A portable appliance tester (PAT tester) checks that electrical equipment is still safe to use: that the earth connection is sound, the insulation is good and nothing is leaking current where it shouldn't. In the UK, testing usually follows the IET's Code of Practice for In-service Inspection and Testing of Electrical Equipment.
The short answer
- Testing a few items at home or in a small office: a handheld with measured values, such as the Seaward PrimeTest 100 or Megger PAT150.
- Testing for a living: a downloading tester with memory, barcode support and reports, such as the Seaward Apollo 500+ or 600+, or the Megger PAT420.
- Testing 110 V site tools: you need a tester that supports 110 V, such as the Megger PAT420 or PAT450, or an adaptor for your tester.
Our picks: professional, mid-range and entry
Some shop links are affiliate links (Amazon UK, Tooled Up): if you buy through one we may earn a small commission, at no extra cost to you. As an Amazon Associate I earn from qualifying purchases. It never changes which products we recommend, and no shop has paid to be included.
Seaward Apollo 600+
Professional testers who need records, photos and risk assessments.
- Stores up to 50,000 records plus 2,000 photos (Apollo 500+: 10,000)
- Built-in camera and risk assessment tools
- Bluetooth transfer to a PC; USB lead download (and USB flash drive on the 600+)
- Earth continuity, insulation, touch current, alternative leakage, load, RCD tests
Why we picked it: Seaward's flagship, with on-board reporting and proof of visual inspection.
Megger PAT150R
Small businesses and in-house testers who want real numbers, with a rechargeable battery.
- Earth continuity at 200 mA, both polarities
- Insulation at 250 V or 500 V
- Substitute and mains-powered leakage, touch current
- Tests 10 mA and 30 mA portable RCDs
- Adjustable pass limits; the plain PAT150 is the same tester, sold to run on AA batteries
Check price atRS
Seaward PrimeTest 100
Low-volume testing with measured values and a pass or fail.
- Earth continuity at 200 mA, 0.00 to 19.99 Ω
- Insulation at 250 V or 500 V
- Substitute leakage at 40 V, 0.1 to 5.00 mA
- IEC lead test and mains socket check
- Six AA batteries; works with Seaward's PATMobile app
Why we picked it: Simple push-button test sequences, with measured values rather than just a pass or fail.
Megger PAT420
Contractors who meet 110 V site equipment.
- 230 V and 110 V operation
- Earth bond at 200 mA, 10 A and 25 A
- Insulation at 250 V and 500 V; substitute, differential and touch leakage
- Portable RCD and extension lead tests
- 10,000 results with USB download
Watch out: The PAT450 adds 1.5 kV and 3 kV flash testing, for tool hire and service workshops.
The tests a PAT tester does
- Earth continuity (bond): checks the resistance from the plug's earth pin to exposed metal on a Class I appliance. Most handhelds use 200 mA, which is safe for equipment that higher currents could damage. Some testers also offer 10 A or 25 A.
- Insulation resistance: a 500 V dc test between live parts and earth or exposed metal. A 250 V option suits surge-protected and IT equipment.
- Leakage: substitute (alternative) leakage runs at low voltage without mains, so the appliance doesn't switch on. Differential and touch current tests run on mains, with the appliance working.
- Extension leads and portable RCDs: polarity and RCD trip tests for leads and plug-in RCDs.
Class II (double insulated) equipment has no earth to test, so its test sequence skips earth continuity.
What to look for
Pass/fail only, or measured values
Pass/fail testers are quick, but measured values let you spot a reading that's drifting towards a fail. All four picks above show measurements.
Records
If you test for other people, you'll need records. Built-in memory with download, barcode scanning and label printing save hours on large jobs. Handhelds like the PrimeTest 100 record through a phone app.
110 V and three-phase
Construction sites use 110 V tools. Check the tester supports 110 V directly or through an adaptor. Three-phase equipment needs adaptors too.
Calibration and training
Testers should be calibrated, typically yearly. Training to the IET Code of Practice (for example City & Guilds 2377) matters more than the tester you pick.
Before you buy: a quick checklist
- Measured values, not only pass or fail.
- Earth bond at 200 mA (and 10 A or 25 A if a customer asks for it).
- Insulation at 500 V and 250 V; substitute and mains leakage.
- Portable RCD and extension lead tests.
- Memory, download or app if you test for other people; 110 V if you test site tools.
Questions people ask
How often should appliances be tested?
Can I PAT test my own equipment?
What's the difference between PAT testers and installation testers?
Sources
The main references behind this guide.
- HSE: Maintaining portable electrical equipment (FAQs on PAT)
- IET Wiring Matters: the 5th edition of the Code of Practice for In-service Inspection and Testing of Electrical Equipment (the Code itself is paid)
- Seaward Apollo 400+, 500+ and 600+ datasheet
- Megger PAT400 series datasheet
- Megger PAT120, PAT150 and PAT150R datasheet (Farnell copy)
- Seaward PrimeTest 100 datasheet (Farnell copy)