Cable sizing calculator (twin and earth)

Find the smallest twin and earth (6242Y) cable for a final circuit. It checks the current rating against BS 7671 Table 4D5, with correction factors for ambient temperature, grouping and thermal insulation, and then checks the voltage drop.

  • Electrical tool
  • Runs in your browser
  • Tested 19 November 2026
  • Sources
The current the circuit will actually carry.
Cartridge fuses include BS 88 and BS 1361.
Loft: above a plasterboard ceiling under that depth of insulation. Stud wall: insulated, touching or not touching the inner surface.
Including this one. 1 if it runs on its own.

The checks

A cable has to carry the circuit's current without overheating, and deliver enough voltage at the far end. BS 7671 sets both out in Appendix 4.

  1. Current. Pick a device rated at least the design current: In ≥ Ib. Then the cable's tabulated rating must be at least It ≥ In ÷ (Ca × Cg × Ci × Cf).
  2. Voltage drop. drop = mV/A/m × Ib × length ÷ 1000. For a public supply, BS 7671 Appendix 4 suggests 3% for lighting and 5% for other uses, from the origin of the installation to the load.

The factors are: Ca for ambient temperature (Table 4B1), Cg for grouping (Table 4C1), Ci for a cable surrounded by thermal insulation (Regulation 523.9), and Cf = 0.725 for a BS 3036 rewirable fuse.

Twin and earth ratings (Table 4D5)

Size (mm²)C100101102103AmV/A/m
1.0161310.513811.544
1.5201613161014.529
2.52721172113.52018
43727222717.52611
64734273523.5327.3
106445364732444.4
168557466342.5572.8

Ratings in amps at 30 °C ambient, with the conductor at up to 70 °C. Voltage drop is for a single-phase circuit at full operating temperature.

Worked example. A 32 A radial for a 7.4 kW EV charger, design current 32 A, run 20 m clipped direct. 2.5 mm² (27 A) is too small. 4 mm² (37 A) is fine, and the drop is 11 × 32 × 20 ÷ 1000 = 7.0 V, under the 11.5 V allowed. Run the same cable above a ceiling under 100 mm of loft insulation (method 100) and 4 mm² is only 27 A, so it needs 6 mm² (34 A).

Things to know

  • Reference methods 100 to 103 already allow for the insulation they describe. The extra insulation factor Ci is for a cable clipped direct that then passes through, or is buried in, insulation. Regulation 523.9 applies it to the method C rating.
  • Grouping assumes the grouped circuits are similar and all loaded. Lightly loaded neighbours, such as lighting circuits, may justify less derating, but that's a designer's judgement.
  • The voltage drop limit covers the whole installation. If a sub-main already drops some voltage, the final circuit gets less.
  • Passing these two checks isn't the end. You still need to confirm the earth fault loop impedance (max Zs), the cpc size (adiabatic check) and the disconnection time.
  • Check against the current edition of BS 7671 and the cable manufacturer's data before you install.