Fault finding simulator
About this simulatorAbout this simulator
A live house with a hidden fault. Find it with a voltage indicator, multimeter, insulation tester, loop tester and clamp meter, fix it safely and prove it works. Every reading is calculated from the real circuit.
How it works
Each job is a call-out to the same house: a TN-C-S (PME) supply, a dual-RCD consumer unit and five circuits (a ring final, an outside socket radial through a garage junction box, an immersion heater, and two loop-in lighting circuits with two-way switching on the stairs). One fault is hidden in it (on some level 5 call-outs, two). Pick a job from one of the five levels; each level unlocks when you have a star on half the jobs in the one before.
- Look and operate. Switch breakers, RCDs and the main switch, flick light switches, plug and unplug appliances (or move them to another socket), press the RCD test button, and take the top off an appliance's plug to check its fuse. Take the consumer unit cover off (and, with the main switch locked off and the board proved dead, lift the main earthing conductor off the MET for a Ze test), and open sockets, roses, switches and junction boxes to get at the terminals.
- Test. Pick a tool, pick up a lead from its socket and put it on a terminal (or drag it there). Empty socket outlets take a plug-in test adaptor. The clamp meter fits round the meter tails, the main earthing conductor and each circuit's conductors inside the consumer unit.
- Diagnose, fix, check. When you know what it is, tap Diagnose, then the faulty part, and name the fault. From level 4 on (the call-outs too), a diagnosis only counts once you have evidence on that circuit or part: a reading that's clearly wrong without needing to know what a healthy house reads (compare sockets, before/after, OL where there should be continuity, volts where there should be none…), or you've safely opened the part and can see the fault. Until then every pick gets the same reply, right or wrong. Fix it, put everything back, prove it works, and hand over.
Each job gives up to three stars, and each star needs the one before. The first is for finding and fixing it, checking it and leaving the house safe and working. The second adds no safety strikes or slips. The third adds no hints, no wrong or unproven guesses, and finishing inside the par time. Three safety strikes stop the job.
Safety rules it checks
- Safe isolation before you touch conductors. Switch off and lock off before you open anything. Then, at the point of work, prove the voltage indicator (on the proving unit or a known live supply), test L–N, L–E and N–E (and every other conductor there, including the bare end of any loose or disconnected core: it may be live from somewhere else), then prove the indicator again: on an accessory's own terminals (or a socket's outlet, with the plug-in adaptor) before you repair it, and on the circuit's terminals in the board before you disconnect a conductor there. You don't have to test at the board first. Open an accessory with care: until you have proved it dead there, treat it as live (the wrong breaker locked, a borrowed neutral or a second feed can keep it live). Every circuit you are working on must be locked off and proved dead. Opening an accessory with nothing locked off, or disconnecting a conductor or starting a repair before all of that, is a strike. A multimeter doesn't count: Electrical Safety First Best Practice Guide 2 says prove dead with an approved two-pole voltage indicator (GS38 covers the probes and leads).
- Every circuit in a box, locked off. A box fed by two circuits by design, like the hall 2-gang switch (the hall light and the landing two-way, circuits 4 and 5), opens only with both locked off, and refits under the same rule; prove–test–prove there covers both circuits' terminals. A circuit that is only in a box because of the fault (a borrowed neutral) isn't asked for: proving dead at the point of work is what shows it, and the repair needs it dead too.
- Plug tops come off unplugged. Opening a plug that is still in its socket is a strike, and a plug goes back in only with its top on. Fitting the wrong fuse rating for the appliance is a slip.
- Loop tests are live tests, made the normal way. At a socket face with the plug-in adaptor, or at the board: the loop tester won't test on an open accessory's terminals or a loose core, and on a dead circuit it says "No supply" and doesn't test. On an RCD-protected circuit use the no-trip setting: the 2-wire high-current setting sends its whole test current out on the line and back on the earth, so the RCD trips (a slip).
- The main earthing conductor comes off only with the installation isolated. Lifting it for a Ze test needs the main switch locked off and prove–test–prove inside the board first (otherwise a strike). Switching the main switch on with it still off is a strike, and leaving it off counts against putting everything back.
