One-way light switch wiring with a loop-in ceiling rose: the switch drop's brown from the loop terminal goes to COM, its blue core sleeved brown carries the switched line from L1 back to the rose, and the lamp flex connects to the switched line and neutral terminals
Beginner

Most UK lighting is wired with "loop-in" ceiling roses and a switch drop: a cable that runs down the wall from the ceiling rose to the switch. Knowing how it fits together makes it much easier to swap a switch safely, fit a dimmer, or understand what you're looking at.

Safety first. Turn off the lighting circuit's breaker, lock it off if you can, and prove the switch is dead with a proper voltage indicator before touching anything. A non-contact tester isn't enough. See safe isolation. Replacing a switch or light like for like isn't notifiable, but adding a new circuit is, and new lighting circuits in a home must be protected by a 30 mA RCD. If in doubt, use a registered electrician.

Wire colours

ConductorCurrent colours (since 2004)Old colours (before 2006)
Line (live)BrownRed
NeutralBlueBlack
Protective conductor (earth)Green and yellow (bare in twin and earth, sleeved green and yellow at terminals)Green and yellow (bare in cable)
Three-core cable for two-way switchingBrown, black and greyRed, yellow and blue

The new colours came in with Amendment 2 to BS 7671:2001 in 2004, and were required for all new work from April 2006. Old colours on an existing installation aren't a defect, but where old and new meet there should be a warning notice.

In a switch drop, one core carries the switched line, which is live when the switch is on. It's usually the blue (or, in old wiring, black) core, so it should be sleeved or taped brown (or red) at both ends to show it's a line conductor, not a neutral. Lots of older installations miss this, so never assume a blue or black core is a safe neutral.

One-way switching

One switch controls one light. With a twin and earth switch drop from a loop-in ceiling rose:

  • At the switch: brown goes to COM (common), blue sleeved brown goes to L1, and the bare earth, sleeved green and yellow, goes to the earth terminal of the back box, and to the faceplate if it's metal. A one-way switch only needs those two terminals; a two-way switch used as one-way leaves L2 empty.
  • At the ceiling rose there are usually four groups of terminals:
    • Loop (permanent line): the brown of the supply cable in, the brown of the cable out to the next light, and the brown of the switch drop.
    • Neutral: the blues of the supply in and out, and the blue of the flex to the lampholder.
    • Switched line: the blue (sleeved brown) from the switch drop and the brown of the flex to the lampholder.
    • Earth: all the cpcs, sleeved green and yellow, and the flex's earth if the light fitting is Class I (metal).

Older installations sometimes use junction boxes instead of loop-in roses. The connections are the same idea: permanent line, neutral, switched line and earth.

Two-way switching

Two switches control one light, for example at the top and bottom of the stairs. The common UK method uses a twin and earth drop to the first switch and a three-core and earth cable between the switches:

  • Switch 1: the drop's brown (permanent line) goes to COM. The three-core's grey and black go to L1 and L2. The three-core's brown and the drop's blue are joined in a connector; together they carry the switched line back to the light.
  • Switch 2: grey and black go to L1 and L2 (grey to the same terminal number as at switch 1), and the three-core's brown goes to COM.
  • The grey and black wires between the switches are called strappers. Sleeve them brown, because they're line conductors. If grey and black are swapped at one switch it still works; it just flips which position is on.
  • Join all the earths at each switch.

For three or more switches, an intermediate switch goes between the two-way switches. It has four terminals, the strappers from each side go into it, and it crosses them over when you press it.

Why there's usually no neutral at the switch

Because a switch only interrupts the line conductor, a standard switch drop doesn't bring a neutral down to the switch. That matters if you want a smart switch or some electronic dimmers: many of them need a neutral to power their own electronics. Check the product's instructions. Some are made for "no neutral" installations, but those can make LED lamps flicker or glow faintly when off. Never use the earth as a neutral.

Dimmers and LED lamps

  • Use a dimmer rated for LED loads and check its minimum and maximum load. Many are rated much lower for LEDs than for old filament lamps.
  • Use dimmable LED lamps. Non-dimmable lamps on a dimmer can buzz, flicker and fail early.
  • A metal dimmer plate and a metal back box must be earthed, and a dimmer's heat needs space, so check the box depth.

Testing after the work

An electrician checks the cpc reaches the switch and light (R1+R2 testing), that the switch is in the line conductor (polarity), and the insulation resistance, then tests the RCD. If you've done it yourself, at least confirm the lamp holder's centre contact or the switched terminal is only live with the switch on, using a proper voltage indicator.