Most UK lighting is wired with "loop-in" ceiling roses and a switch drop: a cable that runs down the wall from the ceiling rose to the switch. Knowing how it fits together makes it much easier to swap a switch safely, fit a dimmer, or understand what you're looking at.
Wire colours
| Conductor | Current colours (since 2004) | Old colours (before 2006) |
|---|---|---|
| Line (live) | Brown | Red |
| Neutral | Blue | Black |
| Protective conductor (earth) | Green and yellow (bare in twin and earth, sleeved green and yellow at terminals) | Green and yellow (bare in cable) |
| Three-core cable for two-way switching | Brown, black and grey | Red, yellow and blue |
The new colours came in with Amendment 2 to BS 7671:2001 in 2004, and were required for all new work from April 2006. Old colours on an existing installation aren't a defect, but where old and new meet there should be a warning notice.
In a switch drop, one core carries the switched line, which is live when the switch is on. It's usually the blue (or, in old wiring, black) core, so it should be sleeved or taped brown (or red) at both ends to show it's a line conductor, not a neutral. Lots of older installations miss this, so never assume a blue or black core is a safe neutral.
One-way switching
One switch controls one light. With a twin and earth switch drop from a loop-in ceiling rose:
- At the switch: brown goes to
COM(common), blue sleeved brown goes toL1, and the bare earth, sleeved green and yellow, goes to the earth terminal of the back box, and to the faceplate if it's metal. A one-way switch only needs those two terminals; a two-way switch used as one-way leavesL2empty. - At the ceiling rose there are usually four groups of terminals:
- Loop (permanent line): the brown of the supply cable in, the brown of the cable out to the next light, and the brown of the switch drop.
- Neutral: the blues of the supply in and out, and the blue of the flex to the lampholder.
- Switched line: the blue (sleeved brown) from the switch drop and the brown of the flex to the lampholder.
- Earth: all the cpcs, sleeved green and yellow, and the flex's earth if the light fitting is Class I (metal).
Older installations sometimes use junction boxes instead of loop-in roses. The connections are the same idea: permanent line, neutral, switched line and earth.
Two-way switching
Two switches control one light, for example at the top and bottom of the stairs. The common UK method uses a twin and earth drop to the first switch and a three-core and earth cable between the switches:
- Switch 1: the drop's brown (permanent line) goes to
COM. The three-core's grey and black go toL1andL2. The three-core's brown and the drop's blue are joined in a connector; together they carry the switched line back to the light. - Switch 2: grey and black go to
L1andL2(grey to the same terminal number as at switch 1), and the three-core's brown goes toCOM. - The grey and black wires between the switches are called strappers. Sleeve them brown, because they're line conductors. If grey and black are swapped at one switch it still works; it just flips which position is on.
- Join all the earths at each switch.
For three or more switches, an intermediate switch goes between the two-way switches. It has four terminals, the strappers from each side go into it, and it crosses them over when you press it.
Why there's usually no neutral at the switch
Because a switch only interrupts the line conductor, a standard switch drop doesn't bring a neutral down to the switch. That matters if you want a smart switch or some electronic dimmers: many of them need a neutral to power their own electronics. Check the product's instructions. Some are made for "no neutral" installations, but those can make LED lamps flicker or glow faintly when off. Never use the earth as a neutral.
Dimmers and LED lamps
- Use a dimmer rated for LED loads and check its minimum and maximum load. Many are rated much lower for LEDs than for old filament lamps.
- Use dimmable LED lamps. Non-dimmable lamps on a dimmer can buzz, flicker and fail early.
- A metal dimmer plate and a metal back box must be earthed, and a dimmer's heat needs space, so check the box depth.
Testing after the work
An electrician checks the cpc reaches the switch and light (R1+R2 testing), that the switch is in the line conductor (polarity), and the insulation resistance, then tests the RCD. If you've done it yourself, at least confirm the lamp holder's centre contact or the switched terminal is only live with the switch on, using a proper voltage indicator.
Sources
The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.
- BS 7671 Table 51 and Regulation 514.14.1: identification of conductors and the notice where old and new colours meet (IET, paid standard)
- Electrical Safety First Best Practice Guide 2: Safe isolation (Issue 4.2, 2024)
- Electrical Safety First Best Practice Guide 4: Electrical installation condition reporting, classification codes (Issue 7.4, August 2026)
- HSE GS38: Electrical test equipment for use on low voltage electrical systems