Transformer current and fault level calculator

Work out the full-load current on each side of a single or three-phase transformer, and the largest fault current it can deliver on its secondary.

  • Electrical tool
  • Runs in your browser
  • Tested 19 November 2026
  • Sources
Line to line for three-phase.
From the rating plate. Often 4 to 6 % for distribution transformers.

Full-load current

  • Three-phase: I = S / (√3 × VL), with S in VA and VL the line-to-line voltage.
  • Single-phase: I = S / V.

Fault current on the secondary

A transformer's percentage impedance (Z %) is the share of rated voltage needed on the primary to drive full-load current through a short-circuited secondary. So with full voltage applied, the short-circuit current is:

Isc = Ifull load × 100 / Z %

This assumes the supply feeding the transformer has no impedance of its own, called the infinite bus method. Real fault current is a little lower, so this is the safe upper figure to compare with the breaking capacity of switchgear on the secondary.

Worked example. From IAEI Magazine: a 1,500 kVA transformer with a 480 V secondary and 5.75 % impedance. Full-load current = 1,500,000 ÷ (1.732 × 480) = 1,804 A. Fault current = 1,804 × 100 ÷ 5.75 = 31,378 A, about 31.4 kA.

Things to know

  • Adding cable between the transformer and the fault point reduces the fault current, often a lot on small cables. Work that out with the cable's impedance.
  • Motors running at the time of a fault briefly feed current back into it, which adds to the transformer's contribution.
  • The rating plate's impedance has a manufacturing tolerance, typically ±7.5 % or ±10 %. For worst-case fault levels, use the lowest likely value.