Every UK plug to BS 1363 has a fuse in it, and choosing the wrong one, or overloading an extension lead, is a common cause of overheating. Here's how to get it right, based on Electrical Safety First's guidance.
3 A or 13 A?
Plug fuses are made to BS 1362, and manufacturers have standardised on two ratings: 3 A and 13 A. Electrical Safety First's guide is that appliances rated from about 700 W up to 3,000 W, the most a wall socket can supply, need a 13 A fuse. Lower-powered items take a 3 A fuse.
| Fuse | For | Examples |
|---|---|---|
| 3 A (red) | Appliances up to about 700 W | Table and standard lamps, television, computer, soldering iron |
| 13 A (brown) | Appliances from about 700 W to 3,000 W | Kettle, toaster, iron, washing machine, dishwasher, fridge, freezer, microwave, vacuum cleaner, power drill |
Electrical Safety First lists fridges and freezers under 13 A even though they use only a few hundred watts while running. Motors and compressors draw a much larger current for a moment when they start, so follow the appliance's instructions rather than the running wattage alone. 5 A fuses are still sold for some older equipment. If you're not sure, check the appliance's instructions, and always replace a blown fuse with one of the same rating.
Working out the current
amps = watts ÷ volts
UK mains is nominally 230 V. A 700 W appliance draws 700 ÷ 230 = 3.0 A, which is where the 3 A limit comes from, and 3,000 W draws 13.0 A, the most a 13 A plug and socket should carry. The power is on the appliance's rating plate. Electrical Safety First publishes typical ratings for common appliances, and our Ohm's law calculator converts between watts, amps and volts.
What the plug fuse protects
The fuse in the plug protects the flexible cable between the plug and the appliance. The socket circuit in your wall is protected by a circuit-breaker or fuse in the consumer unit, often rated 32 A for a ring final circuit. That's far more than the thin flex on a table lamp could carry safely, so the plug fuse is there to blow first if the flex or appliance develops a fault or is overloaded.
That's also why fitting a 13 A fuse "to stop it blowing" is dangerous. If a 3 A fuse keeps blowing on a lamp, something is wrong with the lamp or its flex. Unplug it and get it checked.
Wiring a plug
- Brown (red on old flex) to live (L), the terminal with the fuse, bottom right when you look into the back of the plug.
- Blue (black on old flex) to neutral (N), bottom left.
- Green and yellow (green on old flex) to earth (E), top centre.
- The cord grip must clamp the cable's outer sheath, with no coloured inner wires showing outside the plug.
- Check the plug is marked BS 1363 and the fuse BS 1362, and that there are no signs of overheating.
Most appliances now come with a moulded plug that can't be rewired. Only change the fuse in those, using the fuse carrier.
Extension leads: don't overload them
Most extension leads are rated at 13 A (some older ones at 10 A), however many sockets they have. Four sockets doesn't mean four times the power: the total must stay within the lead's rating, which is 3,000 W for a 13 A lead.
| Plugged in | Power | Current |
|---|---|---|
| Kettle | 3,000 W | 13.0 A |
| Fan heater | 2,000 W | 8.7 A |
| Toaster (2 slice) | 900 W | 3.9 A |
| Phone charger | 20 W | 0.1 A |
| Total | 5,920 W | 25.7 A, nearly twice the 13 A limit |
Kettles, heaters, irons, toasters and hair dryers are the ones to watch: any one of them can use most of a lead's capacity on its own. Plug high-power appliances straight into a wall socket.
Electrical Safety First's rules for extension leads
- Use only one extension lead per wall socket, and never plug one extension lead into another ("daisy chaining").
- Fully unwind cable reels before use. A reel's rating assumes it's unwound, and running it wound up can make it overheat and catch fire. Use reels fitted with a thermal cut-out.
- Buy from reputable retailers, not third-party sellers online, and check the lead has a standard UK plug with a fuse.
- Look out for danger signs: a smell of hot plastic, scorch marks, crackling, melted plastic, or a fuse or circuit-breaker that keeps operating.
- If you rely on extension leads all the time, have more wall sockets fitted by a registered electrician. Adding a socket to an existing circuit isn't usually notifiable in England; see Part P notifiable work.
Electric vehicles shouldn't be charged from an extension lead at all. See EV charger installation.
Sources
The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.