RCD types explained: AC, A, F and B, and which one you need

Four RCDs labelled AC, A, F and B, each detecting more kinds of residual current: AC only, then pulsating DC, then mixed frequencies, then smooth DC
Beginner

A residual current device (RCD) compares the current going out on the line conductor with the current coming back on the neutral. If some is leaking away, for example through a person to earth, it trips. A 30 mA RCD trips well before most people would suffer a fatal shock.

The trouble is that modern electronics don't always leak plain AC. Power supplies, inverters and motor drives can leak DC or high-frequency current, and a basic RCD may not see it, or may be "blinded" by DC so it fails to trip on a normal AC fault too. That's what the RCD types are about.

The four types

TypeDetectsTypical uses
ACSinusoidal AC residual current only.Simple resistive, capacitive or inductive loads with no electronics, such as a basic immersion heater.
AAs AC, plus pulsating DC, including with up to 6 mA of smooth DC.General domestic circuits: LED drivers, induction hobs, most appliances with switch-mode power supplies.
FAs A, plus composite residual currents from single-phase frequency-controlled loads, and up to 10 mA of smooth DC.Washing machines, dishwashers, heat pumps and other single-phase appliances with variable-speed motors.
BAs F, plus smooth DC and sinusoidal AC up to 1 kHz.Three-phase drives, solar PV inverters without isolation, some EV chargers, UPS systems.

Each type does everything the one above it does, so a type B can always replace a type A. The type is marked on the device with a small symbol: a sine wave for AC, a sine wave plus a pulsed half-wave for A, and so on.

Type AC is now restricted

BS 7671 Regulation 531.3.3 was tightened by Amendment 2 in 2022. Type AC RCDs can now only be used where the load is known not to produce DC components. In practice type A is the normal minimum for new domestic work, and many consumer units now come with type A as standard.

Electric vehicle chargers

A car charger can produce a DC fault current that would blind a type A RCD. BS 7671 Section 722 requires each charging point to be protected by a type B RCD, or by a type A RCD together with a device that detects 6 mA of smooth DC (an RDC-DD, often built into the charger). Check what the charger's manufacturer has built in before choosing the RCD upstream.

Other markings you'll see

  • S type: time-delayed, used upstream of other RCDs so they don't both trip. It must trip between 130 ms and 500 ms at IΔn.
  • RCCB: an RCD on its own, with no overcurrent protection (BS EN 61008).
  • RCBO: an RCD and circuit-breaker in one, so one fault only takes out one circuit (BS EN 61009).
  • IΔn: the rated residual current. 30 mA is used for additional protection of people; 100 mA and 300 mA for fire protection and selectivity.

To check an RCD's test results, use the RCD test calculator. For a full list of test limits, see the BS 7671 test values cheat sheet.

Sources

The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.