The formulas
- Stored energy:
E = ½ C V², in joules. - Through a resistor R, the voltage falls exponentially:
V(t) = V₀ e−t / RC. So the time to fall to a safe voltage Vs ist = RC × ln(V₀ / Vs). - Rearranged for a bleeder resistor that reaches Vs in time t:
R = t / (C × ln(V₀ / Vs)). - The resistor's peak power is at the start:
P = V₀² / R. Its average power is much lower, but it must also handle the voltage itself, so use a resistor or a chain of resistors rated for V₀.
Worked example. A 470 µF capacitor charged to 400 V stores ½ × 0.00047 × 400² = 37.6 J. Through 100 kΩ, the time constant is 47 s, and it takes 47 × ln(400 ÷ 50) = 97.7 s to fall below 50 V. To get below 50 V in 60 s, the bleeder needs to be 61.4 kΩ or less, dissipating 2.6 W at the start.
Staying safe
- Even a few joules at a high voltage can give a dangerous shock. Always measure the voltage across the capacitor before touching it, even when a bleeder is fitted, because resistors can fail open.
- Standards set their own limits for how fast equipment must discharge and to what voltage. Check the one that applies to your work.
- Don't short a large charged capacitor with a screwdriver. The current can weld metal, throw sparks and damage the capacitor. Use a suitable resistor.