UK cable colours cheat sheet

Printable one-page chart of UK cable core colours, new and old, for single-phase, three-phase and two-way switching.

Full guide

UK cable colours cheat sheet ohmandtoken.com
ConductorSince 2004 (required from April 2006)Before
Line (single-phase)BrownRed
NeutralBlueBlack
Protective conductorGreen and yellowGreen and yellow
Three-phase lines L1, L2, L3Brown, black, greyRed, yellow, blue
Three-core and earth (two-way switching)Brown, black, greyRed, yellow, blue
  • Sleeve the blue core of a switch drop brown, because it's a switched line, not a neutral.
  • Strappers between two-way switches are line conductors too: sleeve them brown.
  • Where old and new colours meet, fit a warning notice. Old colours alone aren't a defect.
  • Bare cpcs in twin and earth are sleeved green and yellow at terminations.

Sources:

  • BS 7671:2018+A4:2026 Table 51 (IET, paid)

Always check against your own copy of the current documents. Mains work must be carried out by a competent person.

Why the colours changed

The UK moved to the harmonised European core colours so that fixed wiring matches flexible cords, which have used brown, blue and green and yellow since the 1970s. The new colours could be used from 31 March 2004 and became the only option for new work from 31 March 2006, so most homes wired or extended around then have both.

The trap in mixed three-phase wiring

The colours that cause trouble are black and blue, because both changed meaning. In old wiring, black is the neutral and blue is line 3. In new wiring, black is line 2 and blue is the neutral. Where old and new cables meet in the same enclosure, never assume: identify each conductor by testing and by where it goes, then mark it.

The warning notice

Where an installation has wiring to both colour schemes, BS 7671 asks for a notice at or near the consumer unit or distribution board. It warns that the installation has wiring colours to two versions of BS 7671 and that great care is needed to identify every conductor before any extension, alteration or repair.

Marking by number or letter

Colour isn't the only accepted way to identify a conductor. Cores can also be identified with numbers or letters, such as L1, L2, L3 and N, which is common in control panels and on multicore cables with numbered cores.