- Dead tests on dead circuits only. An ohms, continuity or insulation test on a live circuit is a strike. An insulation test with appliances still plugged into the circuit is a slip (GN3: unplug everything first).
- Right socket, right range. A lead in the multimeter's A or mA socket across a voltage is a short circuit inside the meter: the meter's high-breaking-capacity fuse blows (it clears a fault that size in well under a millisecond, before the breaker or RCD can react), and it is a strike.
- Live testing is allowed with the cover off or an accessory open, because fault finding needs it (Electricity at Work Regulations, regulation 14). Refitting a faceplate needs the circuit isolated again. Switching a breaker back on onto the same short circuit before you have changed anything is a slip.
How accurate is it?
The whole house is one AC circuit, solved by nodal analysis (with complex numbers, like a circuit simulator) every time anything changes, including the instrument you are holding. Nothing is scripted: trips, bangs and readings all come out of the solution.
- Cables use copper resistance at 20 °C from the On-Site Guide: 7.41 mΩ/m for 2.5 mm², 12.1 for 1.5 mm² and 18.1 for 1.0 mm², so 2.5/1.5 twin and earth is 19.51 mΩ/m for R1 + R2. Zs comes out as Ze plus R1 + R2 plus the few milliohms of the tails, switches and breaker.
- The supply's own impedance is 0.20–0.32 Ω, so Ze measured at the origin (with the tails and the main earthing conductor) reads 0.18–0.35 Ω, and the open-circuit supply is 237–244 V, different every job. Lamps are filament lamps: their cold resistance (what an ohmmeter sees) is about a thirteenth of their hot resistance.
- RCDs (and RCBOs) trip somewhere between 60 % and 85 % of 30 mA, inside the BS EN 61008-1 / 61009-1 windows (they must not trip at 50 % or below, and must trip by 100 %). B-type MCBs trip magnetically at 3.6–4.6 times their rating. On overload they heat up and cool down like a real bimetal: no trip at 1.13 times their rating, a few minutes at 1.45 times, about half a minute at 2.55 times (BS EN 60898-1).
- Appliances with mains filters leak a little current to earth through their Y capacitors, and hot heating elements leak through their warm insulation. Each filter is drawn from the real mix: most have a Y capacitor from line and from neutral to earth, some have one on the line side only, and a few have an X capacitor across L–N with one Y capacitor. A fridge has 2.2–4.7 nF (about 0.16–0.34 mA at 230 V), a washing machine 6.8–15 nF and a home office of several items 10–22 nF in all. The leakage job (4.2) is an inspection find, not a trip: a home office of 3.5–5 mA, an inverter fridge freezer and washing machine, a pond pump and the immersion heater add up to about 9.2–9.6 mA standing on RCD 1 (about 10 mA with everything heating), every item inside its own limit and nothing faulty. That is over the 30 % of the RCD's rating (9 mA) that Regulation 531.3.2 allows in normal service, but nowhere near the 18 mA where a 30 mA RCD can start to trip, so nothing ever trips. Fitting RCBOs puts each circuit's leakage on its own 30 mA device (the ring is then under 9 mA). Every appliance stays inside its own product limit when hot (BS EN 60335-1 clause 13.2): 0.75 mA for a portable Class I appliance such as the kettle or pond pump, 3.5 mA for a stationary motor-driven one such as the washing machine or fridge, and 0.75 mA per kW for a fixed heater such as the immersion (measured at 1.06 times rated voltage). IT equipment is allowed up to 3.5 mA per item. The leakage is measured the IEC 60990 way. The RCD sees capacitive and resistive leakage together (they add at right angles). An insulation tester doesn't see the capacitive part, because it tests with DC, and you test elements cold. The clamp meter is an earth-leakage clamp: put it round line and neutral together and it shows what leaks away.
