Buying guide: PAT testers for in-service testing of electrical equipment

A portable appliance tester with a 13 A test socket, display reading PASS, keypad and earth bond lead
Beginner
How we wrote this: we haven't tested these instruments hands-on for this guide. Every figure comes from the manufacturer's own specifications (a few via distributor copies of the datasheet), linked under Sources, checked on 22 November 2026. Models get updated and replaced, so check the current version before you buy.

A portable appliance tester (PAT tester) checks that electrical equipment is still safe to use: that the earth connection is sound, the insulation is good and nothing is leaking current where it shouldn't. In the UK, testing usually follows the IET's Code of Practice for In-service Inspection and Testing of Electrical Equipment.

Is PAT testing a legal requirement? Not as such. The HSE says the law requires electrical equipment to be maintained so it's safe, but doesn't say how or how often. A visual inspection finds most faults, and testing frequency should depend on risk. Many businesses use PAT testing as a sensible way to show their equipment is maintained.

The short answer

  • Testing a few items at home or in a small office: a handheld with measured values, such as the Seaward PrimeTest 100 or Megger PAT150.
  • Testing for a living: a downloading tester with memory, barcode support and reports, such as the Seaward Apollo 500+ or 600+, or the Megger PAT420.
  • Testing 110 V site tools: you need a tester that supports 110 V, such as the Megger PAT420 or PAT450, or an adaptor for your tester.

Our picks: professional, mid-range and entry

Some shop links are affiliate links (Amazon UK, Tooled Up): if you buy through one we may earn a small commission, at no extra cost to you. As an Amazon Associate I earn from qualifying purchases. It never changes which products we recommend, and no shop has paid to be included.

Professional pick

Seaward Apollo 600+

Professional testers who need records, photos and risk assessments.

  • Stores up to 50,000 records plus 2,000 photos (Apollo 500+: 10,000)
  • Built-in camera and risk assessment tools
  • Bluetooth transfer to a PC; USB lead download (and USB flash drive on the 600+)
  • Earth continuity, insulation, touch current, alternative leakage, load, RCD tests

Why we picked it: Seaward's flagship, with on-board reporting and proof of visual inspection.

Check price atAmazon UKCPCRS

Mid-range pick

Megger PAT150R

Small businesses and in-house testers who want real numbers, with a rechargeable battery.

  • Earth continuity at 200 mA, both polarities
  • Insulation at 250 V or 500 V
  • Substitute and mains-powered leakage, touch current
  • Tests 10 mA and 30 mA portable RCDs
  • Adjustable pass limits; the plain PAT150 is the same tester, sold to run on AA batteries

Check price atRS

Entry pick

Seaward PrimeTest 100

Low-volume testing with measured values and a pass or fail.

  • Earth continuity at 200 mA, 0.00 to 19.99 Ω
  • Insulation at 250 V or 500 V
  • Substitute leakage at 40 V, 0.1 to 5.00 mA
  • IEC lead test and mains socket check
  • Six AA batteries; works with Seaward's PATMobile app

Why we picked it: Simple push-button test sequences, with measured values rather than just a pass or fail.

Check price atAmazon UKCPCRS

Also consider

Megger PAT420

Contractors who meet 110 V site equipment.

  • 230 V and 110 V operation
  • Earth bond at 200 mA, 10 A and 25 A
  • Insulation at 250 V and 500 V; substitute, differential and touch leakage
  • Portable RCD and extension lead tests
  • 10,000 results with USB download

Watch out: The PAT450 adds 1.5 kV and 3 kV flash testing, for tool hire and service workshops.

Check price atAmazon UKRS

The tests a PAT tester does

  • Earth continuity (bond): checks the resistance from the plug's earth pin to exposed metal on a Class I appliance. Most handhelds use 200 mA, which is safe for equipment that higher currents could damage. Some testers also offer 10 A or 25 A.
  • Insulation resistance: a 500 V dc test between live parts and earth or exposed metal. A 250 V option suits surge-protected and IT equipment.
  • Leakage: substitute (alternative) leakage runs at low voltage without mains, so the appliance doesn't switch on. Differential and touch current tests run on mains, with the appliance working.
  • Extension leads and portable RCDs: polarity and RCD trip tests for leads and plug-in RCDs.

Class II (double insulated) equipment has no earth to test, so its test sequence skips earth continuity.

What to look for

Pass/fail only, or measured values

Pass/fail testers are quick, but measured values let you spot a reading that's drifting towards a fail. All four picks above show measurements.

Records

If you test for other people, you'll need records. Built-in memory with download, barcode scanning and label printing save hours on large jobs. Handhelds like the PrimeTest 100 record through a phone app.

110 V and three-phase

Construction sites use 110 V tools. Check the tester supports 110 V directly or through an adaptor. Three-phase equipment needs adaptors too.

Calibration and training

Testers should be calibrated, typically yearly. Training to the IET Code of Practice (for example City & Guilds 2377) matters more than the tester you pick.

Before you buy: a quick checklist

  • Measured values, not only pass or fail.
  • Earth bond at 200 mA (and 10 A or 25 A if a customer asks for it).
  • Insulation at 500 V and 250 V; substitute and mains leakage.
  • Portable RCD and extension lead tests.
  • Memory, download or app if you test for other people; 110 V if you test site tools.

Questions people ask

How often should appliances be tested?
It depends on the equipment and how it's used. The IET Code of Practice gives suggested starting intervals, and the HSE's guidance says to base it on risk: a kettle in a café needs checking more often than a desk monitor.
Can I PAT test my own equipment?
Yes, if you're competent to do it. The HSE says the person doing it needs the right knowledge and training, and for simple pass/fail testers that can be an employee who has been trained.
What's the difference between PAT testers and installation testers?
PAT testers test equipment through its plug. Installation testers (MFTs) test the fixed wiring. They're different jobs with different tests.