plastic units aren't automatically unsafe, but new ones in homes must meet it.

RCD protection

30 mA RCD protection is required, broadly, for:

  • socket-outlets rated up to 32 A (Regulation 411.3.3);
  • mobile equipment rated up to 32 A used outdoors;
  • AC final circuits supplying luminaires in domestic premises (411.3.4);
  • cables concealed in walls or partitions at a depth of less than 50 mm, or in metal-framed partitions, unless protected in other ways (522.6.202 and 522.6.203).

Put together, almost every circuit in a new home installation ends up RCD-protected. Type AC RCDs may only be used to serve fixed equipment known to have no DC component in its fault currents; Type A is the usual minimum now.

The labels you should see

  • A circuit chart saying what each way supplies.
  • An RCD test notice asking you to test RCDs every six months by pressing the T button. (The 18th Edition, BS 7671:2018, changed this from quarterly.) If pressing T doesn't trip it, call an electrician.
  • A periodic inspection notice giving the recommended date of the next inspection.
  • Where relevant, warnings about dual supplies (such as solar PV or a battery) and non-standard colours from older wiring.

Replacing a consumer unit

In England, replacing a consumer unit is notifiable under Part P: it must be done by an electrician registered with a competent person scheme, or notified to building control. See Part P notifiable work. Before the swap, the electrician should test the existing circuits, because a new RCD-protected board will expose insulation faults that an old fuse board tolerated, and some may need repair before the new board will stay on.

Good reasons to replace a board include: no RCD protection, damage or signs of overheating, rewirable fuses with no spare capacity, or an additional circuit, such as an EV charger or heat pump, that needs a way and protection the old board can't provide.

Buying guide: Tightening terminals to the maker's figure? Our VDE torque screwdriver buying guide compares four.
Intermediate and advanced

Going deeper

Rated short-circuit capacity

Domestic consumer units to BS EN 61439-3 are commonly assessed with a conditional short-circuit current rating of 16 kA when supplied through a distributor's BS 88-3 cut-out fuse of up to 100 A. That's why a 6 kA-rated MCB can be fitted in a domestic board where the prospective fault current is well above 6 kA: the combination of the board, the devices and the upstream fuse has been tested. That assessment depends on the maker's devices, which is one reason mixing brands inside a board isn't acceptable unless the board maker approves it.

Discrimination between devices

A fault should trip only the device nearest to it. Between an MCB and an upstream RCD, discrimination for earth faults is poor, because an RCD responds to residual current regardless of which circuit it's on. Time-delayed (Type S) RCDs as main switches, with 30 mA RCBOs downstream, give discrimination on TT installations where a 100 mA or 300 mA S-type upfront is needed for fault protection.

Heat and the busbar

The consumer unit's rated current and the rated diversity factor (given by the maker) limit how much total load the board should carry continuously. A modern home with an EV charger, a heat pump, an induction hob and an electric shower can approach the limits of a 100 A supply. A demand assessment, and possibly a load management device for the charger, is part of designing additions.

Plastic units in existing installations

Regulation 421.1.201 applies to new work. On a condition report, a plastic consumer unit in a home isn't, on its own, potentially dangerous. Inspectors code what they find, such as signs of overheating or a unit not installed to its maker's instructions.