R1+R2 continuity testing: how to do it and what to expect

The R1+R2 test: at the consumer unit the circuit's line conductor is linked to its protective conductor, and a low-resistance ohmmeter at the far socket measures between line and earth, reading 0.39 ohms
Beginner

Continuity of protective conductors is the first test in the sequence for a new circuit. It proves every circuit protective conductor (cpc) is connected all the way from the earth bar to every point, and its result, R1+R2, is the circuit's share of the earth fault loop impedance.

R1 is the resistance of the line conductor from the board to the furthest point. R2 is the resistance of the cpc over the same run. It's a dead test, so the circuit must be safely isolated first.

The instrument

Use a low-resistance ohmmeter, usually the continuity range on a multifunction or insulation tester, made to BS EN 61557-4. It tests with an open-circuit voltage of 4 V to 24 V and a current of at least 200 mA. Null the test leads before you start, so their resistance doesn't add to every reading.

Method 1: the R1+R2 method

  1. Isolate the circuit and prove it dead.
  2. At the board, link the circuit's line conductor to its cpc with a short lead or a temporary connector.
  3. At each point on the circuit (socket, light, switch), measure between line and earth. The reading is R1+R2 for that point.
  4. The highest reading, normally at the far end, is the one you record.
  5. Remove the link before you do anything else.

Because the link is in the line conductor, a reading at a lighting point also proves the switch is in the line conductor, so you check polarity at the same time. Operate each switch and confirm the reading only appears with it on.

Method 2: the wander lead method

Connect one end of a long test lead to the main earthing terminal and touch the other probe on each earthed point in turn. That measures R2 on its own (once you've subtracted or nulled the long lead). It's handy for checking the earth on metal accessories, light fittings and bonding, where there's no line conductor to link to.

What reading should you expect?

Multiply the cable length by the resistance per metre of the line and cpc together. These are for copper at 20 °C, from the maximum conductor resistances in IEC 60228, the same figures the IET On-Site Guide uses:

Line / cpc (mm²)Typical useR1+R2 per metre (mΩ/m)For 20 m
1.0 / 1.0Lighting36.200.72 Ω
1.5 / 1.0Lighting30.200.60 Ω
2.5 / 1.5Sockets, radials19.510.39 Ω
4.0 / 1.5Radials, cookers16.710.33 Ω
6.0 / 2.5Cookers, showers10.490.21 Ω
10 / 4.0Showers, sub-mains6.440.13 Ω

A reading much higher than expected usually means a loose or poor connection. A reading of infinity means the cpc is broken. Ring final circuits are tested differently, end to end and then cross-connected: see ring final circuit testing. On a ring, R1+R2 at each socket should be about a quarter of the end-to-end r1 + r2.

Checking the result against Zs

Add your R1+R2 to the measured Ze and compare the total with the maximum measured Zs for the protective device. For example, a 20 m radial in 2.5/1.5 cable on a B20 breaker: 0.39 + 0.35 (worst case for TN-C-S) = 0.74 Ω, well below the 1.75 Ω maximum measured value for a B20. The ring final calculator and max Zs calculator do these sums for you.

Temperature

Copper's resistance rises by about 0.4% per °C. At 70 °C, the normal maximum for PVC cable, R1+R2 is about 1.2 times its value at 20 °C. The On-Site Guide's maximum measured Zs values already allow for this, so compare room-temperature readings with them, not with BS 7671 Table 41.3.

Bonding conductors

Use the wander lead method to check main protective bonding from the main earthing terminal to the clamp on the gas and water pipes, and supplementary bonding where it's fitted. IET guidance suggests a value in the order of 0.05 Ω or less for main bonding conductors. A higher reading usually means a poor clamp or a corroded pipe surface.

Sources

The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.

  • IET Guidance Note 3: Inspection and Testing (continuity, earth fault loop impedance and prospective fault current tests; paid)
  • IET On-Site Guide, Appendix B Table B6: maximum measured earth fault loop impedance at ambient temperature (paid)
  • BS EN 61557-4: Equipment for testing, resistance of earth connection and equipotential bonding (test voltage and current; paid)
  • IEC 60228: Conductors of insulated cables (maximum resistance values, paid standard)
  • IET On-Site Guide and Guidance Note 3: continuity of ring final circuit conductors (three-step test; paid)