Home / Quizzes / Insulation resistance testing
Insulation resistance testing quiz
Test voltages, minimum values, what to disconnect, two-way switching and what low readings usually mean.
1What test voltage and minimum insulation resistance apply to a circuit above 500 V?
Answer: 1000 V DC and 1 MΩ
Table 64: SELV and PELV 250 V and 0.5 MΩ; up to 500 V, 500 V and 1 MΩ; above 500 V, 1000 V and 1 MΩ.
Source: BS 7671 Regulation 643.3 and Table 64 (paid), as set out in our guide
Read more: Insulation resistance testing: test voltages, minimum values and method
2Which of these should be disconnected before an insulation resistance test?
Answer: Surge protective devices and electronic equipment such as dimmers and LED drivers
The test voltage can damage electronics and they can affect the reading, so disconnect them, along with anything the manufacturer says to.
Source: BS 7671 Regulation 643.3 and Table 64 (paid), as set out in our guide
Read more: Insulation resistance testing: test voltages, minimum values and method
3How should you test insulation resistance on a two-way lighting circuit?
Answer: With the switches in both positions, so each strapper is tested
Switch positions decide which strapper is connected, so test in both to cover each one.
Source: BS 7671 Regulation 643.3 and Table 64 (paid), as set out in our guide
Read more: Insulation resistance testing: test voltages, minimum values and method
4An SPD on a circuit can't reasonably be disconnected. What does BS 7671 allow for the insulation resistance test?
Answer: Reducing the test voltage for that circuit to 250 V DC, with a minimum of 1 MΩ
Regulation 643.3 lets the test voltage be reduced to 250 V DC where an SPD or other equipment can't reasonably be disconnected, but the reading must still be at least 1 MΩ.
Source: BS 7671 Regulation 643.3 and Table 64 (paid), as set out in our guide
Read more: Insulation resistance testing: test voltages, minimum values and method
5Insulation resistance reads low between neutral and earth only. What is a common cause?
Answer: A neutral touching earth in an accessory, or a borrowed neutral
Low neutral to earth on its own often points to a neutral touching earth or a neutral borrowed from another circuit.
Source: BS 7671 Regulation 643.3 and Table 64 (paid), as set out in our guide
Read more: Insulation resistance testing: test voltages, minimum values and method
6Line to neutral insulation resistance reads very low. What's the most likely reason on a lighting circuit?
Answer: A lamp or transformer still connected
A connected load gives a low line to neutral reading. Remove lamps and disconnect equipment before testing.
Source: BS 7671 Regulation 643.3 and Table 64 (paid), as set out in our guide
Read more: Insulation resistance testing: test voltages, minimum values and method
7Why keep the test leads connected for a moment after an insulation resistance test on a long cable?
Answer: So the charge stored by the test can discharge before anyone touches the conductors
Long cables and capacitive loads store charge. Most testers discharge automatically once you release the test button.
Source: BS 7671 Regulation 643.3 and Table 64 (paid), as set out in our guide; HSE GS38: Electrical test equipment for use on low voltage electrical systems
Read more: Insulation resistance testing: test voltages, minimum values and method
8What kind of voltage does an insulation resistance tester apply?
Answer: DC, higher than the normal working voltage
It applies a DC test voltage, measures the tiny leakage current and works out a resistance in megohms.
Source: BS 7671 Regulation 643.3 and Table 64 (paid), as set out in our guide
Read more: Insulation resistance testing: test voltages, minimum values and method
9A new installation's circuits read 0.9 MΩ at 500 V. Is that acceptable?
Answer: No, the minimum is 1 MΩ
For circuits up to 500 V, Table 64 sets a minimum of 1 MΩ at 500 V DC. A new installation would normally read hundreds of megohms.
Source: BS 7671 Regulation 643.3 and Table 64 (paid), as set out in our guide
Read more: Insulation resistance testing: test voltages, minimum values and method
Your score
Written by us to help you revise. Not affiliated with SJIB, SECTT, the IET or City & Guilds. Questions follow BS 7671:2018+A4:2026 and the other documents named in each answer. If you think an answer is wrong, tell us and we'll check it against the source.