- Plug fuses are BS 1362 cartridges in a BS 1363 plug: 3 A (red) for appliances up to about 700 W such as a TV or lamp, 13 A (brown) from 700 W to 3 kW, or what the maker specifies (Electrical Safety First). A good fuse reads 25.8–47.9 mΩ (3 A) or 3.2–5.9 mΩ (13 A) cold (Multicomp Pro datasheet), so near nought on the low-ohms range; a blown one reads open circuit. They blow on a time–current curve taken from the Electrical Safety First earth fault loop table: a 3 A fuse in 0.4 s at about 17 A and 5 s at about 12 A, a 13 A fuse in 0.4 s at about 113 A and 5 s at about 71 A. So a 3 A fuse in a 3 kW kettle (13 A) goes in a couple of seconds. Tested in the plug, an open fuse looks just like an appliance switched off: take it out and test it on its own.
- The insulation tester has a low-ohms continuity range (BS EN 61557-4: 200 mA, 0.01 Ω steps, leads nulled) for ring and cpc continuity; the multimeter's ohms range only reads to 0.1 Ω, like a real 87V.
- The loop tester (BS EN 61557-3) reads the loop impedance of the solved circuit between its two leads, in 0.01 Ω steps up to 20 Ω, with a steady scatter of up to ±0.02 Ω (the same each time you repeat a test). The no-trip Zs setting draws about 15 mA, under half an RCD's 30 mA; the 2-wire setting draws 10–25 A and trips the RCD. It works out the fault current (PEFC on L–E, PSC on L–N) from the voltage it measures before the test (U ÷ Z), as a real tester does, not from 230 V. The most a breaker allows, measured, is in the explanation, never on the tester: 0.8 × U0 × Cmin ÷ Ia (BS 7671 Table 41.3 at 0.4 s, corrected for conductor temperature, as OSG Table B6), with U0 230 V, Cmin 0.95 and Ia 5 × In for a type B: 1.10 Ω for a B32, 1.75 for a B20, 2.19 for a B16 and 5.83 for a B6. A Ze test with the main earthing conductor still on the MET also measures the parallel path through the bonding and the ground, so it can read low; with a bad PEN, Ze reads high, but a high Ze alone only says the problem is on the supply side.
- On a PME supply the main earthing terminal is joined to the supply neutral (PEN). A bad PEN joint in the DNO's cable shows as a big voltage drop at the origin under load, and it lifts every earthed part with it. The water pipe is bonded to the main earthing terminal and also touches the ground (3.5–5.5 Ω here). So with a bad PEN, part of your neutral current comes home through the bonding conductor. On a real street the metal water main also joins the neighbours' earthing, so the bonding often carries a standing current from them as well (here 0.2–1 A, on a real street sometimes several amps). One clamp reading proves nothing. The method is to watch the bonding current rise and fall as your own load goes on and off, and compare that with the change in the neutral tail. In this house a healthy PEN moves it by a few per cent and a bad one by much more; real percentages depend on the street. That is what separates a PEN fault from a loose line connection at the cut-out, which drops the voltage just the same.
- When a socket's earth is lost, its appliances' Y capacitors hold the metal cases at about half mains, or nearer line voltage with a line-side-only filter or a hot element. A stray path to earth pulls it lower, so it can be anywhere from a few tens of volts up to near line. The model puts a person between the case and the sink or radiator (hand to hand, a body resistance of 1–2 kΩ, from IEC 60479-1), or between the case and the floor (that body resistance plus the floor and shoes: 1 kΩ on a wet kitchen floor up to 500 kΩ in dry shoes). The job's write-up gives the current that flows and compares it with the 0.5 mA you can feel (IEC 60479-1). It is far below the 30 mA RCD's trip level, so nothing trips: the tingle is the warning that the earth has gone.
- A TV and a PC have switch-mode power supplies: mains goes through an X capacitor and a bridge rectifier to a big electrolytic capacitor, so there is no DC path between L and N. Across their plug pins an ohmmeter reads very high (OL) even when they're healthy, so a blown plug fuse shows only when you test the fuse out of the plug. A kettle, washing machine heater or pressure washer reads its load.
- Twin and earth has about 75 pF per metre between cores, so a disconnected conductor running beside a live one picks up a "ghost" voltage. A 10 MΩ multimeter shows it; a voltage indicator, which draws a few milliamps, doesn't.
Things it doesn't do: it uses one fixed house, lamps are all filament lamps (LED lamps would read open circuit on a meter), and the appliances are simple resistive loads.