Three-phase power explained: 400 V, 230 V, balance and the neutral

New to this? Read from the top. Already know the basics? Jump to Going deeper for intermediate and advanced detail.

Three sine waves 120 degrees apart: L1 brown, L2 black, L3 grey. Each line is 230 V to neutral, and 400 V between any two lines, because 230 times the square root of 3 is about 400
Beginner

Most UK homes have a single-phase supply: one line and a neutral at 230 V. Businesses, farms, flats blocks and the street itself use three-phase, and more homes are asking for it for fast EV charging and big heat pumps. This guide explains how three-phase works and the numbers you need.

Three waves, 120° apart

A three-phase supply has three lines, called L1, L2 and L3, and usually a neutral. Each line carries a 230 V, 50 Hz sine wave, just like a single-phase supply, but each wave peaks a third of a cycle (120°) after the one before.

L1 brownL2 blackL3 grey one cycle = 20 ms at 50 Hz; each phase is 120° (6.7 ms) behind the one before
Three phases, each 230 V to neutral, a third of a cycle apart.

In BS 7671 colours, L1 is brown, L2 black and L3 grey, with a blue neutral and a green and yellow protective conductor.

Why 400 V and 230 V

Between any line and neutral you measure the phase voltage, 230 V. Between two lines you measure the line voltage. Because the two waves are 120° apart, they never cancel and never simply add: the difference between them is √3 times the phase voltage.

Vline = √3 × Vphase = 1.732 × 230 ≈ 400 V

(The exact figure is 398.4 V; it's always called 400 V.) The UK declared voltage is 230 V between line and neutral, and the Electricity Safety, Quality and Continuity Regulations allow it to vary from 10% above to 6% below, so you can measure anywhere from about 216 V to 253 V on a healthy supply, and from about 376 V to 440 V between lines.

400 V between phases. Where two phases are in the same enclosure, room or socket set, someone touching both gets 400 V, not 230 V. Keep different phases apart where possible, label equipment where 400 V is present, and treat every conductor as live until proven dead with an approved voltage indicator.

Power and current

For a balanced three-phase load, such as a three-phase motor or heater:

P = √3 × Vline × I × power factor

A 10 kW balanced heater (power factor 1) on 400 V draws 10,000 ÷ (1.732 × 400) = 14.4 A in each line. The same 10 kW on a single 230 V phase would draw 43.5 A. Spreading the load over three lines is why three-phase can deliver much more power through cables of the same size.

The same sum works per phase: each line supplies a third of the power at 230 V. That's where EV charger ratings come from: a 32 A single-phase charger gives 230 × 32 = 7,360 W (sold as 7.4 kW), and a 32 A three-phase charger gives 3 × 230 × 32 = 22,080 W (sold as 22 kW).

The AC power calculator does these sums for single and three-phase loads.

Balance and the neutral

When the three phases carry equal currents, the neutral currents cancel and the neutral carries almost nothing. When they don't, the neutral carries the difference. Because the currents are 120° apart, the sum isn't simple arithmetic:

Neutral current for resistive loads (power factor 1)
L1L2L3Neutral
20 A20 A20 A0 A
20 A10 A10 A10 A
20 A15 A0 A18.0 A
30 A0 A0 A30 A

So with three-phase, the neutral normally carries no more than the most heavily loaded line, which is why it can be the same size. The exception is equipment such as LED drivers, computers and chargers, which draw distorted currents. Their third harmonics don't cancel; they add in the neutral, which can then carry more than any line. Designers allow for that in buildings full of electronic loads.

That's also why you share single-phase circuits out across the phases when you design a three-phase board: balanced phases mean less neutral current, less voltage drop and a smaller supply.

A lost neutral is dangerous

If the supply neutral breaks on a three-phase system, single-phase loads on different phases end up in series across 400 V. The lightly loaded phase can rise towards 400 V while the heavily loaded one falls, which can destroy equipment and cause fires. Signs include lights getting very bright or dim as other loads switch on. Treat it as an emergency: in Great Britain, call the network operator on 105.

Phase rotation

The order in which the phases peak (L1, L2, L3) is the phase rotation or phase sequence. It decides which way a three-phase motor turns: swap any two lines and the motor runs backwards, which can wreck a pump or make a machine dangerous. Check rotation with a phase rotation tester before connecting motors, after any work on the supply, and when a generator is connected.

Star and delta

A three-phase load or winding can be connected two ways. In star (wye), each element sits between a line and a common star point, which can be connected to neutral, so each sees 230 V. In delta, each element sits between two lines and sees 400 V, and there is no neutral. The local distribution transformer has a delta primary and a star secondary, and its star point is the neutral and earth reference for your supply.

Three-phase at home

A home can have a three-phase supply if the network operator can provide one; it may need a new cable from the street, which can be expensive. It's worth it for a 22 kW EV charger, a large heat pump, or a big solar and battery system that is over the single-phase export limits. A three-phase supply also needs a three-phase consumer unit or distribution board, and the single-phase circuits shared across the phases. Many people find a 7.4 kW single-phase charger is plenty for overnight charging.

Intermediate and advanced

Going deeper

Where √3 comes from

Write the phase voltages as phasors of length V at 0°, −120° and +120°. The line voltage L1 to L2 is the difference V∠0° − V∠−120°. Its length is 2V sin 60° = √3 V. The same geometry gives the line current in a delta load: √3 times the current in each delta element.

Neutral current in general

For three line currents I1, I2, I3 in phase with their voltages, the neutral current is |I1 + a I2 + a² I3|, where a = 1∠−120°. For two loaded phases this reduces to √(I1² + I2² − I1I2). With reactive loads, include each current's angle too.

Third harmonics

The third harmonic of each phase current is 3 × 120° = 360° shifted from the next, so all three are in step and add in the neutral. With heavily non-linear single-phase loads, the neutral current can approach 1.7 times the line current. BS 7671 requires the neutral to be sized for it where the harmonic content is high, and Appendix 4 gives reduction factors for four-core and five-core cables carrying harmonic currents.

Fault levels

A three-phase symmetrical fault usually gives the highest prospective fault current. As a rule of thumb, the three-phase value is about twice the line to neutral value measured with a loop tester, where the neutral and line impedances are similar. Use the higher figure when checking breaking capacity.