EICR codes cheat sheet ohmandtoken.com
| Code | Meaning | Outcome |
|---|
| C1 | Danger present. Immediate remedial action. | Unsatisfactory |
| C2 | Potentially dangerous. Urgent remedial action. | Unsatisfactory |
| C3 | Improvement recommended. | Can be satisfactory |
| FI | Further investigation is advised. | Can be satisfactory (Amendment 4) |
Examples
- C1: missing blank exposing live parts; damaged accessory with live parts exposed; metalwork made live by a fault; incorrect polarity at the origin.
- C2: no effective earthing; no main bonding or bonding under 6 mm²; no earth at a socket; insulation resistance below 1 MΩ; broken ring conductor or borrowed neutral; signs of overheating; socket within 2.5 m of zone 1; Zs too high with no RCD.
- C3: Type AC RCD where Type A is needed; no RCD on home lighting; no AFDD in an HMO, care home, student block or high-rise residential building; missing labels.
- Not coded: old red and black colours, rewireable fuses that still protect, BS 3871 breakers.
Sources:
- Electrical Safety First Best Practice Guide 4
- BS 7671:2018+A4:2026 Chapter 65 (IET, paid)
Always check against your own copy of the current documents. Mains work must be carried out by a competent person.
How the codes decide the result
An EICR's overall result follows from the codes. Any C1 or C2 makes the report unsatisfactory. C3 on its own does not, because it's a recommendation, not a requirement. Under Amendment 4, an FI no longer makes a report unsatisfactory by itself, but the investigation still needs doing, and what it finds may well be coded C1 or C2.
C1 means act now
A C1 is a danger to anyone who comes near it. The inspector should make it safe on the spot where they can, for example by isolating the circuit, and tell the person responsible straight away, in writing as well as in person. It shouldn't wait for the report to be typed up.
For landlords in England
Under the Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020, a landlord who receives an unsatisfactory report must have the remedial work or further investigation done within 28 days, or sooner if the report says so, and then get written confirmation that it has been done.
Coding is judgement, not a lookup
The same defect can earn different codes in different places. Best Practice Guide 4 gives typical codes for common findings, but the inspector still has to decide how likely the defect is to cause harm where it is. That's why the examples on the sheet are a guide, not a rule.