Full-load current
- Three-phase:
I = S / (√3 × VL), with S in VA and VL the line-to-line voltage. - Single-phase:
I = S / V.
Fault current on the secondary
A transformer's percentage impedance (Z %) is the share of rated voltage needed on the primary to drive full-load current through a short-circuited secondary. So with full voltage applied, the short-circuit current is:
Isc = Ifull load × 100 / Z %
This assumes the supply feeding the transformer has no impedance of its own, called the infinite bus method. Real fault current is a little lower, so this is the safe upper figure to compare with the breaking capacity of switchgear on the secondary.
Things to know
- Adding cable between the transformer and the fault point reduces the fault current, often a lot on small cables. Work that out with the cable's impedance.
- Motors running at the time of a fault briefly feed current back into it, which adds to the transformer's contribution.
- The rating plate's impedance has a manufacturing tolerance, typically ±7.5 % or ±10 %. For worst-case fault levels, use the lowest likely value.