"What size cable do I need?" is one of the most searched electrical questions, and the honest answer is "it depends on how the cable is installed". A 6 mm² cable that's perfectly fine clipped to a wall can overheat buried in loft insulation. This guide explains how cable sizing works under BS 7671:2018+A4:2026, with the real figures for the twin and earth cable used in UK homes.
The three currents: Ib ≤ In ≤ Iz
- Ib, the design current: the current the circuit will actually carry.
- In, the rated current of the protective device: the circuit-breaker or fuse.
- Iz, the current-carrying capacity of the cable, as installed.
Regulation 433.1.1 requires Ib ≤ In ≤ Iz. In plain English: the breaker must be big enough for the load, and the cable must be able to carry the breaker's rating where it's installed. The breaker protects the cable, not the appliance.
Installation methods change everything
A cable's rating depends on how easily it can lose heat. BS 7671's Appendix 4 tabulates ratings for each reference method. For 70 °C thermoplastic flat twin and earth (6242Y), Table 4D5 gives:
| Size | Method 100 | Method 101 | Method 102 | Method 103 | Method C | Method A | mV/A/m |
|---|---|---|---|---|---|---|---|
| 1 mm² | 13 | 10.5 | 13 | 8 | 16 | 11.5 | 44 |
| 1.5 mm² | 16 | 13 | 16 | 10 | 20 | 14.5 | 29 |
| 2.5 mm² | 21 | 17 | 21 | 13.5 | 27 | 20 | 18 |
| 4 mm² | 27 | 22 | 27 | 17.5 | 37 | 26 | 11 |
| 6 mm² | 34 | 27 | 35 | 23.5 | 47 | 32 | 7.3 |
| 10 mm² | 45 | 36 | 47 | 32 | 64 | 44 | 4.4 |
| 16 mm² | 57 | 46 | 63 | 42.5 | 85 | 57 | 2.8 |
- Method C: clipped direct to a surface, or buried in plaster.
- Method 100: above a plasterboard ceiling, covered by thermal insulation not more than 100 mm thick.
- Method 101: above a plasterboard ceiling, covered by insulation more than 100 mm thick. Modern lofts often have 270 mm or more.
- Method 102: in a stud wall with thermal insulation, cable touching the inner wall surface.
- Method 103: in a stud wall with thermal insulation, cable not touching the inner wall surface.
- Method A: enclosed in conduit in a thermally insulating wall.
Look at 2.5 mm²: 27 A clipped direct, but only 13.5 A surrounded by insulation in a stud wall.
Correction factors
The tables assume a 30 °C ambient temperature and no other cables nearby. If the real conditions are worse, the tabulated rating It must be big enough after correction:
It ≥ In ÷ (Ca × Cg × Ci × Cc)
- Ca, ambient temperature: less than 1 above 30 °C, for example in a hot plant room or airing cupboard.
- Cg, grouping: cables bunched together heat each other.
- Ci, thermal insulation: for a cable totally surrounded by insulation for more than 0.5 m, 0.5 (half the clipped-direct rating) unless a method above already covers it.
- Cc, circuit protection: 0.725 where the device is a BS 3036 rewirable fuse, because it needs more overload current to blow.
Then check voltage drop
A long cable loses voltage. BS 7671 Appendix 4 gives limits for installations supplied from the public low-voltage network: 3% for lighting (6.9 V at 230 V) and 5% for other uses (11.5 V). Using the mV/A/m figure from the table:
voltage drop (V) = mV/A/m × Ib × length (m) ÷ 1000
Our cable voltage drop calculator does this for you.
Worked example: a 9.5 kW electric shower
- Design current: 9,500 W ÷ 230 V = 41.3 A. The shower's own circuit is designed for its full rating, with no diversity.
- Protective device: the next standard size at or above Ib is a 45 A circuit-breaker. (Always check the shower maker's instructions, which state the device rating to use.)
- Cable, clipped direct (Method C): 6 mm² is rated 47 A, which is at least 45 A. ✓
- Same cable run over a ceiling under 100 mm of insulation (Method 100): 6 mm² is only 34 A ✗; 10 mm² is 45 A ✓.
- Under thicker loft insulation (Method 101): 10 mm² is 36 A ✗; 16 mm² is 46 A ✓. Better still, route the cable so it isn't buried in insulation.
- Voltage drop for 6 mm² clipped direct over 15 m: 7.3 × 41.3 × 15 ÷ 1000 = 4.52 V, about 2.0%, inside the 5% limit. ✓
The design then goes on to check the earth fault loop impedance against the breaker's maximum (see our max Zs calculator), that the cpc can survive a fault (the adiabatic calculator), and the RCD protection required for the circuit.
The protective conductor in twin and earth
Flat twin and earth has a smaller earth (cpc) than its live conductors: 1.0 mm² in 1.5 mm² cable, 1.5 mm² in 2.5 and 4 mm², 2.5 mm² in 6 mm², 4 mm² in 10 mm² and 6 mm² in 16 mm². That smaller cpc is why the earth fault loop impedance and adiabatic checks matter.
Going deeper
Grouping factors in practice
Table 4C1 gives grouping factors that fall as more circuits are bunched together. Two things make life easier. First, Appendix 4 allows grouping to be ignored for cables that are lightly loaded, broadly those carrying not more than 30% of their grouped rating. Second, the reduction only applies over the length where the cables are actually grouped, and where that length is short, a designer can often avoid it by spacing the cables. In domestic work, the place grouping usually bites is where many circuits leave the consumer unit together through insulation.
Thermal insulation over short lengths
For a cable surrounded by insulation for only a short length, as where it passes through an insulated wall, Table 52.2 gives derating factors smaller in effect than 0.5: the shorter the length, the less the cable heats up, because heat flows along the copper to the cooler parts either side. At 0.5 m or more, the factor is 0.5.
Voltage drop at the real conductor temperature
The mV/A/m figures assume the conductor is at its maximum operating temperature, 70 °C for thermoplastic cable. A lightly loaded cable runs cooler and has a lower resistance, so the real drop is smaller. Appendix 4 allows a correction for this, which can justify a long, lightly loaded run that fails the simple calculation. Our voltage drop calculator uses the full-temperature figures, which is the cautious approach.
Overload protection that's not needed
Regulation 433.3 allows overload protection to be omitted in some cases, such as a circuit supplying a load that can't cause an overload, like a fixed immersion heater with its own rating. Fault protection is still required. This is why the In ≤ Iz rule sometimes appears to be broken on real installations; the designer must be able to justify it under 433.3.
Sources
The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.