An Electrical Installation Condition Report (EICR) is a check-up on an existing installation. The inspector inspects and tests it, lists anything wrong as an observation, and gives each observation a classification code. The codes decide whether the report is satisfactory, and how urgently things need fixing.
The four codes
| Code | Meaning | What happens | Report outcome |
|---|---|---|---|
| C1 | Danger present. Risk of injury. | Immediate remedial action required. The inspector should make it safe there and then, with your agreement, for example by isolating the circuit. | Unsatisfactory |
| C2 | Potentially dangerous. | Urgent remedial action required. Not dangerous right now, but it would become dangerous if a fault or other foreseeable event happened. | Unsatisfactory |
| C3 | Improvement recommended. | Not a danger, but fixing it would make the installation safer. | Can still be satisfactory |
| FI | Further investigation is advised. | The inspector found a possible issue they couldn't fully identify within the agreed limits of the inspection. | Can still be satisfactory (from Amendment 4) |
Each observation gets only one code, the most serious that applies. If there's even one C1 or C2, the overall condition must be reported as unsatisfactory. If there are only C3s, it can be satisfactory.
What changed in Amendment 4 (2026)
BS 7671:2018+A4:2026 has been the only current version since 15 October 2026, and it changed the EICR in two ways that matter here:
- FI no longer makes a report unsatisfactory on its own. The observations section is now split in two. C1 and C2 go in the first part and decide the outcome. C3 and FI go in the second part and don't.
- The wording of FI changed from "further investigation required without delay" to "further investigation is advised".
The IET's explanation is that FI was often misused, for example when there wasn't enough time to test properly, or when a circuit couldn't be identified. Its view is that an unidentified circuit or an insulation resistance below 1 MΩ should get a proper code, not FI, because periodic inspection is about deciding whether the installation is safe to keep using, not about fault finding. Electrical Safety First's guidance says that in a domestic installation it should generally be possible to code every observation without FI.
Reports done before 15 October 2026 to the earlier version follow the old rules, so an older report with an FI may say unsatisfactory.
Examples of each code
These come from Electrical Safety First's Best Practice Guide 4 (issue 7.4, August 2026), which the whole industry uses. It's strongly recommended that inspectors follow it, and justify any departure from it.
C1, danger present
- A breaker missing from a consumer unit with no blank fitted, so live parts can be touched.
- A badly damaged socket or switch with exposed live parts.
- Metalwork that has become live because of a fault.
- Incorrect polarity at the origin of the installation.
C2, potentially dangerous
- No reliable and effective means of earthing, or a gas, oil or water pipe used as the earth.
- No main protective bonding to incoming gas or water pipes, or bonding smaller than 6 mm².
- No earth at a socket-outlet.
- No RCD for sockets that could reasonably be used to supply equipment outdoors.
- The main RCD on a TT installation fails to trip when tested.
- Earth fault loop impedance too high for the protective device to disconnect in time, where there's no RCD.
- Incorrect polarity at a final circuit or accessory.
- Insulation resistance below 1 MΩ.
- A ring final circuit with a broken conductor, or a borrowed neutral shared between two circuits.
- A loose connection with signs of overheating, or evidence of excessive heat such as charring.
- A socket (other than SELV or a shaver socket) less than 2.5 m horizontally from the edge of zone 1 in a bathroom.
C3, improvement recommended
- A Type AC RCD where a Type A is required.
- No RCD on lighting circuits in a home.
- No RCD for socket circuits that aren't likely to supply equipment outdoors and don't serve a bathroom.
- No AFDD in a high-rise residential building, HMO, purpose-built student accommodation or care home.
- No surge protective device where Regulation 443.4.1 (a) or (c) requires one.
- A plastic consumer unit under a wooden staircase or on the only escape route, not inside a non-combustible enclosure.
- Missing circuit labels or a missing "Safety electrical connection, do not remove" notice.
Not coded at all
Best Practice Guide 4 also lists things that are only non-compliances with today's standard, or myths, and shouldn't be coded. Examples: old cable colours (red and black), rewireable fuses that still give adequate protection, older BS 3871 circuit-breakers, and the absence of bonding to metal sinks or baths that aren't extraneous-conductive-parts. An installation built to an older edition of BS 7671 isn't unsafe just because it doesn't meet the current one.
How often you need an EICR
- Rented homes in England: at least every 5 years, by law. This now covers social housing too: social tenancies granted from 1 December 2025, and older social tenancies from 1 May 2026. Landlords must give tenants a copy within 28 days of the inspection, give new tenants a copy before they move in, and give the council a copy within 7 days if asked.
- Owner-occupied homes: no legal requirement, but IET guidance suggests up to 10 years, and also on a change of occupancy.
- The inspector sets the date for the next inspection on the report, and it can be sooner if the installation's condition calls for it.
How long you have to fix a C1, C2 or FI
For a rented home in England, the landlord must complete remedial work or further investigation within 28 days, or sooner if the report says so, and then give the tenant and the council written confirmation. The government's guidance for landlords still uses the older wording for FI, so landlords should treat an FI as work to be done, even though Amendment 4 means it doesn't make the report unsatisfactory. Councils can fine landlords up to £40,000 for breaches.
For your own home there's no legal deadline, but C1 means now and C2 means as a matter of urgency. Don't pay to fix C3s unless you want to, and be wary of any report that codes everything C2. Electrical Safety First's guidance warns against coding being influenced by anyone except the inspector's own judgement.
Sources
The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.
- Electrical Safety First Best Practice Guide 4: Electrical installation condition reporting, classification codes (Issue 7.4, August 2026)
- IET Wiring Matters, July 2026: Further investigation (EICR codes in BS 7671:2018+A4:2026)
- NICEIC: Understanding BS 7671:2018+Amendment 4:2026 (changes and FAQs, including FI and AFDD terminology)
- Electrical Safety First: BS 7671:2018+A4:2026 and domestic installations, pocket guide (2026)
- SELECT: So what's new? Overview of BS 7671:2018+Amendment 4:2026
- GOV.UK: Electrical safety standards in the private and social rented sectors, guidance (England)