Three kinds of power
- Real power, P, in watts or kW, is what actually does work or makes heat.
- Apparent power, S, in volt-amps or kVA, is simply volts × amps. Cables, fuses and transformers have to carry this.
- Reactive power, Q, in var or kvar, flows back and forth into the magnetic fields of motors and transformers without doing work.
They form a right-angled triangle: S² = P² + Q². The power factor is P / S, which for a sine wave equals cos φ, where φ is the angle between voltage and current.
The formulas
- Single-phase:
S = V × IandP = V × I × PF. - Balanced three-phase:
S = √3 × VL × ILandP = √3 × VL × IL × PF, where VL is the line-to-line voltage (400 V in the UK) and IL the current in each line. - Current from power:
I = Pout / (η × √3 × VL × PF)for three-phase, without the √3 for single-phase, where η is the efficiency.
Worked example. A 7.5 kW three-phase motor on 400 V with a power factor of 0.85 and 90 % efficiency draws 7,500 ÷ (0.9 × 1.732 × 400 × 0.85) = 14.2 A per line.
Things to know
- For a real motor, use the full-load current on its nameplate when you size cables and protection. Power factor and efficiency both fall at light load, and starting current can be several times the running current.
- Loads with switch-mode power supplies, such as LED drivers and computers, draw distorted current. Their power factor includes the effect of harmonics, not just the phase angle, so cos φ alone doesn't describe them.
- This calculator assumes a balanced three-phase load. An unbalanced load needs each phase worked out separately.