Every electrical installation needs a path for fault current to get back to the source, so a fault blows a fuse or trips a breaker quickly. How that path is made is the earthing system. In the UK you'll meet three: TN-S, TN-C-S and TT. Knowing which one you're working on changes how you test, which values you expect, and what extra protection you need.
What the letters mean
The names come from IEC 60364, the international standard that BS 7671 is based on.
- First letter, the supply: T (from terra) means the supply is connected directly to earth, usually at the transformer's star point. I means it's isolated from earth, or earthed through a high impedance.
- Second letter, the installation: T means the installation's exposed metalwork is connected to its own earth electrode. N means it's connected back to the supply's earthed point through the supply cable.
- Any letters after that: S means the neutral and protective conductors are separate. C means they're combined in one conductor, the PEN.
The three you'll meet
| System | How the earth gets back | How to spot it | Typical maximum Ze |
|---|---|---|---|
| TN-S | A separate protective conductor all the way back, usually the lead sheath or armour of the supply cable. | Earth clamp on the supply cable sheath, or a separate earth terminal on the cut-out. Common in older properties with underground supplies. | 0.8 Ω |
| TN-C-S (PME) | The supply uses a combined neutral and earth (PEN). The earth terminal is connected to the neutral at the cut-out. | A label reading "Safety electrical connection, do not remove" and the earth terminal bonded to the neutral of the cut-out. The most common system in the UK today. | 0.35 Ω |
| TT | Through the ground: the installation has its own earth electrode, and current returns via the soil to the supply's earth. | An earth rod, usually near the meter position, and no earth terminal from the supplier. Common with overhead supplies in rural areas. | 21 Ω for the supply side only; the electrode is usually much higher |
The Ze figures are the maxima distribution network operators typically quote for design. The actual value must be measured, and it's often much lower. IT systems, where the supply isn't earthed, are rare in the UK outside specialist places such as some hospital operating theatres.
Why TT installations rely on RCDs
On a TT system the earth fault loop includes the soil, so the loop impedance is often tens or hundreds of ohms. A 32 A circuit-breaker needs well under 2 Ω to trip instantly, so it can't provide fault protection on its own. An RCD does the job instead, and BS 7671 Regulation 411.5.3 requires RA × IΔn ≤ 50 V. Use the RCD test calculator to check an electrode against it.
Why PME needs extra care
On a TN-C-S supply the same conductor carries neutral current and earth. If that PEN conductor breaks somewhere in the street, the earthed metalwork in every house beyond the break can rise towards line voltage, and current from neighbouring properties can flow through the main bonding conductors. That's why BS 7671 has extra rules for PME:
- Bigger main bonding conductors. They're sized from the supply neutral using Table 54.8: 10 mm² copper for a neutral up to 35 mm², 16 mm² up to 50 mm², 25 mm² up to 95 mm², 35 mm² up to 150 mm² and 50 mm² above that.
- Some places can't use a PME earth. For example, BS 7671 Section 708 doesn't allow it for the socket outlets on caravan park pitches. Section 722 restricts it for electric vehicle charge points: you need one of the protective measures it lists, such as a separate earth electrode or a device that disconnects on a broken PEN.
- Check the distribution network operator's own conditions before exporting a PME earth to an outbuilding, a farm or anywhere with lots of exposed metal in contact with the ground.
Earthing and bonding conductor sizes
For a typical home with 25 mm² meter tails:
- The main earthing conductor is usually 16 mm² copper (BS 7671 Table 54.7: 16 mm² for line conductors over 16 mm² and up to 35 mm²). The supplier may ask for more, and on TT, the size of a buried earthing conductor also depends on whether it's protected against corrosion and damage.
- Main protective bonding to the incoming gas and water pipes is 10 mm² copper. On TN-S and TT, the rule (Regulation 544.1.1) is at least half the earthing conductor size, at least 6 mm², and no more than 25 mm² for copper. On PME it's Table 54.8, as above.
Things to know
- Never disconnect the main earthing conductor or main bonding with the installation energised. On PME it can carry current.
- Record the earthing system and measured Ze on every certificate and report.
- Ze is measured with the main earthing conductor disconnected from the main earthing terminal and the installation safely isolated, so the parallel paths through the bonding don't affect the reading. Reconnect it straight away.
- Always check against the current edition of BS 7671 and the supplier's requirements.
For the values to compare against when testing, see the BS 7671 test values cheat sheet. To check a loop impedance, use the max Zs calculator.
Sources
The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.
- BS 7671 Chapter 54: earthing arrangements and protective conductors, Tables 54.7 and 54.8, Regulation 544.1.1 (IET, paid standard)
- BS 7671 Regulation 411.5.3 and Table 41.5 (RA × IΔn ≤ 50 V; IET, paid standard)
- BS 7671 Sections 708 (caravan parks) and 722 (electric vehicle charging) (IET, paid standard)
- Eland Cables: earth bonding cable size (PME bonding sizes)
- IET On-Site Guide, Appendix B Table B6: maximum measured earth fault loop impedance at ambient temperature (paid)