An earth resistance tester measures how well an earth electrode, such as the rod at a TT installation, a lightning protection earth or a substation grid, connects to the ground around it. A low, stable reading means fault current can flow away safely. This guide explains the test methods and which tester suits which job.
The short answer
- Domestic TT installations: many electricians measure RA with their MFT's loop test. A dedicated tester such as the Kewtech KEW4105DLH adds proper 3-pole testing.
- Commercial, lightning protection and repeated testing: a 2-, 3- and 4-pole tester such as the Megger DET4TD2.
- Substations, telecoms and large earth systems: a full-method tester with selective and stakeless testing, such as the Fluke 1623-2 or 1625-2.
- Testing without disconnecting or driving stakes, where there are parallel earth paths: a clamp tester such as the Megger DET14C.
Our picks: professional, mid-range and entry
Some shop links are affiliate links (Amazon UK, Tooled Up): if you buy through one we may earn a small commission, at no extra cost to you. As an Amazon Associate I earn from qualifying purchases. It never changes which products we recommend, and no shop has paid to be included.
Fluke 1625-2 (or 1623-2)
Substations, telecoms and big earthing systems.
- 3- and 4-pole fall of potential, with stakes
- 4-pole soil resistivity
- Selective testing (one clamp and stakes) without disconnecting the electrode
- Stakeless testing with two clamps
- IP56 case; the -2 versions store and download results by USB
Why we picked it: Every common earth test method in one instrument. The 1625-2 adds automatic frequency control to work around interference.
Megger DET4TD2
Contractors testing TT electrodes and lightning protection earths.
- 2-, 3- and 4-pole tests
- 0.01 Ω to 20 kΩ
- 100 V CAT IV, IP54
- Kit includes leads, stakes and carry case
- Accuracy 2% ± 3 digits on 2-pole and 4-pole
Check price atRS
Kewtech KEW4105DLH
TT installations and occasional electrode tests.
- 3- and 2-wire earth resistance, 0.01 to 2000 Ω
- Earth voltage 0 to 300 V AC/DC
- IP67 dust and waterproof
- Noise rejection up to 25 V rms
- Supplied with leads, spikes and a hard case
Check price atRS
Megger DET14C
Stakeless testing where there are parallel earth paths.
- Clamp-on earth resistance, 0.05 Ω to 1500 Ω
- Elliptical jaw takes cables and tapes up to 50 mm
- True RMS earth leakage current
- CAT IV 600 V; DET24C adds download
Watch out: Clamp testing only works where there's a parallel return path, so it can't test a single isolated rod.
How the test methods work
3-pole fall of potential
The tester drives a current from the electrode under test (E) to a current spike (C) placed well away, and measures the voltage at a potential spike (P) in between. With P at about 62% of the distance from E to C in uniform soil, the reading is a good estimate of the electrode's resistance. Moving P a little either way and checking the reading barely changes confirms the spikes are far enough apart. The picture at the top of this guide shows the layout.
4-pole
A fourth lead removes the resistance of the test lead to the electrode from the result, which matters for very low readings. Four poles are also used for soil resistivity surveys, before a new earth system is designed.
2-pole
Measures between the electrode and a known good earth, such as a metal water pipe. It's quick, but the result includes the other earth's resistance.
Selective and stakeless
Selective testing uses a clamp around the electrode's conductor to measure that one electrode without disconnecting it from the rest of the system. Stakeless testing uses two clamps and no spikes at all, but only works where the electrode is part of a multi-earthed system.
What reading is good enough?
For a TT installation protected by an RCD, BS 7671 requires RA × IΔn ≤ 50 V. On a 30 mA RCD that would allow up to 1667 Ω, but guidance notes that readings above 200 Ω may not be stable, as ground conditions change with the seasons. Our earthing systems guide explains TT in more detail.
Before you buy: a quick checklist
- The methods you need: 3-pole for most electrodes; 4-pole for low readings and soil resistivity.
- Selective or stakeless testing if you can't disconnect the electrode.
- Long enough leads in the kit to place the spikes properly.
- Noise and interference rejection if you test near substations or railways.
- An IP rating that suits outdoor use.
Questions people ask
Can I use my MFT instead?
Why does my reading change through the year?
Sources
The main references behind this guide.
- Fluke 1623 and 1625 GEO earth ground testers technical data (RS copy)
- Megger DET4TD2 and DET4TR2 datasheet (Farnell copy)
- Megger DET14C and DET24C datasheet (Farnell copy)
- Kewtech KEW4105 DLH product data sheet (RS copy)
- IET Guidance Note 3: Inspection and Testing (test sequence, ring and RCD test methods, inspection intervals; paid)
- BS 7671 Regulation 411.5.3 and Table 41.5 (RA × IΔn ≤ 50 V; IET, paid standard)