If a line conductor touches earthed metalwork, the fault current flows round a loop: out through the supply transformer and the line conductor, through the fault, back along the circuit protective conductor (cpc) to the main earthing terminal, and back to the transformer through the supplier's earth path. The earth fault loop impedance is the impedance of that whole loop. It sets how big the fault current is, and so whether the circuit-breaker or fuse trips fast enough to prevent a dangerous shock.
Ze and Zs
- Ze is the part of the loop outside the installation: the transformer, the supply cable and the supplier's earth return. It's measured at the origin.
- Zs is the whole loop for a circuit, so it's Ze plus the resistance of the circuit's line conductor (R1) and cpc (R2):
Zs = Ze + (R1 + R2).
Network operators typically quote these maximum Ze values for design: 0.8 Ω for TN-S, 0.35 Ω for TN-C-S (PME, and also PNB, which Amendment 4 recognises), and 21 Ω for the supply side of a TT system. The measured value is often much lower.
How the fault current trips the breaker
The fault current is roughly I = U₀ × Cmin / Zs, where U₀ is 230 V and Cmin, 0.95, allows for the supply voltage being at the low end of its range. A circuit-breaker trips instantly once the current reaches its magnetic trip level, Ia. For a Type B breaker that's 5 times its rating, so a B32 needs 160 A. That gives the maximum Zs in BS 7671 Table 41.3:
Zs(max) = 230 × 0.95 / 160 = 1.37 Ω for a B32
For final circuits up to 63 A with sockets, and up to 32 A for fixed equipment, a TN system must disconnect within 0.4 s, which the instantaneous trip gives.
Why you compare readings with lower values
Table 41.3 values apply when the conductors are at their maximum operating temperature, 70 °C for ordinary PVC cable. You test at room temperature, when copper's resistance is about 17% lower (put the other way, the hot values are about 20% higher). So a reading that just passes cold could fail hot. That's why the IET On-Site Guide gives a table of maximum measured values, at 80% of the Table 41.3 figures. This is often called the 0.8 rule.
| Breaker | 6 A | 10 A | 16 A | 20 A | 32 A | 40 A |
|---|---|---|---|---|---|---|
| Type B | 7.28 | 4.37 | 2.73 | 2.19 | 1.37 | 1.09 |
| Type C | 3.64 | 2.19 | 1.37 | 1.09 | 0.68 | 0.55 |
| Type D | 1.82 | 1.09 | 0.68 | 0.55 | 0.34 | 0.27 |
| Breaker | 6 A | 10 A | 16 A | 20 A | 32 A | 40 A |
|---|---|---|---|---|---|---|
| Type B | 5.83 | 3.50 | 2.19 | 1.75 | 1.10 | 0.88 |
| Type C | 2.92 | 1.75 | 1.10 | 0.88 | 0.55 | 0.44 |
| Type D | 1.46 | 0.88 | 0.55 | 0.44 | 0.28 | – |
For other breaker ratings and 5 s disconnection, use the earth fault loop impedance (max Zs) calculator, or the table on the test values cheat sheet. Both cover circuit-breakers and RCBOs only. For fuses (BS 88, BS 3036 or BS 1362), use BS 7671 Tables 41.2 and 41.4 or the fuse tables in your On-Site Guide.
Measuring Ze
- Safely isolate the installation at the main switch.
- Disconnect the main earthing conductor from the main earthing terminal, so parallel paths through the bonding to gas and water pipes don't lower the reading. Never do this with the installation energised.
- Test between the line conductor on the supply side of the main switch and the main earthing conductor you disconnected, using a loop tester on its two-lead high-current setting.
- Reconnect the main earthing conductor straight away and check it's tight.
The supply side of the main switch stays live throughout, so this is a job for a competent person using test leads to GS38.
Record the value on the certificate and check it against the earthing system you've identified. A TN-C-S reading of several ohms, or a TN-S reading that looks like a TT, needs investigating with the network operator.
Measuring Zs
- Test at the furthest point of each circuit, between line and the cpc, with the circuit live. On a socket you can use a plug-in lead.
- On RCD-protected circuits, use the tester's no-trip (low-current) setting, so the test current doesn't trip the RCD. No-trip readings can scatter by a few hundredths of an ohm, so repeat a borderline reading.
- Where a live test isn't practical, add the measured R1+R2 to the measured Ze. That is an accepted way to find Zs, and it doesn't include parallel earth paths.
- Compare the result with the maximum measured value for the device. If it's too high and there's no other means of fault protection, the circuit fails.
Worked example
A ring final circuit on a B32 RCBO, TN-C-S supply. Ze = 0.21 Ω, and the R1+R2 from the ring test is 0.38 Ω.
Zs = 0.21 + 0.38 = 0.59 Ω, below the 1.10 Ω maximum measured value, so it passes
You can also work backwards: R1+R2 = Zs − Ze. That's useful for checking whether a Zs reading makes sense for the cable length.
What if Zs is too high?
- Check the connections at the accessory, the breaker and the earth bar. A loose terminal is the usual cause of a sudden jump.
- Look at the circuit length and conductor sizes. A long run in 1.0 mm² cable with a 1.0 mm² cpc might need a larger cable or a lower-rated breaker.
- On a TT system, Zs is always far too high for a breaker alone, so an RCD provides fault protection instead. The check is
RA × IΔn ≤ 50 V. - On an existing installation where there's no RCD, a Zs above the limit is coded C2 on an EICR.
Prospective fault current
The same tester measures the prospective fault current (PFC) at the origin: both the prospective short-circuit current between line and neutral (PSCC) and the prospective earth fault current between line and earth (PEFC). Record the higher one. It must not be more than the breaking capacity of the devices fitted. A typical domestic breaker is rated 6 kA, but a consumer unit built to BS EN 61439-3 can have a higher conditional rating, commonly 16 kA, when the supplier's fuse is 100 A or less, so check the manufacturer's data. On a three-phase supply, the IET On-Site Guide's rule of thumb is to take about twice the single-phase value.
Sources
The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.
- BS 7671:2018+A4:2026 Chapter 41 and Table 41.3: maximum earth fault loop impedance (IET, paid standard)
- IET On-Site Guide, Appendix B Table B6: maximum measured earth fault loop impedance at ambient temperature (paid)
- IET Guidance Note 3: Inspection and Testing (continuity, earth fault loop impedance and prospective fault current tests; paid)
- NICEIC: Understanding BS 7671:2018+Amendment 4:2026 (changes and FAQs, including FI and AFDD terminology)
- IEC 60228: Conductors of insulated cables (maximum resistance values, paid standard)