Circuit-breakers and RCDs quiz

MCB curves, trip ranges, overload limits, breaking capacity, RCD types AC, A, F and B, S types and RCBOs.

21 questionsFICA area: BS 7671 Parts 1, 3, 4, 5 and 7Answers checked against the sources shown

0 of 21 answered
  1. 1Between what multiples of its rated current must a Type C circuit-breaker trip instantly?

    Answer: Over 5 × In, up to 10 × In

    Type C breakers trip instantly somewhere above 5 × In and must trip by 10 × In. BS 7671 uses the top of the range, 10 × In, for maximum Zs.

    Source: BS EN 60898-1: circuit-breakers for household installations (paid)

    Read more: Type B vs Type C vs Type D circuit-breakers (MCBs and RCBOs)

  2. 2Between what multiples of its rated current must a Type D circuit-breaker trip instantly?

    Answer: Over 10 × In, up to 20 × In

    Type D covers very high inrush loads and trips instantly above 10 × In, up to 20 × In.

    Source: BS EN 60898-1: circuit-breakers for household installations (paid)

    Read more: Type B vs Type C vs Type D circuit-breakers (MCBs and RCBOs)

  3. 3Over what range of current will a 32 A Type B circuit-breaker trip instantly?

    Answer: 96 A to 160 A

    Type B trips instantly above 3 × In and by 5 × In: 3 × 32 = 96 A and 5 × 32 = 160 A.

    Source: BS EN 60898-1: circuit-breakers for household installations (paid)

    Read more: Type B vs Type C vs Type D circuit-breakers (MCBs and RCBOs)

  4. 4How do a B32 and a C32 circuit-breaker compare under a small overload?

    Answer: They behave the same, because the type only changes the instant magnetic trip

    Both share the same thermal (overload) limits in BS EN 60898-1. The B, C or D letter only sets the magnetic trip range.

    Source: BS EN 60898-1: circuit-breakers for household installations (paid)

    Read more: Type B vs Type C vs Type D circuit-breakers (MCBs and RCBOs)

  5. 5What is a circuit-breaker's conventional non-tripping current to BS EN 60898-1?

    Answer: 1.13 × In: it must not trip within 1 hour

    At 1.13 × In the breaker must not trip within an hour. At 1.45 × In it must trip within an hour.

    Source: BS EN 60898-1: circuit-breakers for household installations (paid)

    Read more: Type B vs Type C vs Type D circuit-breakers (MCBs and RCBOs)

  6. 6At 2.55 × In, how quickly must a 20 A circuit-breaker to BS EN 60898-1 trip?

    Answer: In more than 1 second and less than 60 seconds

    At 2.55 × In it must trip in more than 1 s and less than 60 s (120 s for breakers over 32 A).

    Source: BS EN 60898-1: circuit-breakers for household installations (paid)

    Read more: Type B vs Type C vs Type D circuit-breakers (MCBs and RCBOs)

  7. 7Which part of a circuit-breaker deals with short circuits and earth faults?

    Answer: The magnetic trip, which opens in about 10 milliseconds

    The magnetic coil pulls the contacts open almost immediately at high current. The bimetal strip handles overloads more slowly.

    Source: BS EN 60898-1: circuit-breakers for household installations (paid)

    Read more: Type B vs Type C vs Type D circuit-breakers (MCBs and RCBOs)

  8. 8Which circuit-breaker type suits very high inrush loads such as welders and X-ray machines?

    Answer: Type D

    Type D tolerates surges up to 10 × In without tripping instantly, so it suits welders, X-ray machines and large transformers.

    Source: BS EN 60898-1: circuit-breakers for household installations (paid)

    Read more: Type B vs Type C vs Type D circuit-breakers (MCBs and RCBOs)

  9. 9Compared with a Type B breaker of the same rating, what is the maximum Zs for a Type C?

    Answer: Half, because it needs twice the fault current to trip instantly

    Ia for Type C is 10 × In against 5 × In for Type B, so maximum Zs is halved. That's why swapping a B for a C to cure tripping can leave a circuit unable to disconnect in time.

    Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard)

    Read more: Type B vs Type C vs Type D circuit-breakers (MCBs and RCBOs)

  10. 10What short-circuit capacity are domestic circuit-breakers usually rated at?

    Answer: 6 kA (marked 6000)

    Domestic breakers are usually 6 kA and commercial ones often 10 kA. The figure in a box on the front is Icn in amps.

