Maximum Zs cheat sheet

Printable one-page table of maximum measured earth fault loop impedance for Type B, C and D circuit-breakers and RCBOs at 230 V, with the BS 7671 Table 41.3 values and the formula.

Full guide

Maximum Zs cheat sheet ohmandtoken.com

Maximum measured Zs at room temperature

For testing. Matches the IET On-Site Guide Table B6: circuit-breakers to BS EN 60898 and RCBOs to BS EN 61009, U₀ 230 V.

Type6 A10 A16 A20 A25 A32 A40 A50 A63 A
B5.833.502.191.751.401.100.880.700.56
C2.921.751.100.880.700.550.440.350.28
D (0.4 s)1.460.880.550.440.350.28–––
D (5 s)2.921.751.100.880.700.550.440.350.28

BS 7671 Table 41.3 (conductors at operating temperature)

For design. 0.4 s, U₀ 230 V.

Type6 A10 A16 A20 A32 A40 A
B7.284.372.732.191.371.09
C3.642.191.371.090.680.55
D1.821.090.680.550.340.27

How the numbers work

  • Zs(max) = U₀ × Cmin ÷ Ia, with Cmin = 0.95 and Ia = 5 × In (Type B), 10 × In (Type C) or 20 × In (Type D).
  • Measured values are about 80% of Table 41.3, because you test with the cable cold.
  • Zs = Ze + (R1 + R2). Typical maximum Ze quoted for design: TN-C-S 0.35 Ω, TN-S 0.8 Ω.
  • Disconnection times, TN at 230 V: 0.4 s for final circuits up to 63 A with sockets and up to 32 A for fixed equipment; 5 s for distribution circuits.

Sources:

  • BS 7671:2018+A4:2026 Table 41.3 (IET, paid)
  • IET On-Site Guide Table B6 (paid)

Always check against your own copy of the current documents. Mains work must be carried out by a competent person.