The formula
Motors, transformers and fluorescent ballasts draw reactive power to build their magnetic fields. Capacitors supply reactive power of the opposite sign, so fitting them near the load means less of it flows through the supply. The reactive power the capacitors must provide is:
Qc = P × (tan φ1 − tan φ2)
where P is the real power, φ1 = arccos of the present power factor and φ2 = arccos of the target.
Capacitance
- Single-phase:
C = Qc / (2πf V²). - Three-phase, delta: each of the three capacitors sees the line voltage, so
C = Qc / (3 × 2πf VL²). - Three-phase, star: each sees VL / √3, so it needs three times the capacitance:
C = Qc / (2πf VL²). That's why banks are usually connected in delta.
Worked example. The Schneider Electric Electrical Installation Guide's example: 100 kW at a power factor of 0.75, raised to 0.93. tan φ goes from 0.882 to 0.395, so Qc = 100 × (0.882 − 0.395) = 48.7 kvar, which the guide rounds to about 48 kvar. On 400 V, 50 Hz in delta, that's 323 µF per capacitor.
Things to know
- Aim for about 0.95, not 1. Over-correcting gives a leading power factor, which can cause overvoltage when the load is light.
- Capacitors and the supply's inductance form a resonant circuit. Where there are a lot of harmonics, from variable-speed drives for example, use detuned banks with series reactors, and get the system assessed.
- Capacitors keep their charge after switching off. Banks must have discharge resistors, and you should check they're discharged before touching them. See the capacitor discharge calculator.
- Correcting a single motor at its terminals has its own rules, because the capacitor can make the motor self-excite when it's switched off. Follow the motor and capacitor makers' guidance on the maximum kvar.