The letter on a miniature circuit-breaker (MCB) or RCBO, like the B in B32, is its type, sometimes called its curve. The number is its rated current, In. The type tells you how much current it takes to trip the breaker instantly.
Two ways a breaker trips
- Thermal (overload) trip. A bimetal strip heats up as current flows. A modest overload takes a long time to trip it, a big one trips it quicker. This protects the cable from overheating.
- Magnetic (instantaneous) trip. A coil pulls the mechanism open almost immediately, in about 10 milliseconds, once the current is high enough. This deals with short circuits and earth faults.
The type only changes the magnetic part. A B32 and a C32 behave the same under a small overload.
The trip ranges
| Type | Trips instantly between | Example: 32 A breaker | Typical uses |
|---|---|---|---|
| B | Over 3 × In, up to 5 × In | 96 A to 160 A | Most domestic circuits: sockets, lighting, cookers, showers |
| C | Over 5 × In, up to 10 × In | 160 A to 320 A | Loads with a high switch-on surge: motors, large banks of LED or fluorescent lighting, small transformers, some commercial kitchens |
| D | Over 10 × In, up to 20 × In | 320 A to 640 A | Very high inrush: welders, X-ray machines, large transformers and motors |
A breaker must not trip instantly at the bottom of its range, and must trip instantly at the top. BS 7671 uses the top of the range, 5, 10 or 20 times In, when it works out maximum earth fault loop impedance, because that's the current that guarantees an instant trip.
The overload part
All three types share the same thermal limits in BS EN 60898-1 (for breakers up to 63 A):
- At 1.13 × In, the breaker must not trip within 1 hour. This is the conventional non-tripping current.
- At 1.45 × In, it must trip within 1 hour. This is the conventional tripping current, I₂, used for cable sizing (BS 7671 requires I₂ ≤ 1.45 × the cable's current-carrying capacity, which a 60898 breaker meets automatically if In isn't more than the cable rating).
- At 2.55 × In, it must trip in more than 1 second and less than 60 seconds (120 seconds for breakers over 32 A).
Why you can't just fit a C to stop nuisance tripping
A Type C needs twice as much fault current as a Type B to trip instantly. So the maximum Zs for a C is half that of a B of the same rating:
| Breaker | 6 A | 10 A | 16 A | 20 A | 32 A | 40 A |
|---|---|---|---|---|---|---|
| Type B | 7.28 | 4.37 | 2.73 | 2.19 | 1.37 | 1.09 |
| Type C | 3.64 | 2.19 | 1.37 | 1.09 | 0.68 | 0.55 |
| Type D | 1.82 | 1.09 | 0.68 | 0.55 | 0.34 | 0.27 |
Swapping a B32 for a C32 on a long ring final with a Zs of 0.9 Ω would leave it unable to disconnect in time on an earth fault, unless an RCD provides the fault protection. Only change the type after checking Zs, and find out why the B was tripping first: a breaker that trips on switch-on may be pointing to a fault.
Breaking capacity
The number in a box on the front, such as 6000, is the rated short-circuit capacity, Icn, in amps: the biggest fault current the breaker can safely interrupt. Domestic breakers are usually 6 kA, and commercial ones often 10 kA. The prospective fault current measured at the board must not be more than this, unless the consumer unit has a higher conditional rating with the supplier's fuse upstream.
RCBOs
An RCBO (residual current breaker with overcurrent protection, BS EN 61009-1) is a circuit-breaker and an RCD in one, so it has two type ratings:
- A curve letter, B, C or D, for the overcurrent part, exactly as above.
- An RCD type, AC, A, F or B, for the earth leakage part, plus its sensitivity, usually 30 mA. See RCD types explained.
So "B32 30 mA Type A" means a 32 A breaker with a Type B curve and a 30 mA Type A RCD. The advantage of one RCBO per circuit is that a fault only switches off its own circuit, not half the house.
Older breakers
Older installations may have breakers to BS 3871 marked Type 1, 2 or 3. These aren't the same as B, C and D and have their own maximum Zs values; the max Zs calculator includes them. Electrical Safety First lists BS 3871 breakers as a "myth": they don't need coding on an EICR just for being old.
Sources
The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.
- BS EN 60898-1: Circuit-breakers for overcurrent protection for household and similar installations (paid)
- BS EN 61009-1: Residual current operated circuit-breakers with integral overcurrent protection (RCBOs) (paid)
- BS 7671:2018+A4:2026 Chapter 41 and Table 41.3: maximum earth fault loop impedance (IET, paid standard)
- IET On-Site Guide, Appendix B Table B6: maximum measured earth fault loop impedance at ambient temperature (paid)
- Electrical Safety First Best Practice Guide 4: Electrical installation condition reporting, classification codes (Issue 7.4, August 2026)