    Source: BS EN 60898-1: circuit-breakers for household installations (paid)

    Read more: Type B vs Type C vs Type D circuit-breakers (MCBs and RCBOs)

  11. 11Which standard does an RCBO (an RCD and circuit-breaker in one) meet?

    Answer: BS EN 61009-1

    RCBOs are made to BS EN 61009-1. An RCCB, an RCD with no overcurrent protection, is BS EN 61008-1.

    Source: BS EN 61008-1 and BS EN 61009-1: RCCBs and RCBOs (paid)

    Read more: Type B vs Type C vs Type D circuit-breakers (MCBs and RCBOs)

  12. 12What does 'B32 30 mA Type A' on an RCBO mean?

    Answer: A 32 A Type B curve breaker with a 30 mA Type A RCD

    The curve letter and number describe the overcurrent part. The mA rating and the RCD type describe the earth leakage part.

    Source: BS EN 61008-1 and BS EN 61009-1: RCCBs and RCBOs (paid)

    Read more: Type B vs Type C vs Type D circuit-breakers (MCBs and RCBOs)

  13. 13What does an RCD compare to decide whether to trip?

    Answer: The current going out on the line with the current coming back on the neutral

    If the two differ, the difference is leaking away, for example through a person to earth, and the RCD trips.

    Source: IET Wiring Matters (September 2019): Which RCD type?

    Read more: RCD types explained: AC, A, F and B, and which one you need

  14. 14Which RCD type adds detection of composite residual currents from single-phase frequency-controlled loads, and up to 10 mA of smooth DC?

    Answer: Type F

    Type F does everything Type A does, plus composite currents from single-phase variable-speed drives, and copes with up to 10 mA of smooth DC.

    Source: IET Wiring Matters (September 2019): Which RCD type?

    Read more: RCD types explained: AC, A, F and B, and which one you need

  15. 15Which RCD type detects smooth DC and sinusoidal AC up to 1 kHz?

    Answer: Type B

    Type B is used for three-phase drives, PV inverters without isolation, some EV chargers and UPS systems.

    Source: IET Wiring Matters (September 2019): Which RCD type?

    Read more: RCD types explained: AC, A, F and B, and which one you need

  16. 16Which RCD type detects every kind of residual current a Type A detects, and more?

    Answer: Type B

    Each type does everything the one before it does: AC, then A, then F, then B. So a Type B covers everything a Type A detects, plus smooth DC.

    Source: IET Wiring Matters (September 2019): Which RCD type?

    Read more: RCD types explained: AC, A, F and B, and which one you need

  17. 17Between what times must an S type (time-delayed) RCD trip at its rated residual current?

    Answer: 130 ms and 500 ms

    S types are delayed on purpose so a downstream RCD trips first, but must still trip between 130 ms and 500 ms at IΔn.

    Source: BS EN 61008-1 and BS EN 61009-1: RCCBs and RCBOs (paid)

    Read more: RCD types explained: AC, A, F and B, and which one you need

  18. 18Why is an S type RCD fitted upstream of other RCDs?

    Answer: So the RCD nearest the fault trips first and they don't both trip

    The time delay gives selectivity, so one fault doesn't take out everything downstream.

    Source: IET Wiring Matters (September 2019): Which RCD type?

    Read more: RCD types explained: AC, A, F and B, and which one you need

  19. 19What are 100 mA and 300 mA RCDs typically used for?

    Answer: Fire protection and selectivity

    30 mA is the rating used for additional protection of people. Higher ratings are used for fire protection and selectivity.

    Source: IET Wiring Matters (September 2019): Which RCD type?

    Read more: RCD types explained: AC, A, F and B, and which one you need

  20. 20What is an RDC-DD, often built into EV chargers, for?

    Answer: Detecting 6 mA of smooth DC fault current, so a Type A RCD can be used upstream

    Section 722 allows a Type B RCD, or a Type A RCD together with a device that detects 6 mA of smooth DC. That device is the RDC-DD.

    Source: BS 7671:2018+A4:2026, IET Wiring Regulations (paid standard); IET Wiring Matters (September 2019): Which RCD type?

    Read more: RCD types explained: AC, A, F and B, and which one you need

  21. 21A washing machine with a variable-speed motor is on its own RCD. Which RCD type is typically chosen?

    Answer: Type F

    Type F covers the composite residual currents produced by single-phase frequency-controlled motors, as in washing machines, dishwashers and heat pumps.

    Source: IET Wiring Matters (September 2019): Which RCD type?

    Read more: RCD types explained: AC, A, F and B, and which one you need