The checks
A cable has to carry the circuit's current without overheating, and deliver enough voltage at the far end. BS 7671 sets both out in Appendix 4.
- Current. Pick a device rated at least the design current: In ≥ Ib. Then the cable's tabulated rating must be at least
It ≥ In ÷ (Ca × Cg × Ci × Cf). - Voltage drop.
drop = mV/A/m × Ib × length ÷ 1000. For a public supply, BS 7671 Appendix 4 suggests 3% for lighting and 5% for other uses, from the origin of the installation to the load.
The factors are: Ca for ambient temperature (Table 4B1), Cg for grouping (Table 4C1), Ci for a cable surrounded by thermal insulation (Regulation 523.9), and Cf = 0.725 for a BS 3036 rewirable fuse.
Twin and earth ratings (Table 4D5)
| Size (mm²) | C | 100 | 101 | 102 | 103 | A | mV/A/m |
|---|---|---|---|---|---|---|---|
| 1.0 | 16 | 13 | 10.5 | 13 | 8 | 11.5 | 44 |
| 1.5 | 20 | 16 | 13 | 16 | 10 | 14.5 | 29 |
| 2.5 | 27 | 21 | 17 | 21 | 13.5 | 20 | 18 |
| 4 | 37 | 27 | 22 | 27 | 17.5 | 26 | 11 |
| 6 | 47 | 34 | 27 | 35 | 23.5 | 32 | 7.3 |
| 10 | 64 | 45 | 36 | 47 | 32 | 44 | 4.4 |
| 16 | 85 | 57 | 46 | 63 | 42.5 | 57 | 2.8 |
Ratings in amps at 30 °C ambient, with the conductor at up to 70 °C. Voltage drop is for a single-phase circuit at full operating temperature.
Things to know
- Reference methods 100 to 103 already allow for the insulation they describe. The extra insulation factor Ci is for a cable clipped direct that then passes through, or is buried in, insulation. Regulation 523.9 applies it to the method C rating.
- Grouping assumes the grouped circuits are similar and all loaded. Lightly loaded neighbours, such as lighting circuits, may justify less derating, but that's a designer's judgement.
- The voltage drop limit covers the whole installation. If a sub-main already drops some voltage, the final circuit gets less.
- Passing these two checks isn't the end. You still need to confirm the earth fault loop impedance (max Zs), the cpc size (adiabatic check) and the disconnection time.
- Check against the current edition of BS 7671 and the cable manufacturer's data before you install.