When a fault happens, the protective device nearest to it should operate, and the devices further back should stay closed. Then a fault on one circuit only takes out that circuit, not the whole board or the whole building. BS 7671 calls this selectivity. Older books, and many electricians, call it discrimination; it's the same thing.
Total and partial selectivity
- Total selectivity: the downstream device clears every overcurrent up to the highest fault current possible at that point, without the upstream device operating.
- Partial selectivity: the devices are selective only up to a certain current, the "selectivity limit". Above it, both may operate.
Partial selectivity is common and often acceptable. What matters is whether the limit is above the fault current that can really flow at the downstream device.
Time-current curves
Every fuse and breaker has a curve showing how long it takes to operate at each current. Plot the downstream device's curve and the upstream device's curve on the same graph. If the downstream curve is entirely to the left of, and below, the upstream curve, with a gap between them, the pair is selective over that range.
Curves only show the time to operate under steady conditions. For high fault currents, where devices operate in less than 0.1 s, the curves aren't enough, and selectivity is checked using the energy each device lets through (I²t) or the manufacturer's tested selectivity tables.
Fuses: the 1.6:1 rule
BS 88 gG fuse links are designed so that a fuse is selective with another of at least 1.6 times its rating, when both are the same type: a 100 A fuse discriminates with a 63 A fuse below it, and a 160 A fuse with a 100 A one. Manufacturers' data confirms the figures for their own fuses. This is a big reason fuses are still used for distribution: selectivity between them is easy to achieve and predictable.
MCBs in series
An MCB has two trip mechanisms. A thermal element handles overloads slowly. A magnetic element trips almost instantly once the current passes a multiple of its rating: 3 to 5 times for Type B, 5 to 10 for Type C and 10 to 20 for Type D. See MCB types explained.
That magnetic trip is the problem. Put a 63 A Type B upstream of a 32 A Type B, and a fault current above 189 to 315 A (the 63 A breaker's magnetic range) can trip both instantly. Short circuits on a domestic final circuit often exceed that. So MCB-to-MCB selectivity is usually only partial, and the limit is often no higher than the upstream breaker's magnetic trip current. Manufacturers publish selectivity tables for their own combinations, which are the only reliable source; some upstream devices are specially designed to be selective.
In a house
A domestic consumer unit's main switch is usually an isolator, not a breaker, so it doesn't affect selectivity. The service fuse in the cut-out (typically 60, 80 or 100 A) is upstream of every MCB in the house. For overloads it is easily selective with a 32 A MCB. For a short circuit near the consumer unit, the fault current can be high enough to blow it too. The network operator's fuse has to be replaced by them, so this is worth thinking about when you choose an MCB's breaking capacity and where the cut-out fuse is rated low.
RCDs in series
An RCD trips on earth leakage, not overcurrent, so it needs its own selectivity. BS 7671 Regulation 536.4.1.4 says that where RCDs are in series and selectivity is needed, the upstream one must be a time-delayed type, such as an S type, and its rated residual operating current must be at least three times that of the downstream one.
So a 30 mA RCD needs at least a 100 mA S type upstream. Two ordinary 30 mA RCDs in series are not selective: an earth fault on one circuit can trip either, or both. This is common on TT systems, where a time-delayed 100 mA RCD at the origin protects the tails and board, and 30 mA RCDs or RCBOs protect the circuits. An S type can't be used to provide the 30 mA additional protection itself.
Why it matters
- Safety. Losing all the lighting, fire alarm supply or medical equipment because of a fault on one socket circuit is a hazard, not just a nuisance. BS 7671 Section 536 covers selectivity, which a designer provides where safety or the use of the installation needs it.
- Fault finding. When only the faulty circuit trips, the fault is easy to find. See why an RCD keeps tripping.
- Design. In commercial and industrial installations, a selectivity study using the manufacturer's data is part of the design. In a house, RCBOs on every circuit are the simplest way to stop one fault taking out several circuits.
Going deeper
Energy (I²t) selectivity
For faults that clear in less than 0.01 s, what matters is energy, not time. A downstream fuse is selective with an upstream fuse if its total operating I²t (pre-arcing plus arcing) is less than the upstream fuse's pre-arcing I²t at that current: the small fuse has finished clearing the fault before the big one has started to melt. Fuse datasheets give both values. The 1.6:1 rule for gG fuses comes from the standard ranges of these values.
Current-limiting devices
Fuses and current-limiting MCBs operate before the fault current reaches its first peak, so they let through much less energy than the prospective fault would. That's why a fuse upstream of an MCB can be selective to a higher current than two MCBs: the MCB limits the current so the fuse never sees enough energy to melt. Again, only the manufacturer's tested tables tell you the real limit.
Back-up protection
The opposite of selectivity is back-up protection (sometimes called cascading): the upstream device is deliberately allowed to help the downstream one break a fault current bigger than the downstream device's breaking capacity. BS 7671 Regulation 434.5.1 allows a device with a lower breaking capacity where an upstream device with enough breaking capacity is coordinated with it, and the manufacturer's data shows the combination works. You trade away selectivity at high fault currents.
Zone selective interlocking
In large installations, air circuit breakers can talk to each other. The breaker nearest the fault sends a restraint signal upstream, so the upstream breaker holds off for its set delay; if no restraint arrives, the fault is in its own zone and it trips instantly. This gets selectivity without long delays everywhere.
Sources
The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.
- BS 7671:2018+A4:2026 Section 536: coordination and selectivity of protective devices (IET, paid standard)
- IET: RCDs, everything an electrician should know (selectivity between RCDs)
- Rexel fuse catalogue: BS 88 fuse link discrimination (1.6:1 ratio)