Home / Learn / Electrical installations

Why does my RCD keep tripping? A step-by-step guide

A consumer unit with its RCD tripped, and the three steps to find the cause: switch all breakers off and reset the RCD, switch breakers on one at a time, then unplug appliances and add them back one by one
Beginner

An RCD (residual current device) compares the current going out on the line conductor with the current coming back on the neutral. If more than a small amount is missing, it's leaking to earth somewhere, possibly through a person, so the RCD switches off. A 30 mA RCD must trip within 300 ms when 30 mA leaks, and it's allowed to trip at anything from half its rating (15 mA) upwards.

So an RCD that trips is usually doing its job. The trick is finding what's leaking.

Never bypass or hold in an RCD. It's there to stop you being electrocuted. If it won't stay on with everything unplugged, or you see scorching, smell burning or hear crackling, leave it off and call an electrician.

Step 1: notice when it trips

The pattern is the best clue you have.

When it tripsLikely causes
When you switch a particular appliance onA fault in that appliance, often a heating element (kettle, washing machine, dishwasher, oven, immersion heater)
When it rains, or on damp morningsWater in an outdoor socket, outside light, garden cable or junction box
At night, apparently at randomThings that switch themselves on: immersion heater on a timer, fridge or freezer defrost heater, central heating pump, outside lights on a sensor
Straight away, with everything unpluggedA fault in the fixed wiring, such as a nail through a cable, a damaged cable or water in a fitting
When any big load starts, even on a different circuitA neutral-to-earth fault (see below)
During thunderstormsA surge from nearby lightning. If it resets straight away and doesn't trip again, there may be nothing wrong

Step 2: find the circuit

  1. Switch off all the circuit-breakers (MCBs) under the RCD that has tripped.
  2. Reset the RCD. If it won't reset with all its breakers off, the fault is in the RCD itself or the wiring between it and the breakers. Stop and call an electrician.
  3. Switch the breakers back on one at a time. When the RCD trips, the last breaker you switched on is the circuit with the problem. Leave that one off and turn the rest back on.

If your consumer unit has RCBOs (a combined RCD and breaker for each circuit) instead, only the faulty circuit's RCBO trips, which saves this step.

Step 3: find the appliance

  1. On the faulty circuit, unplug everything, including things hidden behind units and in the garage.
  2. Switch the circuit back on. If it stays on, plug things back in one at a time, waiting a minute or so and switching each one on, until it trips.
  3. If it trips with nothing plugged in, the fault is in the fixed wiring or something hard-wired, like an extractor fan, cooker, shower or outside light. That's a job for an electrician.

Kettles, washing machines and dishwashers are the most common culprits, because their heating elements break down and leak to earth with age. A faulty appliance should be repaired by someone competent or replaced, not used.

Faults that fool the simple method

Neutral-to-earth faults

If a neutral conductor touches earth somewhere after the RCD, part of the returning current flows back through the earth instead of the neutral. The RCD sees that as leakage, but only when current is flowing in that neutral. So the RCD trips when a big load starts, and the load might be on a different circuit to the fault. Unplugging appliances won't find it. An electrician finds it with an insulation resistance test between neutral and earth on each circuit.

Built-up leakage

Computers, TVs, chargers, LED drivers and other electronics leak a small current to earth through their filters. It's harmless, but it adds up. Lots of equipment on one RCD can leave it close to tripping, so a small extra leak tips it over. BS 7671 says the normal leakage on an RCD-protected part of an installation should stay below 30% of the RCD's rating, which is 9 mA for a 30 mA RCD. Spreading circuits across more RCDs, or fitting RCBOs, solves it.

Inverter drives (variable speed drives)

A variable speed drive, also called an inverter drive or VSD, controls a motor's speed by switching its output on and off very fast. That switching drives high-frequency current through the stray capacitance of the motor cable and the motor to earth. The drive's EMC (radio interference) filter has capacitors from the supply lines to earth, which send most of that current back inside the drive, but they also leak current to earth at 50 Hz. Control Techniques puts a typical drive's leakage at a few to tens of milliamps, and more with a long motor cable. That's enough to trip a 30 mA RCD, or to use up most of the 9 mA leakage allowance described above.

SupplyRCD DriveEMC filter motor cableMotor filter capacitors:50 Hz leakage stray capacitance:high frequency earth: the RCD sees all of this as leakage
A drive leaks to earth in two ways. Both add up at the RCD.

The risk can also go the other way. A drive, especially a three-phase one, can produce a smooth DC fault current. The IET warns that DC can saturate the core of a Type AC or Type A RCD, so the RCD won't trip at all, which can be as dangerous as having no RCD. So the fix for a tripping drive is never "fit something less sensitive and hope". This is a job for an electrician, working from the drive's installation manual:

  • Use the RCD type the drive maker states. Under BS EN 62477-1, the drive maker should say which RCD types are compatible. If you can't get that information, the IET advises a Type B RCD. Some Type B devices are also built to be less sensitive to high-frequency leakage. Control Techniques calls these "super-immune".
  • Give the drive its own RCD or RCBO, so its leakage doesn't add to other equipment's.
  • Keep the motor cable as short as practical. Leakage rises with cable length, and the IET notes it also varies with motor speed.
  • Change the filter only as the manual allows. Some drives let you disconnect the internal filter capacitors, or offer a low-leakage filter for short motor cables. That can affect radio interference, so follow the maker's limits.
  • Check why the RCD is there. If it's providing 30 mA additional protection that BS 7671 requires, it has to stay. If it's only there for fault protection, for example on a TT system, the designer may be able to use a less sensitive device. Control Techniques notes that a 1 A RCD is often enough for a permanently wired drive in a dry location.

Borrowed neutrals

If a circuit's neutral is connected to a different circuit's neutral (common with two-way lighting between floors), current goes out through one RCD and comes back through another, and both see an imbalance. Best Practice Guide 4 codes a borrowed neutral as C2, potentially dangerous.

A worn-out RCD

Occasionally the RCD itself is faulty and trips below 15 mA. An electrician can test its trip current and time with an RCD tester. Press the test button on each RCD every six months, as the notice at the consumer unit says (BS 7671 Regulation 514.12.2), or as often as the manufacturer recommends; it proves the mechanism still works.

What an electrician will do

  • Measure the insulation resistance of the circuit, usually at 500 V DC, between line and earth and between neutral and earth, to find wiring faults and neutral-earth faults. Values below 1 MΩ need investigating; a healthy circuit is usually hundreds of megohms.
  • Measure the leakage with a sensitive clamp meter around the line and neutral together.
  • Check the RCD's trip time and trip current.
  • Check the RCD type suits the loads. A Type AC RCD isn't right for loads like heat pumps, EV chargers or some washing machines with DC components; Type A is the usual minimum now.

Sources

The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.