Home / Tools / Maximum demand and diversity calculator

Maximum demand and diversity calculator

Add up the loads in a house and apply the allowances for diversity from the IET On-Site Guide. You get an estimated maximum demand for the whole installation, and a check against the supply fuse.

  • Electrical tool
  • Runs in your browser
  • Tested 19 November 2026
  • Sources
All the lighting points added together. Allow at least 100 W per lampholder.
The breaker rating of each ring or radial socket circuit, separated by commas.
Oven, hob and any other cooking appliances on the cooker circuit.
One number per appliance, separated by commas.
For example panel heaters and fixed appliances not on a socket circuit.
Immersion heaters, storage heaters, underfloor heating and EV chargers.
Usually 60, 80 or 100 A for a house.

How diversity works

Not everything in a house runs flat out at the same time. "Diversity" is the allowance for that, so a supply, a main switch or a sub-main can be sized for a realistic peak rather than the total of every load. The IET On-Site Guide gives standard allowances. This calculator uses its column for individual household installations:

LoadAllowance
Lighting66% of the total current demand
Standard socket circuits (rings and radials)100% of the largest circuit + 40% of every other circuit
Cooking appliances10 A + 30% of the rest, + 5 A if the cooker unit has a socket
Instantaneous water heaters (electric showers)100% of the largest + 100% of the second + 25% of the rest
Other heating and power100% up to 10 A + 50% of the rest
Thermostatic water heaters, storage heaters, floor warmingNo diversity

For a standard socket circuit, the current demand is the rating of its protective device, so a ring on a 32 A breaker counts as 32 A.

Worked example. A house at 230 V. Lighting 1 kW is 4.35 A, so 66% is 2.87 A. Socket circuits of 32, 32 and 20 A give 32 + 40% × 52 = 52.8 A. A 6.9 kW cooker is 30 A, so 10 + 30% × 20 = 16 A. An 8.5 kW shower is 37.0 A at 100%. A 3 kW immersion heater is 13.0 A with no diversity. The total is about 122 A, which is more than a 100 A fuse.

Why the answer often looks high

The On-Site Guide allowances are deliberately cautious. They were written to make sure cables and switchgear are never undersized, so a typical house can come out above its 100 A supply fuse on paper and still never blow it. Treat a result over the fuse as a prompt to look at what really runs together. Smart load management, such as an EV charger that backs off when the shower is on, is the usual answer.

Things to know

  • Apply diversity once, at the point you are sizing (the supply, main switch or a sub-main). Never apply it to a final circuit itself.
  • EV chargers: BS 7671 Regulation 722.311 says no diversity on the charger's final circuit, and allows it upstream only where load control is fitted. This tool counts them with no diversity.
  • Heat pumps, air conditioning and other big fixed loads belong in "other heating and power" or in the no-diversity box, depending on how they run. If in doubt, use no diversity.
  • Diversity is guidance, not a regulation. A designer can use measured data or a better-informed estimate instead.
  • The network operator (DNO) uses its own method to decide the supply. Ask them before adding a big load, such as a heat pump or EV charger, to an existing supply.

Sources

Where the formulas and figures on this page come from. We test every tool against worked examples from these before publishing.

  • IET On-Site Guide, Appendix A: allowances for diversity, individual household installations (paid)
  • BS 7671:2018+A4:2026 Regulation 722.311: no diversity on EV charging final circuits (IET, paid standard)