How diversity works
Not everything in a house runs flat out at the same time. "Diversity" is the allowance for that, so a supply, a main switch or a sub-main can be sized for a realistic peak rather than the total of every load. The IET On-Site Guide gives standard allowances. This calculator uses its column for individual household installations:
| Load | Allowance |
|---|---|
| Lighting | 66% of the total current demand |
| Standard socket circuits (rings and radials) | 100% of the largest circuit + 40% of every other circuit |
| Cooking appliances | 10 A + 30% of the rest, + 5 A if the cooker unit has a socket |
| Instantaneous water heaters (electric showers) | 100% of the largest + 100% of the second + 25% of the rest |
| Other heating and power | 100% up to 10 A + 50% of the rest |
| Thermostatic water heaters, storage heaters, floor warming | No diversity |
For a standard socket circuit, the current demand is the rating of its protective device, so a ring on a 32 A breaker counts as 32 A.
Why the answer often looks high
The On-Site Guide allowances are deliberately cautious. They were written to make sure cables and switchgear are never undersized, so a typical house can come out above its 100 A supply fuse on paper and still never blow it. Treat a result over the fuse as a prompt to look at what really runs together. Smart load management, such as an EV charger that backs off when the shower is on, is the usual answer.
Things to know
- Apply diversity once, at the point you are sizing (the supply, main switch or a sub-main). Never apply it to a final circuit itself.
- EV chargers: BS 7671 Regulation 722.311 says no diversity on the charger's final circuit, and allows it upstream only where load control is fitted. This tool counts them with no diversity.
- Heat pumps, air conditioning and other big fixed loads belong in "other heating and power" or in the no-diversity box, depending on how they run. If in doubt, use no diversity.
- Diversity is guidance, not a regulation. A designer can use measured data or a better-informed estimate instead.
- The network operator (DNO) uses its own method to decide the supply. Ask them before adding a big load, such as a heat pump or EV charger, to an existing supply.